b.
Unsuitable
absorption. Conventional subsurface soil absorption trenches shall not
be installed in soils that have a percolation rate less than 1 minute per inch
or greater than 60 minutes per inch. Plans for an alternative method of
wastewater treatment shall be submitted to the administrative authority for
approval prior to construction.
Table Ilia Maximum Soil Application Rates Based Upon
Percolation Rates
| Percolation Rate (minutes per inch) |
Monthly Averages |
| Septic Tank Effluent(1)
BOD530 mg/L - 220 mg/L TSS30mg/L- 150 mg/L (gals/sq
ft/day)(2)
|
Pretreated Effluent BOD5 <= 30
mg/L TSS <= 30 mg/L (gals/sq ft/day) |
| 0 to 5 |
1.2 |
1.6 |
| Fine sands |
0.5 |
0.9 |
| 6 to 10 |
0.8 - 0.6 |
1.2 |
| 11 to 29 |
0.6 - 0.5 |
0.9 |
| 30 to 45 |
0.5 - 0.4 |
0.7 |
| 46 to 60 |
0.4 - 0.2 |
0.5 |
| 61 to 120 |
0.0 |
0.3 |
| Greater than 120 |
0.0 |
0.0 |
NOTE: "BOD" means biochemical oxygen demand. "TSS" means
total suspended solids.
(1) Typical
waste strengths for domestic waste. Pretreatment should be considered for waste
of higher strength.
(2) Percolation
rates and soil loading rates do not precisely correlate; therefore, a range is
provided.
Table Illb
Maximum Soil Loading Rates Based Upon Soil Evaluations
in Gallons per Square Foot per Day (gal/ft2/day) for
Septic Tank Effluent. Values in () are for secondary treated effluent.
| Soil Texture |
Single Grain |
Massive |
Structure Granular, Blocky, or Prismatic
|
Platy |
|
|
|
|
Weak |
Moderate |
Strong |
Weak |
Moderate to |
|
|
|
|
|
|
|
|
Strong |
| Coarse sand and gravel |
1.2 (1.6) |
X |
1.2 (1.6) |
X |
X |
1.2 (1.6) |
X |
| Medium sands |
0.7 (1.4) |
X |
0.7 (1.4) |
X |
X |
0.7 (1.4) |
X |
| Fine sands |
0.5 (0.9) |
X |
0.5 (0.9) |
X |
X |
0.5 (0.9) |
X |
| Very fine sands* |
0.3 (0.5) |
X |
0.3 (0.5) |
X |
X |
0.3 (0.5) |
X |
| Sandy loam |
X |
0.3 (0.5) |
0.45 (0.7) |
0.6 (1.1) |
0.65 (1.2) |
0.4 (0.6) |
0.3 (0.5) |
| Loam |
X |
0.4 (0.6) |
0.45 (0.7) |
0.5 (0.8) |
0.55 (0.8) |
0.4 (0.6) |
0.3 (0.5) |
| Silty loam |
X |
NS |
0.4 (0.6) |
0.5 (0.8) |
0.5 (0.8) |
0.3 (0.5) |
0.2 (0.3) |
| Clay loam |
X |
NS |
0.2 (0.3) |
0.45 (0.7) |
0.45 (0.7) |
0.1 (0.2) |
0.1 (0.2) |
| Silty clay loam |
X |
NS |
0.2 (0.3) |
0.45 (0.7) |
0.45 (0.7) |
NS |
NS |
NOTE: "X" means not found in nature. "NS" means not suitable
for soil absorption.
* Flow rates are difficult to determine for some very fine
sands; experience may provide better information and flow rates.
