40 CFR § 1066.615 - NOX intake-air humidity correction.

§ 1066.615 NOX intake-air humidity correction.

You may correct NOX emissions for intake-air humidity as described in this section if the standard-setting part allows it. See § 1066.605(c) for the proper sequence for applying the NOX intake-air humidity correction.

(a) For vehicles at or below 14,000 pounds GVWR, apply a correction for vehicles with reciprocating engines operating over specific test cycles as follows:

(1) Calculate a humidity correction using a time-weighted mean value for ambient humidity over the test interval. Calculate absolute ambient humidity, H, using the following equation:

H = 1000 · M H 2 O · p d · R H M air · ( p atmos p d · R H ) Eq. 1066.615-1

Where:
MH2O = molar mass of H2O.
pd = saturated vapor pressure at the ambient dry bulb temperature.
RH = relative humidity of ambient air
Mair = molar mass of air.
patmos = atmospheric pressure.
Example:
MH2O = 18.01528 g/mol
pd = 2.93 kPa
RH = 37.5% = 0.375
Mair = 28.96559 g/mol
patmos = 96.71 kPa

H = 1000 · 18.01528 · 2.93 · 0.375 28.96559 · ( 96.71 2.93 · 0.375 ) = 7.14741 g H 2 O vapor / kg dry air

(2) Use the following equation to correct measured concentrations to a reference condition of 10.71 grams H2O vapor per kilogram of dry air for the FTP, US06, LA-92, SC03, and HFET test cycles:

x NOxcor = x NOx · H s 1 0.0329 · ( H 10.71 ) Eq. 1066.615-2

Where:
χNOx = measured NOX emission concentration in the sample, after dry-to-wet and background corrections.
Hs = humidity scale. Set = 1 for FTP, US06, LA-92, and HFET test cycles. Set = 0.8825 for the SC03 test cycle.
H = ambient humidity, as determined in paragraph (a)(1) of this section.
Example:
H = 7.14741 g H2O vapor/kg dry air time weighted over the FTP test cycle
χNOx = 1.21 ppm

x NOxcor = 1.21 · 1 1 0.0329 · ( 7.14741 10.71 ) = 1.08305 ppm

(b) For vehicles above 14,000 pounds GVWR, apply correction factors as described in 40 CFR 1065.670.

[80 FR 9121, Feb. 19, 2015, as amended at 81 FR 74207, Oct. 25, 2016]