Cal. Code Regs. Tit. 19, div. 1, ch. 3, art. 7, tbl. 5 - Hydrostatic Test Interval for Extinguishers
| Extinguisher type | Test Interval (Years) | |
| Stored Pressure Water and/or Antifreeze/Loaded Stream | 5 | |
| AFFF (Aqueous Film Forming Foam) | 5 | |
| FFFP (Film Forming Fluoroprotein Foam) | 5 | |
| Wet Chemical | 5 | |
| Dry Chemical with Stainless Steel Shells | 5 | |
| Carbon Dioxide | 5 | |
| Dry Chemical, Stored Pressure with Mild Steel Shells, Brazed Brass Shells, or Aluminum Shells | 12 | |
| Dry Chemical, Cartridge and Cylinder-Operated, with Mild Steel Shells | 12 | |
| Halogenated Agents | 12 | |
| Dry Powder, stored pressure, cartridge- or cylinder-operated with mild steel shells | 12 | |
Notes
Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.