Iowa Admin. Code r. 567-63.4 - Effluent toxicity testing requirements in permits
(1)
Effluent toxicity
testing. All major municipal and industrial dischargers shall be
required to carry out effluent toxicity testing. Minor dischargers may be
required to conduct effluent toxicity tests based on a case-by-case evaluation
of the impact of the discharge on the receiving stream or industrial
contribution to the system. All dischargers required to conduct effluent
toxicity tests shall conduct, at a minimum, one valid effluent toxicity test
annually. The testing requirements will be placed in the operation permit for
each discharger required to conduct this testing. Additional monitoring may be
specified in the operation permit based on a case-by-case evaluation of the
impact of the discharge on the receiving stream, toxic or deleterious effects
of wastewaters, industrial contribution to the system, complexities of the
treatment process, history of noncompliance or any other factor which requires
strict operational control to meet the effluent limitations of the permit. Any
effluent toxicity test completed by the department or other agency and
conducted according to procedures stated or referenced in this rule may be used
to determine compliance with an operational permit.
(2)
Testing procedures.
Dischargers shall be required to conduct effluent toxicity tests in accordance
with the following general requirements:
a.
Effluent toxicity tests shall be performed using a 24-hour composite sample of
the effluent collected at the location stated in the operation permit. All
composite samples shall be delivered to the testing laboratory within a
reasonable time (approximately 24 hours) after collection, and all tests must
commence within 36 hours following sample collection. The results of all
effluent toxicity tests, including any tests performed at a greater frequency
than required in the operation permit, shall be submitted to the department
within 30 days of completing the test.
b. All effluent toxicity tests shall be
conducted using the test methods referenced in 40 CFR Part 136 and protocols
described in the EPA document EPA-821-R-02-012, Methods for Measuring the Acute
Toxicity of Effluents and Receiving Waters to Freshwater and Marine Organisms,
5th edition, October 2002. All effluent toxicity tests shall be conducted by a
laboratory certified in Iowa.
c.
All effluent toxicity tests shall be performed using the water
flea(Ceriodaphnia dubia), and the fathead
minnow(Pimephales promelas).
d. Effluent toxicity tests shall include, at
a minimum, two different concentrations of effluent. One test shall consist of
100 percent effluent, and a second test shall be a diluted effluent sample as
defined. A control test, consisting of 100 percent culture water for each
respective organism shall also be used. The test shall last for 48 hours at
which time the mortality will be determined for all tests.
e. All effluent toxicity tests shall be of
the pass/fail type.
(3)
If there is a positive toxicity test result in the diluted effluent sample from
a valid effluent toxicity test, the following requirements apply unless the
exception in paragraph "c" of this subrule is applicable.
a. At a minimum, the discharger shall be
required to conduct quarterly effluent toxicity tests until three successive
tests are determined not to be positive, after which the normal annual testing
shall be resumed.
b. If the
discharger has two successive positive valid diluted effluent toxicity test
results or three positive test results out of five valid diluted effluent
toxicity tests, the discharger shall be required to conduct a toxicity
reduction evaluation (TRE). The discharger may be required to carry out
instream monitoring or other analysis in conjunction with the TRE. At any time
during the course of conducting a TRE there are three consecutive follow-up
toxicity test results for the diluted sample which are not positive, the
facility will be considered in compliance and work on the TRE may cease. Annual
testing for effluent toxicity shall then resume. Nothing in these rules shall
preclude the department from taking enforcement action beyond that described in
these rules.
c. When the pretest
chemical analysis for un-ionized ammonia nitrogen (NH3-N) or total residual
chlorine (TRC) on the diluted effluent sample exceeds the concentrations given
below, a positive test result is likely to have been caused by high
concentrations of NH3 or TRC, and the test result will not be used to determine
if follow-up testing is needed.
(1) Un-ionized
Ammonia Nitrogen-0.9 mg/l
(2)
TRC-0.1 mg/l
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.