Table IIIc
Minimum Length of Absorption Trenches in
Feet
|
|
2 bedroom 300 gal. |
3 bedroom 450 gal. |
4 bedroom 600 gal. |
5 bedroom 750 gal. |
6 bedroom 900 gal. |
| Width of trench in feet |
2' |
3' |
2' |
3' |
2' |
3' |
2' |
3' |
2' |
3' |
| Soil loading rate gal/ft2
|
|
| 0.1 |
Not suitable for soil absorption trenches
|
| 0.2 |
750 |
500 |
1125* |
750 |
1500* |
1000* |
1875* |
1250* |
2250* |
1500* |
| 0.3 |
500 |
333 |
750 |
500 |
1000* |
666 |
1250* |
833* |
1500* |
1000* |
| 0.4 |
375 |
250 |
562 |
375 |
750 |
500 |
938* |
625 |
1125* |
750 |
| 0.5 |
300 |
200 |
450 |
300 |
600 |
400 |
750 |
500 |
900* |
600 |
| 0.6 |
250 |
167 |
375 |
250 |
500 |
333 |
625 |
417 |
750 |
500 |
| 0.7 |
214 |
143 |
321 |
214 |
428 |
286 |
536 |
357 |
643 |
429 |
| 0.8 |
188 |
125 |
281 |
188 |
375 |
250 |
469 |
312 |
562 |
375 |
| 0.9 |
167 |
111 |
250 |
167 |
333 |
222 |
417 |
278 |
500 |
333 |
| 1.0 |
150 |
100 |
225 |
150 |
300 |
200 |
375 |
250 |
450 |
300 |
| 1.1 |
136 |
91 |
205 |
136 |
273 |
182 |
341 |
227 |
409 |
273 |
| 1.2 |
125 |
84 |
188 |
125 |
250 |
167 |
313 |
208 |
375 |
250 |
* Requires pressure distribution (pump)
Table IIId
Alternative Option for Use of Absorption Bed*
| Percolation Rate min./inch |
Absorption Area/Bedroom sq. ft. |
Loading Rate/Day gal./sq. ft. |
| 1 - 5 |
300 |
.5 |
| 6-15 |
400 |
.375 |
| 16 -30 |
600 |
.25 |
*Absorption beds may only be used when site space
restrictions require and shall not be used when the soil percolation rate
exceeds 30 min./inch.
(3)
Construction details for all soil absorption trenches.
a.
Depth. Soil absorption
trenches shall not exceed 36 inches in depth unless authorized by the
administrative authority, but a shallower trench bottom depth of 18 to 24
inches is recommended. Not less than 6 inches of porous soil shall be provided
over the laterals. The minimum separation between trench bottom and
groundwater, rock formation or other confining layers shall be 36 inches even
if extra rock is used under the pipe.
b.
Length. No soil
absorption trench shall be greater than 100 feet long.
c.
Separation distance. At
least 6 feet of undisturbed soil shall be left between each trench edge on
level sites. The steeper the slope of the ground, the greater the separation
distance should be. Two feet of separation distance should be added for each 5
percent increase in slope from level.
d.
Grade. The trench bottom
should be constructed level from end to end. On sloping ground, the trench
shall follow a uniform land contour to maintain a minimum soil cover of 6
inches and a level trench bottom.
e.
Compaction. There shall
be minimum use or traffic of heavy equipment on the area proposed for soil
absorption. In addition, it is prohibited to use heavy equipment on the bottom
of the trenches in the absorption area.
f.
Fill soil. Soil
absorption systems shall not be installed in fill soil. Disturbed soils which
have stabilized for at least one year shall require a recent percolation test
or soil analysis.
g.
Bearing strength. Soil absorption systems shall be designed to carry
loadings to meet AASHTO H-10 standards.
h.
Soil smearing. Soils
with significant clay content should not be worked when wet. If soil moisture
causes sidewall smearing, the installation should be discontinued until
conditions improve.
(4)
Gravel systems.
a.
Gravel. A minimum of 6 inches of clean, washed river gravel, free of
clay and clay coatings, shall be laid below the distribution pipe, and enough
gravel shall be used to cover the pipe. This gravel shall be of such a size
that 100 percent of the gravel will pass a 2!/2-inch screen and 100 percent
will be retained on a
3/
4-inch
screen. Limestone or crushed rock is not recommended for soil absorption
systems; however, if used, it shall meet the following criteria:
(1)Abrasion loss. The
percent wear, as determined in accordance with the AASHTO T 96, Grading C,
shall not exceed 40 percent.
