Conn. Agencies Regs. § 16-333-21 - Bonding and grounding
(a) CATV cable
strand shall be bonded to the telephone cable strand or the multiple line wire
support strand at the first and last joint pole, and at every amplifier
and power supply location, with the distance between the bond
points not to exceed ten sections. Where there are no telephone facilities
present and the power system is multi-grounded neutral, the CATV cable
strand shall be bonded to a vertical grounding conductor of
the power system multi-grounded neutral at approximately one quarter mile
intervals.
(b) The outer conductor
of the CATV coaxial service drop shall be grounded at the subscriber's location
in accordance with requirements as specified by the National Electrical Code.
Where a ground rod is used for grounding, an interconnection shall be made
between the CATV ground rod and the existing power system ground.
(c) Where a supporting strand is required for
the CATV service drop, such strand shall be bonded to the CATV cable
strand.