Ill. Admin. Code tit. 35, § 726.207 - Standards to Control HCl and Chlorine Gas Emissions
a) General. The owner or operator must comply
with the HCl and chlorine gas controls provided by subsection (b), (c), or
(e).
b) Screening Limits
1) Tier I Feed Rate Screening Limits. Feed
rate screening limits are specified for total chlorine in Appendix B as a
function of TESH and terrain and land use in the vicinity of the facility. The
feed rate of total chlorine and chloride, both organic and inorganic, in all
feed streams, including hazardous waste, fuels, and industrial furnace feed
stocks must not exceed the levels specified.
2) Tier II Emission Rate Screening Limits.
Emission rate screening limits for HCl and chlorine gas are specified in
Appendix C as a function of TESH and terrain and land use in the vicinity of
the facility. The stack emission rates of HCl and chlorine gas must not exceed
the levels specified.
3)
Definitions and Limitations. The definitions and limitations provided by
Sections
726.200(i)
and
726.206(b)
for the following terms also apply to the screening limits provided by this
subsection: TESH, good engineering practice stack height, terrain type, land
use, and criteria for facilities not eligible to use the screening
limits.
4) Multiple Stacks. Owners
and operators of facilities with more than one on-site stack from a BIF,
incinerator or other thermal treatment unit subject to controls on HCl or
chlorine gas emissions under a RCRA permit or interim status controls must
comply with the Tier I and Tier II screening limits for those stacks assuming
all hazardous waste is fed into the device with the worst-case stack based on
dispersion characteristics.
A) The worst-case
stack is determined by procedures provided in Section
726.206(b)(6).
B) Under Tier I, the total feed rate of
chlorine and chloride to all subject devices must not exceed the screening
limit for the worst-case stack.
C)
Under Tier II, the total emissions of HCl and chlorine gas from all subject
stacks must not exceed the screening limit for the worst-case stack.
c) Tier III
Site-Specific Risk Assessments
1) General.
Conformance with the Tier III controls must be demonstrated by emissions
testing to determine the emission rate for HCl and chlorine gas, air dispersion
modeling to predict the maximum annual average off-site ground level
concentration for each compound, and a demonstration that acceptable ambient
levels are not exceeded.
2)
Acceptable Ambiant Levels. Appendix D lists the RACs for HCl (7
µg/m3) and chlorine gas (0.4
µg/m3).
3) Multiple Stacks. Owners and operators of
facilities with more than one on-site stack from a BIF, incinerator, or other
thermal treatment unit subject to controls on HCl or chlorine gas emissions
under a RCRA permit or interim status controls must conduct emissions testing
and dispersion modeling to demonstrate that the aggregate emissions from all
such on-site stacks do not result in an exceedance of the acceptable ambient
levels for HCl and chlorine gas.
d) Averaging Periods. The HCl and chlorine
gas controls are implemented by limiting the feed rate of total chlorine and
chloride in all feedstreams, including hazardous waste, fuels, and industrial
furnace feed stocks. Under Tier I, the feed rate of total chlorine and chloride
is limited to the Tier I Screening Limits. Under Tier II and Tier III, the feed
rate of total chlorine and chloride is limited to the feed rates during the
trial burn (for new facilities or an interim status facility applying for a
permit) or the compliance test (for interim status facilities). The feed rate
limits are based on either of the following:
2) An instantaneous basis not to
be exceeded at any time.
e) Adjusted Tier I Feed Rate Screening
Limits. The owner or operator may adjust the feed rate screening limit provided
by Appendix B to account for site-specific dispersion modeling. Under this
approach, the adjusted feed rate screening limit is determined by
back-calculating from the acceptable ambient level for chlorine gas provided by
Appendix D using dispersion modeling to determine the maximum allowable
emission rate. This emission rate becomes the adjusted Tier I feed rate
screening limit.
f) Emissions
Testing. Emissions testing for HCl and chlorine gas
(Cl2) must be conducted using the procedures described
in Method 0050 or 0051, in "Test Methods for Evaluating Solid Waste,
Physical/Chemical Methods", USEPA publication number EPA-530/SW-846,
incorporated by reference in 35 Ill. Adm. Code
720.111(a).
g) Dispersion Modeling. Dispersion modeling
must be conducted according to the provisions of Section
726.206(h).
h) Enforcement. For the purposes of permit
enforcement, compliance with the operating requirements specified in the permit
(under Section 726.202) will be regarded as compliance with this Section.
However, evidence that compliance with those permit conditions is insufficient
to ensure compliance with the requirements of this Section is "information"
justifying modification or revocation and re-issuance of a permit under 35 Ill.
Adm. Code
703.270 through
703.273.
Notes
Amended at 32 Ill. Reg. 12741, effective July 14, 2008
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.