Mich. Admin. Code R. 400.10551 - Smoke barriers

Rule 551.

(1) Smoke barriers with a 1-hour-fire-resistance rating shall be provided on each floor that is used for sleeping rooms for more than 24 residents and shall be located so as to form an area of refuge on either side that is served with an approved means of egress. The barriers shall be located as close as possible to the middle of the floor to be protected and shall extend from outside wall to outside wall and from the floor through any interstitial spaces to the roof or floor structure above.
(2) Doors in the smoke barrier shall be at least C-labeled fire doors that are hung in labeled frames with self-closing devices. Where double doors without mullions are used, synchronizing hardware and astragals shall be installed.
(3) Doors in smoke barrier partitions may be held open only by electric hold-open devices which are designed so that interruption of the electric current or actuation of the fire alarm, sprinkler system, or the heat or smoke detector will cause the release of the doors. The doors shall also be capable of being manually opened and closed.

Notes

Mich. Admin. Code R. 400.10551
1992 AACS