Cal. Code Regs. Tit. 14, § 1254 - Minimum Clearance Provisions-PRC 4292
The firebreak clearances required by PRC 4292 are applicable within an imaginary cylindroidal space surrounding each pole or tower on which a switch, fuse, transformer or lightning arrester is attached and surrounding each dead end or corner pole unless such pole or tower is exempt from minimum clearance requirements by provisions of 14 CCR 1255 or PRC 4296. The radius of the cylindroid is 3.1 m (10 feet) measured horizontally from the outer circumference of the specified pole or tower with height equal to the distance from the intersection of the imaginary vertical exterior surface of the cylindroid with the ground to an intersection with a horizontal plane passing through the highest point at which a conductor is attached to such pole or tower. (See Figure 2 this Article.) Flammable vegetation and materials located wholly or partially within the firebreak space shall be treated as follows: