The Compressed Gas Association's (CGA's) American National
Standard Safety Requirements for the Storage and Handling of Anhydrous Ammonia
(6th edition), commonly referred to as ANSI/CGA G-2.1 2014, is adopted by this
reference as the official requirement for the storage and handling of anhydrous
ammonia, with the following exceptions:
1. Strike subrule 3.1 in its entirety and
insert in lieu thereof the following:
3.1 Any
person required to handle, transfer, transport, or otherwise work with ammonia
shall be trained once each calendar year prior to handling to understand the
properties of ammonia, to become competent in safe operating practices, and to
take appropriate actions in the event of a leak or an emergency.
2. Insert a new subrule 5.1.3 to
read as follows:
5.1.3 Equipment and
components must be installed, operated, and maintained in accordance with the
manufacturer's recommendations or best engineering practices.
3. The following subrule 5.3.4 as
set out in CGA G-2.1 2014, page 16, is included:
5.3.4 In the absence of a specific
determination by local jurisdictions, separation distances for new, additional
or relocated ammonia stationary storage containers and placements of containers
covered by Sections 9, 10, 11 and 12 after January 1, 2002, shall be in
accordance with Table 5:
Minimum Separation Distances for Location of Ammonia Storage
Containers
|
Minimum Distances (in feet or meters) from Each
Container to:
|
|
Nominal Capacity of Container3)
(Gallons or Cubic Meters)
|
Mainline of Railroad4)
|
Highway5) or Line of Adjoining
Property which can be built upon
|
Place of Public Assembly6) or
Residential Occupancy7)
|
Institutional
Occupancy8)
|
|
Over 500 to 2,000 gals9)
|
100 ft
|
25 ft
|
150 ft
|
250 ft
|
|
Over 2,000 to 30,000 gals
|
100 ft
|
50 ft
|
300 ft
|
500 ft
|
|
Over 30,000 to 100,000 gals
|
100 ft
|
50 ft
|
450 ft
|
750 ft
|
|
Over 100,000 gals
|
100 ft
|
50 ft
|
600 ft
|
1000 ft
|
|
Over 2 to 8 m3
|
30 m
|
8 m
|
45 m
|
75 m
|
|
Over 8 to 110 m3
|
30 m
|
15 m
|
90 m
|
150 m
|
|
Over 110 to 400 m3
|
30 m
|
15 m
|
140 m
|
230 m
|
|
Over 400 m3
|
30 m
|
15 m
|
180 m
|
300 m
|
1) Separation
distances referred to are approximate and based on experience with minor
releases.
2) For additional
distances, see 5.3.2, 5.3.3, 5.3.4, 5.3.5, 5.3.6 and 6.4.6.
3) The nominal capacity of multiple
containers shall be aggregated, but only if containers are interconnected and
safeguards do not exist to prevent a leak from one container from emptying
interconnected containers.
4) Class
II track or better. See
49 CFR
213.9 [8].
5) A highway is defined as a public way for
purposes of vehicular travel, including the entire area within the right of
way. See American Association of State Highway and Transportation Officials
(AASHTO) Transportation Glossary (1983) [37].
6) Public assembly occupancy is a premise or
that portion of a premise where large numbers of people congregate and from
which occupants cannot quickly vacate the space. Public assembly occupancies
include, among others, auditoriums, ballrooms, classrooms, passenger depots,
restaurants, and theatres. See ANSI/ASHRAE 15 [1].
7) Residential occupancy is a premise or that
portion of a premise that provides the occupants with complete independent
living facilities including permanent provisions for living, sleeping, eating,
cooking, and sanitation. Residential occupancies include, among others,
dormitories, hotels, multiunit apartments, and private residences. See
ANSI/ASHRAE 15 [1].
8)
Institutional occupancy is a premise or that portion of a premise from which,
because they are disabled, debilitated, or confined, occupants cannot readily
leave without the assistance of others. Institutional occupancies include,
among others, hospitals, nursing homes, asylums, and spaces containing locked
cells. See ANSI/ASHRAE 15 [1].
