8 CCR 1507-31, art. 6 - PERMIT APPLICATION SUBMITTAL TO THE DIVISION

6.1 Notification of Submittal to a Local Building Department
6.1.1 For projects that require a permit that will be reviewed and inspected by a local Building Department, the Business Entity shall notify the Division and the State licensing authority prior to beginning construction. Notification must include:
A) Name of project;
B) Location of project;
C) Scope of work of project;
D) Projected total cost of project;
E) Projected square footage of project;
E) Planned construction start and end dates;
F) Identification of Fire Code Official (Name of the Qualified Fire Department or the Division);
G) Identification of Building Code Official (Name of the Building Code Official or the Division);
H) A description of the proposed health services to be provided and the type of licensure being sought through the state licensing authority;
I) A copy of the Life Safety Code plan sheets submitted in the format as prescribed by the Division.
6.2 Permit Application Submittal to the Division
6.2.1 For all construction (including adding previously unlicensed space to a Health Facility license) or operational permits not covered under a Limited Scope Project permit as defined by this Article, the Business Entity shall submit a complete plan review application package to the Division for Life Safety Code compliance review. If there is not a local building department, the Business Entity shall also submit a complete plan review application package to the Division for Building Code compliance review.
6.2.2 The plan review application package must be submitted to the Division in the format defined by Division policy.
6.2.3 The building permit application package shall be concurrently submitted to the Division and to the local fire department. Either the Qualified Fire Department or the Division will review the submittal for compliance with the applicable codes. Permit issuance is contingent upon the review and approval of the submittal by the applicable Life Safety and/or Fire Code Officials. The Business Entity is required to contact the local fire department to determine the required submittal items not listed in this rule.
6.3 Plan Review and Permitting by the Division
6.3.1 The Division will notify the Business Entity if the permit application is incomplete.
6.3.2 The Building Code plan review will be completed by a qualified building plans examiner within the Division or by a qualified third-party reviewer contracted by the Division.
6.3.3 The Fire Code plan reviews will be completed by an individual qualified as a Fire Inspector III- Plans Examiner within the Division, qualified third-party reviewer contracted by the Division, or by the Qualified Fire Department.
6.3.4 The Life Safety Code plan reviews will be completed by an individual qualified as a Fire Inspector III- Plans Examiner and CMS Qualified Life Safety Code Inspector within the Division.
6.3.5 Upon completion of the code review, the Division will provide the Business Entity with a comprehensive list of corrections to be addressed prior to the issuance of a permit. This list of corrections should not be considered all-inclusive and may not be considered as approval of any condition in violation of applicable code. Once all corrections have been satisfactorily addressed, the Division will issue the permit.
6.4 Phased Construction
6.4.1 Upon request by the Business Entity, the Division may issue individual permits for demolition, construction of foundations, and construction of core and shell, or for individual phases of an overall project provided that construction documents for that portion of the building or structure being permitted have been submitted per Article 6.3. The holder of such permit for demolition or the construction of foundations or vertical construction may then proceed at the holder's own risk with building operation and without assurance that a permit for the entire structure will be granted. Issuance of this permit should not be considered all-inclusive and may not be considered as approval of any condition in violation of applicable codes.
6.5 Deferred Design/Build Submittals/Shop Drawings
6.5.1 Deferred design/build (shop drawing) submittals for fire protection and life safety systems are permitted; however, construction documents must provide sufficient information to show compliance with Fire and Life Safety Code requirements and coordination between fire systems and other building systems (i.e., HVAC systems, security systems).
6.5.2 Shop (Installation) drawings for fire protection and life safety systems shall be submitted to the Fire and Life Safety Code Official(s) for review and approval prior to beginning installation of the system.
A) Fire sprinkler and fire alarm shop drawings shall be submitted to the Fire and Life Safety Code Officials in accordance with the requirements of the adopted codes in the format as prescribed by the Division and the local fire department.
B) Shop (installation) drawings for other systems regulated by the Fire and Life Safety Codes shall be submitted to the Division in accordance the appropriate referenced standard for the system.
6.5.3 Minimum Qualifications for Fire Protection and Life Safety System Design and Installation
A) Fire Suppression Systems

Any installation, modification, alteration, or repair of a fire suppression system shall be in accordance with 8 CCR 1507-11- Colorado Fire Suppression program.

B) Fire Alarm Systems
(1) The design of any new system or alteration of an existing fire alarm system using the prescriptive requirements of NFPA 72 shall be performed by a person who is currently a professional engineer or qualified by NICET at a level III or level IV in fire protection engineering technologies- fire alarm systems, or another nationally recognized organization approved by the Division.
(2) The design of any new system or alteration of an existing fire alarm system using performance-based design methods as described by NFPA 72 or alternative materials and methods as described by the adopted Fire Code shall be performed by a person who is currently a professional engineer specializing in fire protection.
(3) The installation of a fire alarm system shall be performed by or supervised by a person who is currently qualified at a minimum of NICET level II in fire protection engineering technologies- fire alarm systems, or another nationally recognized organization approved by the Division.
C) Other Fire and Life Safety Protection Systems Regulated by the Building, Fire, or Life Safety Codes

The design and installation shall be performed by a company or individual with manufacturer- or factory-approved training for the specific system, or as otherwise required by the applicable code section or referenced standard.

6.6 Limited Scope Project Permit
6.6.1 In lieu of an individual Building, Fire, or Life Safety Code permit for each limited scope project, the Division may issue a Limited Scope Project Permit upon approved application for or renewal of a Certificate of Compliance. Permits for Limited Scope Projects expire concurrent with the Certificate of Compliance for the Health Facility. The Business Entity shall notify the Local Fire Department prior to the commencement of work conducted under a Limited Scope Project Permit.
6.6.2 Limited Scope Project Permits are restricted to those projects identified by the Division.
6.6.3 The Business Entity to whom a Limited Scope Project Permit is issued shall keep a detailed record, including stamped engineered drawings (if applicable), of all modifications made under such Permit.
6.6.4 All work completed under an Limited Scope Project Permit shall be inspected by a local building department inspector, a Third-Party Inspector, or a qualified tradesperson (as specified by local or state licensing requirements or the installation standards adopted by the Division [if applicable], the manufacturer's installation recommendations, or minimally a person with 3 years or more of experience in the field of construction) within 10 days of completion of a project, and such inspections shall be recorded on an inspection log. The Division may perform interim inspections at any time and must have access to all inspection logs at all times. Copies of such records shall be submitted to the Division within 30 days of the expiration date of the Limited Scope Project Permit.
6.6.5 If the inspection logs associated with the Limited Scope Project Permit demonstrate compliance with the Limited Scope Project Permit requirements, the Division may issue a Certificate of Compliance for projects completed under that permit.
6.6.6 If the inspection logs associated with the Limited Scope Project Permit demonstrate noncompliance with the Limited Scope Project Permit requirements, the Division will issue a correction notice and may revoke and withhold issuing another Limited Scope Project Permit or Certificate of Compliance to the Business Entity until all corrections have been satisfied and may, based on the extent of noncompliance and at the Division's discretion, elect to not issue a limited scope project permit for the next renewal of the Certificate of Compliance.

Notes

8 CCR 1507-31, art. 6
40 CR 04, February 25, 2017, effective 3/17/2017 42 CR 05, March 10, 2019, effective 3/30/2019 43 CR 14, July 25, 2020, effective 8/14/2020 44 CR 22, November 25, 2021, effective 12/15/2021

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.