Mich. Admin. Code R. 285.641.8 - Alternative to diking for storage containers

Rule 8.

(1) An individual storage container that does not have a capacity of more than 3,000 gallons may be contained within a secondary storage container, that is, an elephant ring, instead of a diked containment area.
(2) A storage facility shall ensure that both the primary storage container and the elephant ring are fabricated of material that is compatible with each other and with the fertilizer that is being stored.
(3) A storage facility shall ensure that the height of the elephant ring wall is not more than 4 feet.
(4) A storage facility shall ensure that the volume that is contained within the secondary storage walls up to the working height of the elephant ring is sufficient to contain 110% of the volume that is contained in the primary storage container plus the volume that is displaced by the footings of any equipment which is placed within the secondary containment vessel.
(5) A storage facility shall ensure that the elephant ring is free of leaks and structural defects. A storage facility shall ensure that the base is protected from corrosion, both from inside and outside, and is underlaid with a concrete pad or with 8 inches of compacted gravel beneath 4 inches of compacted sand or clay or is protected as recommended by the manufacturer of the elephant ring and as approved by the department.
(6) A storage facility shall ensure that all piping connections to the primary storage container are made over the wall of the elephant ring and are adequately supported and braced. A storage facility shall ensure that pumps and other fixtures, if located within the elephant ring containment structure, are placed on an elevated platform or otherwise protected from water accumulation.
(7) A storage facility shall ensure that accumulations of storm water and other material are pumped over the wall of the elephant ring by means of a pump within the secondary container or by means of an exterior portable pump and are disposed of in accordance with R 285.641.10(2).
(8) A storage facility shall fully comply with the provisions of this rule 2 years after the effective date of this rule.