9)
For 500 gallons (2m3) or less, see 5.3.1 and 5.3.3.
4. Strike
subrule 5.3.6 in its entirety and insert in lieu thereof the following:
5.3.6 Areas within 10 feet (3 meters) of a
storage container shall be maintained clear of dry grass and weeds and other
combustible materials. Areas shall be kept clear of debris or any item that
would interfere with emergency actions or evacuation as well as materials or
objects not necessary for the operation of the storage system and
components.
5. Strike
subrule 5.6.6 in its entirety and insert in lieu thereof the following:
5.6.6 Adequate provisions shall be made to
protect the storage system and components, including all exposed piping, from
physical damage which could result from impact by moving machinery, automobiles
or trucks, or any other equipment at the facility. See also 6.7.1.
6. Insert a new subrule 5.10.8.2
to read as follows:
5.10.8.2 For transfer of
liquids from a container utilizing a remote transfer point, each liquid filling
connection shall have a positive shut-off valve in conjunction with either an
internal back-pressure check valve or an internal excess flow valve. Vapor
connections shall have a positive shut-off valve between the supply source and
the intake side of the pump. The liquid line supplying this transfer from the
pump shall have an emergency shut-off valve between the supply source and the
intake side of the pump. The emergency shut-off valve shall remain closed when
the plant is not in use.
Note: The internal back-pressure check valves or internal
excess flow valves shall be installed in the facility piping prior to the
positive shut-off valves. These valves shall be installed so that any break
will occur on the side of the transfer hose. Protection from pull away while
connected is the same as described in 5.10.8.1.
7. Add the following subrule 5.10.10:
5.10.10 Anhydrous ammonia shall be vented
into an adequate supply of water. For this purpose, an adequate supply of water
means ten gallons of water for each gallon of liquid ammonia or fraction
thereof which is contained in the hose or vessel to be vented. The ammonia
should be injected into the water as near the bottom of a vented water
containing vessel as practical. If a hose is used to inject ammonia into water,
the hose should be weighted or secured so that the end of the hose will remain
near the bottom of the vessel. An approved sparging device is recommended. Any
aqueous ammonia solution resulting from the venting process shall be disposed
of safely and properly.
Note: Ammonia vapor may be flared off when appropriate
equipment is used to not allow ammonia vapor to escape unchecked into the
atmosphere. This section does not apply to venting of a coupling between
transfer hose and nurse tank or applicator or venting of vapor through 85
percent bleeder valve when loading a nurse tank or applicator.
8. Add the following
subrule 5.10.10.1:
5.10.10.1 Anhydrous
ammonia shall not be vented into the air. Each transport truck unloading point
at an anhydrous ammonia storage facility shall have a valve for venting
purposes installed in the piping at or near the point where the piping and hose
from the transport truck are connected. Anhydrous ammonia from any transport
truck hose shall be vented into an adequate supply of water. For this purpose,
an adequate supply of water means ten gallons of water for each gallon of
liquid ammonia or fraction thereof which could be contained in the hose. The
ammonia should be injected into the water as near the bottom of a vented water
containing vessel as practical. If a hose is used to inject ammonia into water,
the hose should be weighted or secured so that the end of the hose will remain
near the bottom of the vessel. An approved sparging device is recommended. Any
aqueous solution resulting from the venting process shall be disposed of safely
and properly.
9. Add the
following subrule 5.10.11:
5.10.11 All
anhydrous ammonia storage locations shall have a permanent working platform
installed at each nurse tank or applicator loading location. The working
platform shall be designed to allow for connecting and disconnecting of
transfer hoses without standing on equipment being loaded.
Note: This section does not apply to nurse tanks or
applicators with a working surface designed for loading purposes.
10. Add the following
subrule 6.3.1.1:
6.3.1.1 Containers designed
with internal pressure relief systems are exempt from this
requirement.
