Cal. Code Regs. Tit. 8, § 3056 - Protection of Spaces Below Hoistways
(a) Protection of Usable Space Below
Hoistways. Where the space below the hoistway is used for a passageway, is
occupied by persons, or if unoccupied is not permanently sealed against access,
the following requirements shall be conformed to:
(1) The cylinder shall be supported by a
structure of sufficient strength to support the entire load that may be imposed
upon it; and
(2) No counterweights
will be permitted.
(3) The car
shall be provided with buffers of one of the following types:
(A) Oil buffers conforming to Section
3061(a).
(B) Spring buffers of a design which will not
be fully compressed when struck by the fully loaded car at the maximum speed
attained in the down direction.
(4) Car buffer supports shall be provided
which will withstand, without permanent deformation, the impact resulting from
buffer engagement by the car with its rated load at the maximum speed attained
in the down direction.
(b) Protection of Cylinders and Piping.
Cylinders and piping that pass through areas where vehicles may contact them
shall be protected by guards or barriers. (Title 24, Part 7, Section
7-3056)
Notes
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
Group II regulations apply to existing elevators installed prior to October 25, 1998. Italicized paragraphs, sentences, or phrases apply to all existing elevators while non-italicized apply to elevators installed after 1970 or after the date the regulation was adopted.