Ga. Comp. R. & Regs. R. 120-3-18-.05 - Standards for Grandstands Used for Places of Assembly
(1) New
Construction: All grandstands shall be designed by a Georgia registered
architect or engineer and constructed to conform with NFPA 101 as adopted in
the Rules and Regulations of the Safety Fire Commissioner, Chapter 120-3-3. A
complete set of plans and specifications shall be reviewed, approved and a
construction permit issued by the State Fire Marshal or the proper local fire
official prior to construction. A fee as specified in O.C.G.A. Section
25-2-4.1 shall be charged for
reviewing the plans and specifications. The responsible registered architect or
engineer shall notify the State Fire Marshal or the proper local fire official
in writing 21 days before the grandstand(s) are 80% complete so that an
inspection can be scheduled and conducted. The responsible registered architect
or engineer shall notify the State Fire Marshal, the proper local fire
official, state inspector, or authorized representative of the Safety Fire
Commissioner again in writing 21 days before the grandstand(s) are 100%
complete. A certificate of occupancy shall be issued upon compliance with all
construction standards. A fee as specified in O.C.G.A. Section
25-2-4.1 shall be charged for the
certificate of occupancy.
(2)
Existing Grandstands: Existing grandstands shall comply with NFPA 101 as
adopted in Rules and Regulations of the Safety Fire Commissioner Chapter
120-3-3.
(3) Maintenance of
Grandstands: The grandstand area shall be properly maintained at all times, and
combustibles, flammable and combustible liquids, and LP-Gas cylinders shall not
be stored on or below the grandstand(s). The owner or operator shall provide
for not less than an annual inspection and required maintenance of each outdoor
grandstand to ensure safe conditions. At least biennially, the inspection shall
be performed by a professional engineer, registered architect, or individual
certified by the manufacturer. The owner or operator shall provide a copy of
the inspection report and certification that the inspection has been performed
to the State Fire Marshal.
(4) Exit
Illumination: When races are conducted after sundown, lighting of all exit
ways, aisles and walkways of the grandstand(s) shall be provided as required in
NFPA 101 as adopted in Rules and Regulations of the Safety Fire Commissioner
Chapter 120-3-3.
(5) Portable
Grandstands: Portable grandstands shall comply with NFPA 101 as adopted in
Rules and Regulations of the Safety Fire Commissioner Chapter
120-3-3.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.