11. Strike
subrule 9.7.3 in its entirety and insert in lieu thereof the following:
9.7.3 A cargo tank of 3,500 gallons or less
water capacity may be unloaded into permanent storage locations meeting the
requirements of 3.4.1 and 5.10.8 through 5.10.8.2 or into implements of
husbandry meeting the requirements of Section 11. A cargo tank of greater than
3,500 gallons water capacity but not greater than 5,000 gallons water capacity
may be unloaded at permanent storage locations meeting the requirements of 3.4
and 5.10.8 through 5.10.8.2 or into a portable application equipment container
which is capable of holding the entire load. A cargo tank of greater than 5,000
gallons water capacity may only be unloaded into a permanent storage location
meeting the requirements of 3.4 and 5.10.8 through 5.10.8.2 and capable of
holding the entire load.
12. Strike subrule 11.3.5 in its entirety and
insert in lieu thereof the following:
11.3.5
All vapor and liquid connections, except pressure relief valves and those
specifically exempt in 5.5.5 and 5.5.6, shall be equipped with approved excess
flow valves or may be fitted with quick-closing internal valves, which shall
remain closed except during operating periods.
1. All vapor and liquid connections shall be
closed except during operation periods.
2. Shared piping where multiple containers
are plumbed together shall be equipped with additional excess flow valves or
back-pressure check valves or both to meet the requirements of 5.10.8.
3. Mechanical remote shut-off
valves may be added or substituted for excess flow valves in the piping after
the vapor and liquid connections as a means of controlling the flow.
13. Strike subrule
11.6.1 in its entirety and insert in lieu thereof the following:
11.6.1 Each
person operating, repairing
appurtenances of, or inspecting a nurse tank shall comply with the following
requirements:
1. Any person required to
handle, transfer, transport, or otherwise work with ammonia shall be trained
once each calendar year prior to handling to understand the properties of
ammonia, to become competent in safe operating practices, and to take
appropriate actions in the event of a leak or an emergency; and
2. Any person making, breaking or testing any
ammonia connection, transferring ammonia or performing maintenance or repair on
an ammonia system under pressure shall wear chemical splash goggles and
protective gloves impervious to ammonia. A full face shield may be worn over
the goggles. However, a face shield shall not be worn as a substitute for a
primary eye protection device (goggles).
14. Strike subrule 11.6.2 in its entirety and
insert in lieu thereof the following:
11.6.2
Each nurse tank shall be equipped with the following safety equipment and
features:
1. Each container shall have for
first-aid purposes at least 5 gallons (20 liters) of clean water in a container
designed to provide ready access to the water for flushing any area of the body
contacted by ammonia; and
2. A
legible decal listing first-aid procedures to follow for injuries caused by
ammonia.
15.
Strike subrule 12.3.3 in its entirety and insert in lieu thereof the following:
12.3.3 An excess flow valve is not required
in the vapor connections, provided that the controlling orifice is not in
excess of 0.4375 inches (11.1 mm) in diameter and the valve is a hand-operated
(attached hand wheel or equivalent) shut-off valve. Bleed off of vapors may be
done into water meeting requirements of 5.10.10 if vapor connections cannot be
made to the supplying vessel when filling applicator tanks. Vapors may be
vented into the ground in the field of application under proper field
conditions.
16. Strike
subrule 12.4.1 in its entirety and insert in lieu thereof the following:
12.4.1 Each
person operating, repairing
appurtenances of, or inspecting an applicator tank shall comply with the
following requirements:
1. Any person
required to handle, transfer, transport, or otherwise work with ammonia shall
be trained once each calendar year prior to handling to understand the
properties of ammonia, to become competent in safe operating practices, and to
take appropriate actions in the event of a leak or an emergency; and
2. Any
person making, breaking or testing any
ammonia connection, transferring ammonia or performing maintenance or repair on
an ammonia system under pressure shall wear chemical splash goggles and
protective gloves impervious to ammonia. A full face shield may be worn over
the goggles. However, a face shield shall not be worn as a substitute for a
primary eye protection device (goggles).
This rule is intended to implement Iowa Code section
200.14.