Conn. Agencies Regs. § 16-333-20 - Electrical equipment requirements
(a) A fused
disconnecting means or a circuit breaker device of the lowest current rating
consistent with the load requirements of the ***power supply
shall be provided for power service to the ***power supply.
This device may be included within the ***power supply housing
or it may be in a separate weatherproof enclosure. such enclosure shall be
acceptable to the power company.
(b) Where the power service protective device
is in an enclosure which is external to and not part of the ***power
supply case, this enclosure and the ***power supply
case shall be made electrically continuous by a means other than the power
service neutral conductor.
(c)
Properly identified line and neutral terminals for connecting electrical
service conductors shall be provided. All power service connections at the CATV
***power supply shall be such as to preclude the possibility
of a reversal in polarity.
(d) CATV
power supply equipment shall be designed so as to provide
a separate, permanent electrical interconnection between the
service neutral conductor terminal, metallic enclosure ***and
the CATV cable strand.