402.9 - Automatic sprinkler system
The covered mall building and buildings connected shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, which shall comply with the following: [F]
1. The
automatic sprinkler system shall be complete and operative
throughout occupied space in the covered mall building prior
to occupancy of any of the tenant spaces. Unoccupied tenant spaces shall be
similarly protected unless provided with approved alternative
protection.
2. Sprinkler protection
for the mall shall be independent from that provided for tenant spaces or
anchors. Where tenant spaces are supplied by the same system, they shall be
independently controlled.
Exception: An automatic sprinkler system shall not be required in spaces or areas of open parking garages constructed in accordance with Section 406.3.
402.9.1
Standpipe system. The
covered mall building shall be equipped throughout with a
standpipe system as required by Section 905.3.3. [F]