(2)Freeze and thaw loss.
When gravel is subjected to the freezing and thawing test, Iowa DOT Materials
Laboratory Test Method 211, Method A, the percentage loss shall not exceed 10
percent.
(3)Absorption. The percent
absorption, determined in accordance with Iowa DOT Materials Laboratory Test
Method 202, shall not exceed 3 percent.
b.
Trench width Soil
absorption trenches for gravel systems shall be a minimum of 24 inches and a
maximum of 36 inches in width at the bottom of the trench.
c.
Grade. The distribution
pipes shall be laid with a minimum grade of 2 inches per 100 feet of run and a
maximum grade of 6 inches per 100 feet of run, with a preference given to the
lesser slope.
d.
Pipe. Distribution pipe shall be PVC rigid plastic meeting
ASTM Standard 2729 or other suitable material approved by the administrative
authority. The inside diameter shall be not less than 4 inches, with
perforations at least 1/2 inch and no more than 3/4 inch in diameter,
spaced no more than 40 inches apart. Two rows of perforations shall be provided
located 120 degrees apart along the bottom half of the tubing (each 60 degrees
up from the bottom centerline). The end of the pipe in each trench shall be
sealed with a watertight cap unless, on a level site, a footer is installed
connecting the trenches together. Coiled perforated plastic pipe shall not be
used.
e.
Gravel
cover. Unbacked, rolled, 3 1/2-inch-thick fiberglass insulation,
untreated building paper, synthetic drainage fabric, or other approved material
shall be laid so as to separate the gravel from the soil backfill.
(5)
Gravelless pipe
systems.
a.
Application. Gravelless subsurface soil absorption systems may
be used as an alternative to conventional 4-inch pipe placed in gravel-filled
trenches. However, these systems shall not be used in areas where conventional
systems would not be allowed due to poor permeability, high groundwater, or
insufficient depth to bedrock.
b.
Installation. The manufacturer's specifications and
installation procedures shall be adhered to.
c.
Material. The 10-inch
I.D. corrugated polyethylene tubing used in gravelless systems shall meet the
requirements of ASTM F667, Standard Specification for Large Diameter Corrugated
Polyethylene Tubing.
d.
Perforations. Two rows of perforations shall be located 120
degrees apart along the bottom half of the tubing (each 60 degrees up from the
bottom centerline). Perforations shall be cleanly cut into each inner
corrugation along the length of the tubing and should be staggered so that
there is only one hole in each corrugation.
e.
Top marking. The tubing
should be visibly marked to indicate the top of the pipe.
f.
Filter wrap. All
gravelless drainfield pipe shall be encased, at the point of manufacture, with
a geotextile filter wrap specific to this purpose.
g.
Trench width. The trench
width for the gravelless system shall be 24 inches.
h.
Length of trench. The
total length of absorption trench for a 10-inch gravelless pipe installation
shall be the same as given in Table IIIc for a 2-foot-wide conventional soil
absorption trench.
(6)
Chamber systems.
a.
Application. Chamber systems may be used as an alternative to
conventional 4-inch pipe placed in gravel-filled trenches. However, chamber
systems shall not be used in areas where conventional systems would not be
allowed due to poor permeability, high groundwater, or insufficient depth to
bedrock.
b.
Installation. The manufacturer's specifications and
installation procedures shall be adhered to.
c.
Length of trench. The
total length of soil absorption trench for chambers 15 to 22 inches wide shall
be the same as given in Table IIIc for a 2-foot-wide conventional soil
absorption trench. Chambers 33 inches wide or greater shall be sized as given
in Table IIIc for a 3-foot-wide conventional soil absorption trench.
d.
Sidewall. The chambers
shall have at least 6 inches of sidewall effluent soil exposure height below
the invert of the inlet.
(7)
Expanded polystyrene (EPS)
aggregate system.
a.
Application. EPS aggregate systems may be used as an alternative to
conventional 4-inch pipe placed in gravel-filled trenches. However, EPS
aggregate systems shall not be used in areas where conventional systems would
not be allowed due to poor permeability, high groundwater, or insufficient
depth to bedrock.
b.
