Cal. Code Regs. Tit. 8, § 2940.18 - Current Transformer Secondaries

(a) The employer shall ensure that employees do not open the secondary of a current transformer while the transformer is energized. If the employer cannot deenergize the primary of the current transformer before employees perform work on an instrument, a relay, or other section of a current transformer secondary circuit, the employer shall bridge the circuit so that the current transformer secondary does not experience an open-circuit condition.

Notes

Cal. Code Regs. Tit. 8, § 2940.18
1. New section filed 2-27-2018; operative 4-1-2018 (Register 2018, No. 9).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.