Ariz. Admin. Code § R9-10-1910 - Physical Plant, Environmental Services, and Safety Standards
A. An administrator
shall ensure that a counseling facility has either:
1. Both of the following:
a. A smoke detector installed in each hallway
of the counseling facility that is:
i.
Maintained in an operable condition;
ii. Either battery operated or, if hard-wired
into the electrical system of the outpatient treatment center, has a back-up
battery; and
iii. Tested monthly;
and
b. A portable,
operable fire extinguisher, labeled as rated at least 2A-10-BC by the
Underwriters Laboratories, that:
i. Is
available at the counseling facility;
ii. Is mounted in a fire extinguisher cabinet
or placed on wall brackets so that the top handle of the fire extinguisher is
not over five feet from the floor and the bottom of the fire extinguisher is at
least four inches from the floor;
iii. If a disposable fire extinguisher, is
replaced when its indicator reaches the red zone; and
iv. If a rechargeable fire extinguisher, is
serviced at least once every 12 months and has a tag attached to the fire
extinguisher that specifies the date of the last servicing and the name of the
servicing person; or
2. Both of the following that are tested and
serviced at least once every 12 months:
a. A
fire alarm system installed according to the National Fire Protection
Association 72: National Fire Alarm and Signaling Code, incorporated by
reference in
R9-10-104.01,
that is in working order; and
b. A
sprinkler system installed according to the National Fire Protection
Association 13: Standard for the Installation of Sprinkler Systems,
incorporated by reference in
R9-10-104.01,
that is in working order.
B. An administrator shall ensure that
documentation of a test required in subsection (A) is maintained for at least
12 months after the date of the test.
C. An administrator shall ensure that on a
counseling facility's premises:
1. Exit signs
are illuminated, if the local fire jurisdiction requires illuminated exit
signs;
2. Corridors and exits are
kept clear of any obstructions;
3.
A patient can exit through any exit during hours of clinical
operation;
4. An extension cord is
not used instead of permanent electrical wiring; and
5. Each electrical outlet and electrical
switch has a cover plate that is in good repair.
D. An administrator shall:
1. Obtain a fire inspection conducted
according to the time-frame established by the local fire department or the
State Fire Marshal,
2. Make any
repairs or corrections stated on the fire inspection report, and
3. Maintain documentation of a current fire
inspection.
E. An
administrator shall ensure that:
1. A
counseling facility's premises are:
a.
Sufficient to provide the counseling facility's scope of services;
b. Cleaned and disinfected to prevent,
minimize, and control illness and infection; and
c. Free from a condition or situation that
may cause an individual to suffer physical injury;
2. If a bathroom is on the premises, the
bathroom contains:
a. A working sink with
running water,
b. A working toilet
that flushes and has a seat,
c.
Toilet tissue,
d. Soap for hand
washing,
e. Paper towels or a
mechanical air hand dryer,
f.
Lighting, and
g. A means of
ventilation;
3. If a
bathroom is not on the premises, a bathroom is:
a. Available for a patient's use,
b. Located in a building in contiguous
proximity to the counseling facility, and
c. Free from a condition or situation that
may cause an individual using the bathroom to suffer a physical injury;
and
4. A tobacco
smoke-free environment is maintained on the premises.