7 CCR 1101-15-3-1 - LPG Delivery
(a) Containers
shall be filled only after determination from the point of transfer that the
installation of the container and visible exterior piping system comply with
the provisions of NFPA 58 and these regulations.
(b) It is permissible to fill an ASME tank
whose nameplate or other marking is damaged, provided the following information
can be determined:
(1) If the container is
registered with the National Board and the facility can produce the
Manufacturer's Data Report (U-1A and/or U-2A) form, the manufacturer's name and
container's serial number must be legible.
(2) If the container is not a National
Board-registered container, the manufacturer's name, the container's serial
number, the ASME stamp and the pressure rating must be legible.
(c) If the nameplate or other
marking is missing, delivery to the tank is prohibited. Refer to Section 2-5 of
these regulations for instructions on re-attaching or re-placing
nameplates.
(d) Delivery to a
container with corrosion that appears to be greater than 1/3 of the thickness
of the metal is prohibited.
(e)
When noncompliance with the provisions of the incorporated codes is found, the
container owner or user of record shall be notified in writing.