Kan. Admin. Regs. § 49-52-19 - Pool heaters
(a) Each pool
heater shall have the following controls and safety devices that meet the
following requirements:
(1) A safety relief
valve, with a set pressure not to exceed the maximum allowable working pressure
of the lowest rated component in the system; and
(2) a pressure switch or a flow switch that
prevents the burner from operating if the circulating pump is not in operation
and that maintains adequate temperature controls conforming to the generally
acceptable standards for pool heaters.
(b) Each pool heater that can generate at
least 400,000 BTUH shall be constructed to meet the requirements of ASME
section IV, as adopted by reference in K.A.R. 49-45-5, and shall be registered
with the national board. Each pool heater shall be equipped with the controls
and safety devices required for heating boilers.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.