Mich. Admin. Code R. 400.4543 - Doors
Rule 543.
(1)
Doors to required means of egress shall comply with all of the following
provisions:
(a) Be side-hinged and installed
at floor level.
(b) Be not less
than 36 inches wide in new and converted large and secure facilities and new
small facilities, and not less than 30 inches wide in remodeled and converted
small facilities, except as required by
R
400.4538(10).
(c) Be not less than 78 inches high in new,
remodeled, and converted facilities.
(d) In large and secure facilities, doors
shall be hung to swing in the direction of egress, except doors to
single-occupant rooms and bathrooms.
(e) Be equipped with at least knob-type,
properly operating, approved, positive-latching, nonlocking-against-egress-type
hardware which insures the opening of the door with a single motion, such as
turning a knob or applying pressure of normal strength on a latch, except as
where otherwise provided by subrule (2) of this rule and
R
400.4545.
(2) In secure facilities, locking hardware is
permitted if resident sleeping rooms are equipped with approved electric locks
or if there are staff present and awake, fully dressed, on duty, and in
possession of keys to release residents in an emergency.
(3) Doors entering stairs and other vertical
openings and doors to fire rated enclosures shall not be held in an open
position at any time by an underdoor wedge or hold-open device.
(4) Interior doors to any enclosure which is
required to have not less than a 1-hour fire resistance rating shall be
B-labeled fire doors in labeled frames and shall be equipped with
positive-latching hardware and self-closing devices.