Installation. The manufacturer's specifications and
installation procedures shall be adhered to.
c.
Length of trench The
total length of soil absorption trench for 12-inch EPS aggregate bundles shall
be the same as given in Table IIIc for a 2-foot-wide conventional soil
absorption trench. Twelve-inch EPS aggregate bundles 33 inches wide or greater
shall be sized as given in Table IIIc for a 3-foot-wide conventional soil
absorption trench.
d.
Gravel cover. Unbacked, rolled, 3 '/a-inch-thick fiberglass
insulation, untreated building paper, synthetic drainage fabric, or other
approved material shall be laid so as to separate the EPS aggregate from the
soil backfill.
(8)
Gravity distribution. Dosing is always recommended and
preferred to improve distribution, improve treatment and extend the life of the
system.
a. On a hillside, septic tank effluent
may be serially loaded to the soil absorption trenches by drop boxes or
overflow piping (rigid sewer pipe). Otherwise, effluent shall be distributed
evenly to all trenches by use of a distribution box or commercial distribution
regulator approved by the administrative authority.
b. Design. When a distribution box is used,
it shall be of proper design and installed with separate watertight headers
leading from the distribution box to each lateral. Header pipes shall be rigid
PVC plastic pipe meeting ASTM Standard 2729 or equivalent.
c. Height of outlets. The distribution box
shall have outlets at the same level at least 4 inches above the bottom of the
box to provide a minimum of 4 inches of water retention in the box.
d. Baffles. There shall be a pipe tee or
baffle at the inlet to break the water flow.
e. Unused outlets. All unused outlet holes in
the box shall be securely closed.
f. Materials. All distribution boxes shall be
constructed of corrosion-resistant rigid plastic materials.
g. Level outlets. All outlets of the
distribution box shall be made level. A 4-inch cap with an offset hole
approximately 21/2 inches in diameter shall be installed on each outlet
pipe. These caps shall be rotated until all outlets discharge at the same
elevation. Equivalent leveling devices may be approved by the county board of
health.
h. Equal length required.
The soil absorption area serviced by each outlet of the distribution box shall
be equal.
(9)
Dosing systems.
a.
Pump systems.
(1) Pump and pit
requirements. In the event the effluent from the septic tank outlet cannot be
discharged by gravity and the proper lateral depths still maintained, the
effluent shall discharge into a watertight pump pit with an inside diameter of
not less than 24 inches, equipped with a tight-fitting manhole cover at grade
level. The pump shall be of a submersible type of corrosion-resistant
material.
(2) Pump setting. The
pump shall be installed in the pump pit in a manner that ensures ease of
service and protection from frost and settled sludge. The pump shall be set to
provide a dosing frequency of approximately four times a day based on the
maximum design flow. No onsite electrical connections shall be located in the
pump pit. These connections shall be located in an exterior weatherproof
box.
(3) Pressure line size. The
pressure line from the pump to the point of discharge shall not be smaller than
the outlet of the pump it serves.
(4) Drainage. Pressure lines shall be
installed to provide total drainage between dosing to prevent freezing or shall
be buried below frost level up to the distribution box.
(5) High water alarm. Pump pits shall be
equipped with a sensor set to detect if the water level rises above the design
high water level when the pump fails. This sensor shall activate an auditory or
visual alarm to alert the homeowner that repairs are required.
(6) Discharge point. The effluent shall
discharge under pressure into a distribution box or may be distributed by
small-diameter pipes throughout the entire absorption field.
b.
Dosing
siphons. Dosing siphons may also be used. The manufacturer's
specifications shall be adhered to for installation. Similar dosing volumes and
frequencies are recommended. Dosing siphons require periodic cleaning to ensure
their continued proper operation.
c.
Filtered pump vaults. A
filtered pump vault is a device that is installed in a septic tank and houses a
pump and screens effluent until it is pumped. Filtered pump vaults may be used
when dosing volume is less than 50 gallons. Filtered pump vaults require
periodic inspection and cleaning to ensure their continued proper
operation.