7 CCR 1101-15-3-1 - LPG Delivery

(a) Containers shall be filled only after determination from the point of transfer that the installation of the container and visible exterior piping system comply with the provisions of NFPA 58 and these regulations.
(b) It is permissible to fill an ASME tank whose nameplate or other marking is damaged, provided the following information can be determined:
(1) If the container is registered with the National Board and the facility can produce the Manufacturer's Data Report (U-1A and/or U-2A) form, the manufacturer's name and container's serial number must be legible.
(2) If the container is not a National Board-registered container, the manufacturer's name, the container's serial number, the ASME stamp and the pressure rating must be legible.
(c) If the nameplate or other marking is missing, delivery to the tank is prohibited. Refer to Section 2-5 of these regulations for instructions on re-attaching or re-placing nameplates.
(d) Delivery to a container with corrosion that appears to be greater than 1/3 of the thickness of the metal is prohibited.
(e) When noncompliance with the provisions of the incorporated codes is found, the container owner or user of record shall be notified in writing.

Notes

7 CCR 1101-15-3-1
40 CR 07, April 10, 2017, effective 5/1/2017 40 CR 17, September 10, 2017, effective 9/30/2017

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.