Conn. Agencies Regs. § 16-11-237 - Installation and maintenance of submeters
(a) Submeters
and any submetering equipment shall be installed by the submetering customer in
accordance with the provisions of all applicable codes and standards, including
the National Electrical Safety Code, the National Electrical Code, and state
and local electric codes.
(b)
Submeters shall be clearly and permanently labeled with the owner's identity,
in order that submeters are clearly distinguishable from the electric company's
meters. In addition, each submeter shall be permanently marked to indicate the
portion of the premises and all facilities it serves. Submeters shall be
securely mounted in a manner as to be reasonably free from damage. All
submeters shall be visually accessible to submetered parties or access shall be
provided upon request. Submeters located indoors shall be mounted in a clean,
dry and safe location. If located outdoors, all equipment associated with the
submeter shall be suitable for outdoor installation or otherwise weatherproofed
and the meters shall be mounted at a height of not less than 24? above ground
level.
(c) All electricity sold to
submetered parties shall be measured by commercially acceptable meters, owned
and maintained by the submetering customer.