Cal. Code Regs. Tit. 19, § 567 - Distribution of Fire Extinguishers
(a) The
minimum number of fire extinguishers needed to protect a property shall be
determined as outlined in this section. Additional extinguishers may be
installed to provide more suitable protection.
(b) Fire extinguishers shall be provided for
the protection of both the building structure and the occupancy hazards
contained therein.
(c) Required
building protection shall be provided by fire extinguishers suitable for Class
A fires.
(d) Occupancy hazard
protection shall be provided by fire extinguishers suitable for such Class A,
B, C, D, or K fire potentials as may be present.
(e) Extinguishers provided for building
protection may be considered also for the protection of occupancies having a
Class A fire potential.
(f)
Buildings having an occupancy hazard subject to Class B and/or Class C fires
shall have a standard complement of Class A fire extinguishers for building
protection, plus additional Class B and/or Class C extinguishers. Where fire
extinguishers have more than one letter classification (such as 2-A:20-B:C),
they may be considered to satisfy the requirements of each letter class. When
using multi-purpose extinguishers for the protection of Class B hazards, the
maximum travel distances described in Table 2 must be observed.
(g) Rooms or areas shall be classified
generally as light (low) hazard, ordinary (moderate) hazard, or extra (high)
hazard. Limited areas of greater or lesser hazard shall be protected as
required.
(h) On each floor level,
the area protected and the travel distances shall be based on fire
extinguishers installed in accordance with Tables 2 and 3.
(i) Fire extinguishers shall not be
obstructed or obscured from view.
EXCEPTION: In large rooms, and in certain locations where visual obstruction cannot be completely avoided, means shall be provided to indicate the fire extinguisher's location.
(j) Fire extinguishers shall be conspicuously
located along normal paths of travel where they will be readily accessible and
immediately available in the event of a fire.
(k) Portable fire extinguishers containing
halogenated agents shall conform to confined space volume requirement warnings
contained on the fire extinguisher nameplates.
(l) Wheeled fire extinguishers shall be used
for hazard protection in areas in which a fire risk assessment has shown the
following:
(1) High hazard areas are
present.
(2) Limited availability
of personnel is present; thereby requiring an extinguisher that has the
following features:
(A) High agent flow
rate
(B) Increased agent stream
range
(C) Increased agent
capacity
(m)
Where wheeled extinguishers are installed, aisles and doorways through which
such extinguishers are to be moved shall have a clear and unobstructed width
not less than one foot (1 ft.) wider than the overall width of the
extinguisher.
Notes
2. Repealer and new section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
3. Amendment filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
4. Amendment of subsection (f) filed 11-21-2002; operative 1-1-2003 (Register 2002, No. 47).
5. Change without regulatory effect adding new subsection (k) filed 7-25-2006 pursuant to section 100, title 1, California Code of Regulations (Register 2006, No. 30).
6. New subsections (k)-(l)(2)(C), subsection relettering and amendment of NOTE filed 7-17-2013; operative 10-1-2013 (Register 2013, No. 29).
Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160 and 13190, Health and Safety Code.
2. Repealer and new section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
3. Amendment filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
4. Amendment of subsection (f) filed 11-21-2002; operative 1-1-2003 (Register 2002, No. 47).
5. Change without regulatory effect adding new subsection (k) filed 7-25-2006 pursuant to section 100, title 1, California Code of Regulations (Register 2006, No. 30).
6. New subsections (k)-(l)(2)(C), subsection relettering and amendment of Note filed 7-17-2013; operative 10-1-2013 (Register 2013, No. 29).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.