Cal. Code Regs. Tit. 8, § 2934 - Elevation of Unguarded Live Parts

Exposed energized parts above workspace and above areas where persons may normally walk or stand shall be maintained at elevations not less than that required by the following table:

Table 2934 - Elevation of Unguarded Live Parts above Workspace

NOMINAL VOLTAGE

ELEVATION

BETWEENPHASES

Feet

Meters

601-7500 9.01 2.81
7501-35kV 9.0 2.8
Over 35kv 9 feet + 0.37 inch/kv 2.8 + 9.5 mm/kV
above 35kv over 35 kV

1 The minimum elevation may be 8.5 ft. (2.6 m) for installations built before April 1, 2009.