Cal. Code Regs. Tit. 8, § 2940.9 - Protection from Backfeed Voltages
Before contacting the high voltage side of deenergized transformer(s), or conductor(s) connected thereto, all possible sources of backfeed shall be eliminated by:
(a)
disconnecting or grounding the high voltage side, or
(b) disconnecting or short circuiting the low
voltage side.
EXCEPTION: System(s) worked as energized.
Notes
2. Editorial correction of first paragraph (Register 95, No. 32).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
2. Editorial correction of first paragraph (Register 95, No. 32).