7 CCR 1101-15-3-2 - Delivery after Interruption of Service
(a) When
delivery is made to an LPG container assembly that has had an interruption of
service as defined by these regulations, a leak check shall be performed
immediately after LPG is introduced into the piping.
(b) The leak check shall be performed
according to one of the methods set forth in Annex D (Suggested Method
of Checking for Leakage) of NFPA 54 or another method approved by the
division in advance.
(c) The
person performing the leak check shall document that the test was performed.
The documentation shall include, at minimum, the following information:
(1) Date the test was performed
(2) Test start time
(3) Test end time
(4) Name of person performing the
test
(5) Name of person's
employer
(6) Address and phone
number of person's employer
(7)
Type of test
(8) Test start
pressure and end pressure if a constant pressure is used
(d) Documentation of the leak check shall be
retained for a minimum of one year by the employer of the person who performed
the test.