Cal. Code Regs. Tit. 22, § 73649 - Water Supply and Plumbing
(a)
Where water for human consumption is from an independent source, it shall be
subjected to bacteriological analysis by the local health department, the State
Department or a licensed commercial laboratory at least every three months. A
copy of the most recent laboratory report shall be available for
inspection.
(b) Plumbing and
drainage facilities shall be maintained in compliance with Part 5, Title 24,
California Administrative Code, Basic Plumbing Requirements. Drinking water
supplies shall comply with Group 4, Subchapter 1, Chapter 5, Division T17, Part
6, of Title 24, California Administrative Code.
(c) Vacuum breakers shall be maintained in
operating condition where required by Section T17-210 (c), Division T17, Part
6, Title 24, California Administrative Code.
(d) Hot water temperature controls shall be
maintained to automatically regulate temperature of hot water delivered to
plumbing fixtures used by patients to attain a hot water temperature not less
than 40.5°C (105°F) and not more than 48.9°C (120°F).
(e) Hot water at a minimum temperature of
83°C (180°F) shall be maintained at the final rinse section of
dishwashing facilities unless alternate methods are approved by the
Department.
(f) Taps delivering
water at 51.6°C (125°F) or above shall be prominently identified by
warning signs in letters at least five centimeters (two inches) high. Special
precautions shall be taken to prevent the scalding of patients.
(g) Grab bars readily accessible to patients
shall be maintained at each toilet, bathtub and shower used by patients, where
required by Section T17-212 (b), Division T17, Part 6, of Title 24, California
Administrative Code.
(h) Toilet,
handwashing and bathing facilities shall be maintained in operating condition
and in the number and types specified in construction requirements in effect at
the time the building or unit was constructed. Those handwashing facilities
listed in Section T17-208, Division T17, Part 6, Title 24, California
Administrative Code, shall not be equipped with aerators.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.