40 CFR Appendix Table 2 to Subpart LLLL of Part 60 - Table 2 to Subpart LLLL of Part 60—Emission Limits and Standards for New Multiple Hearth Sewage Sludge Incineration Units

Table 2 to Subpart LLLL of Part 60—Emission Limits and Standards for New Multiple Hearth Sewage Sludge Incineration Units
For the air pollutant You must meet this emission limit a Using these averaging methods and minimum sampling volumes or durations And determining compliance using this method
Particulate matter 60 milligrams per dry standard cubic meter 3-run average (collect a minimum volume of 0.75 dry standard cubic meters per run) Performance test (Method 5 at 40 CFR part 60, appendix A-3; Method 26A or Method 29 at 40 CFR part 60, appendix A-8).
Hydrogen chloride 1.2 parts per million by dry volume 3-run average (For Method 26, collect a minimum volume of 200 liters per run. For Method 26A, collect a minimum volume of 1 dry standard cubic meters per run) Performance test (Method 26 or 26A at 40 CFR part 60, appendix A-8).
Carbon monoxide 52 parts per million by dry volume 24-hour block average (using 1-hour averages of data) Continuous emissions monitoring system. (Performance Specification 4B of this part, using a low-range span of 100 ppm and a high-range span of 1000 ppm, and a relative accuracy of 0.5 ppm instead of 5 ppm specified in section 13.2. For the cylinder gas audit of Procedure 1, ±15% or 0.5 whichever is greater).
Dioxins/furans (total mass basis); or
Dioxins/furans (toxic equivalency basis) b
0.045 nanograms per dry standard cubic meter (total mass basis); or
0.0022 nanograms per dry standard cubic meter (toxic equivalency basis)
3-run average (collect a minimum volume of 3 dry standard cubic meters per run) Performance test (Method 23 at 40 CFR part 60, appendix A-7).
Mercury 0.15 milligrams per dry standard cubic meter 3-run average (For Method 29 and ASTM D6784-02 (Reapproved 2008), c collect a minimum volume of 1 dry standard cubic meters per run. For Method 30B, collect a minimum sample as specified in Method 30B at 40 CFR part 60, appendix A-8) Performance test (Method 29 at 40 CFR part 60, appendix A-8; Method 30B at 40 CFR part 60, appendix A-8; or ASTM D6784-02 (Reapproved 2008). c
Oxides of nitrogen 210 parts per million by dry volume 3-run average (Collect sample for a minimum duration of one hour per run) Performance test (Method 7 or 7E at 40 CFR part 60, appendix A-4).
Sulfur dioxide 26 parts per million by dry volume 3-run average (For Method 6, collect a minimum volume of 200 liters per run. For Method 6C, collect sample for a minimum duration of one hour per run) Performance test (Method 6 or 6C at 40 CFR part 40, appendix A-4; or ANSI/ASME PTC 19.10-1981. c
Cadmium 0.0024 milligrams per dry standard cubic meter 3-run average (collect a minimum volume of 1 dry standard cubic meters per run) Performance test (Method 29 at 40 CFR part 60, appendix A-8). Use GFAAS or ICP/MS for the analytical finish.
Lead 0.0035 milligrams per dry standard cubic meter 3-run average (collect a minimum volume of 1 dry standard cubic meters per run) Performance test (Method 29 at 40 CFR part 60, appendix A-8. Use GFAAS or ICP/MS for the analytical finish.
Fugitive emissions from ash handling Visible emissions of combustion ash from an ash conveying system (including conveyor transfer points) for no more than 5 percent of the hourly observation period Three 1-hour observation periods Visible emission test (Method 22 of appendix A-7 of this part).

a All emission limits are measured at 7 percent oxygen, dry basis at standard conditions.

b You have the option to comply with either the dioxin/furan emission limit on a total mass basis or the dioxin/furan emission limit on a toxic equivalency basis.

c Incorporated by reference, see § 60.17.