Cal. Code Regs. Tit. 8, § 2827 - Raceways (or Ducts) Below Ground
EXCEPTION: No. 1: Direct buried conduits to contain cables for series street lighting circuits operating at less than 7,500 volts shall be installed at a depth of at least 24 inches below the surface under which they are located.
EXCEPTION: No. 2: Where it is impractical to obtain the depth of cover specified, the depth shall be permitted to be reduced, provided that the duct has sufficient strength itself or adequate protection is installed above the duct to prevent damage to the duct system by any surface traffic.
(Title 24, Part 3, Section 3-710 - 3(b).)
(Title 24, Part 3, Section 300-6.)