Cal. Code Regs. Tit. 22, § 64572 - Water Main Separation
(a) New water mains and new supply lines
shall not be installed in the same trench as, and shall be at least 10 feet
horizontally from and one foot vertically above, any parallel pipeline
conveying:
(1) Untreated sewage,
(2) Primary or secondary treated
sewage,
(3) Disinfected
secondary-2.2 recycled water (defined in section
60301.220),
(4) Disinfected secondary-23 recycled water
(defined in section
60301.225), and
(5) Hazardous fluids such as fuels,
industrial wastes, and wastewater sludge.
(b) New water mains and new supply lines
shall be installed at least 4 feet horizontally from, and one foot vertically
above, any parallel pipeline conveying:
(1)
Disinfected tertiary recycled water (defined in section
60301.230), and
(2) Storm drainage.
(c) New supply lines conveying raw water to
be treated for drinking purposes shall be installed at least 4 feet
horizontally from, and one foot vertically below, any water main.
(d) If crossing a pipeline conveying a fluid
listed in subsection (a) or (b), a new water main shall be constructed no less
than 45-degrees to and at least one foot above that pipeline. No connection
joints shall be made in the water main within eight horizontal feet of the
fluid pipeline.
(e) The vertical
separation specified in subsections (a), (b), and (c) is required only when the
horizontal distance between a water main and pipeline is less than ten
feet.
(f) New water mains shall not
be installed within 100 horizontal feet of the nearest edge of any sanitary
landfill, wastewater disposal pond, or hazardous waste disposal site, or within
25 horizontal feet of the nearest edge of any cesspool, septic tank, sewage
leach field, seepage pit, underground hazardous material storage tank, or
groundwater recharge project site.
(g) The minimum separation distances set
forth in this section shall be measured from the nearest outside edge of each
pipe barrel.
(h) With State Board
approval, newly installed water mains may be exempt from the separation
distances in this section, except subsection (f), if the newly installed main
is:
(1) less than 1320 linear feet,
(2) replacing an existing main, installed in
the same location, and has a diameter no greater than six inches more than the
diameter of the main it is replacing, and
(3) installed in a manner that minimizes the
potential for contamination, including, but not limited to:
(A) sleeving the newly installed main,
or
(B) utilizing upgraded piping
material
Notes
2. Change without regulatory effect amending subsection (h) and NOTE filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).
Note: Authority cited: Sections 116271, 116350 and 116375, Health and Safety Code. Reference: Sections 116275 and 116375, Health and Safety Code.
2. Change without regulatory effect amending subsection (h) and Note filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.