Ga. Comp. R. & Regs. R. 120-3-25-.15 - Existing Installation (General)
(1) These are the minimum requirements for
regular maintenance and safety practices for existing elevators as provided for
in the Safety Act and Rules. All existing features or components of the
elevator shall comply with the Rules as adopted by the Commissioner.
(2) All existing elevators having a travel of
more than 25' 0" shall have "Fire Emergency Service" complying with ASME A17.1
1987 Edition as a minimum.
(3) A
permanent decal or metal tag shall be affixed to the lift equipment, in the
machine room, control space, machine space, pits, hoistway required to be
tested by ASME A17.1, Section 8.6 of the Standard. This decal or tag shall be
affixed to the affected equipment when new installations, alterations, or
periodic tests are conducted, as required by the Standard. This decal or tag
must indicate the date of the test, and the name of the person or firm which
performed the test and type of test performed. A decal will not be acceptable
when the Standard requires a metal tag. At the time of new installation,
alteration, or periodic tests, additional data shall be provided to the
building owner or his representative. This document shall include the date of
the test, the name of the person or firm conducting the tests and all pertinent
data relating to the test.
(4) Mass
transit equipment shall have a routine and a periodic inspection as defined by
ASME A17.1 latest adopted edition, as modified by O.C.G.A. Section
8-2-102.
(5) Existing Hydraulic Elevators are exempted
from the requirements of Rule 8.6.5.8 for five (5) years. Elevators shall have
all work required for compliance with ASME A17.3, Section 4.3.3 completed
within five (5) years of the effective date of this regulation. Failure to
complete work within the required time period will result in the elevator being
removed from service until such work is completed, unless the cylinder is
replaced.
(6) Existing escalators
shall meet the Performance Step Indexing requirements of ASME A17.3, Rule
5.1.11 within two (2) years of the effective date of this Rule
revision.
(7) State Elevator
Inspectors are not required to meet 8.11, QEI-1 requirements.
(8) Existing passenger elevators shall meet
the Restricted Opening of Hoistway Doors or Car Doors as required by ASME
A17.3, Rule 2.7.5 within two (2) years of the effective date of this Rule
revision.
(9) All existing
automatic passenger and freight elevators shall comply with ASME A17.3 Section
3.10.12 within three (3) years of the effective date of this rule.
(10) All elevators shall have emergency key
access at all landings that is no greater in height than the applicable code
requires.
(11) The data plates
required under (d) Section 8.9, Code Data Plate in A17.3 of the latest edition
adopted shall follow the requirements of the modifications to 8.9.2 Code Data
Plate: "The data plate shall be in plain view, securely attached to each
mainline disconnect or controller. It shall also be permitted to locate the
data plate in the controller as long as it is in plain view with the controller
door open."