Cal. Code Regs. Tit. 8, § 2970 - Installation of Conductors

Conductors shall be installed as follows:

(a) Wiring Method. Conductors shall be installed in rigid metal conduit, in flexible metal conduit, in liquidtight flexible metal conduit, or in electrical metallic tubing.

(Title 24, Part 3, Section 600-31(a).)

(b) Conductors in Raceways. Where the conductors are covered with lead or other metal sheathing, the covering shall extend beyond the end of the raceway, and the surface of the cable shall not be injured where the covering terminates.

(Title 24, Part 3, Section 600-31(e).)