Mich. Admin. Code R. 400.4552 - Heating devices and flame-producing devices

Rule 552.

(1) In large and secure facilities and all newly constructed and converted facilities, flame-producing-type heating devices and incinerators shall be in an enclosure providing at least 1-hour resistance to fire. Adequate combustion air shall be provided directly from the outside through a permanently open louver. Fire dampers are not required in ducts penetrating this enclosure.
(2) In existing small facilities, flame-producing-type heating devices and incinerators approved under the standards these rules replace shall continue to be approved with regard to enclosure or lack of enclosure until the portion of the facility containing the flame-producing device is remodeled or the facility is converted. This shall not preclude requirements relative to maintaining doors and other safety factors in proper working order.
(3) Electric heating shall be installed in accordance with the manufacturer's specifications and shall be approved by a nationally recognized, independent testing laboratory.
(4) Portable heaters and space heaters, including solid fuel heaters, are prohibited.
(5) A fireplace is permitted if it is masonry and has all of the following components:
(a) An approved glass door shielding the opening. The door shall be closed at all times except when a fire is being tended.
(b) A noncombustible hearth extending a minimum of 16 inches out from the front and 8 inches beyond each side of the fireplace opening.
(c) A noncombustible face extending not less than 12 inches above and 8 inches on each side of the fireplace opening.
(d) A masonry chimney constructed with approved flue liners.
(e) The chimney shall be visually inspected every other month while in use and cleaned as needed, but not less than once every 12 months.
(6) A heating plant room shall not be used for combustible storage or for a maintenance shop unless the room is provided with automatic sprinkler protection. Flammable liquids or gases shall not be stored in a heating plant room.
(7) A furnace and other flame-producing unit shall be installed according to manufacturer and test specifications and shall be vented by metal ducts to a chimney which is constructed of bricks, solid block masonry, or reinforced concrete, which has an approved flue lining, and is properly erected and maintained in a safe condition. A bracket chimney is not permitted. This rule does not prohibit the installation and use of any prefabricated chimney bearing the label of an approved, nationally recognized, independent testing laboratory if the chimney is installed and used in accordance with manufacturer and test specifications and is compatible with the heating unit or units connected to it. Only gas and oil-fired units may be connected to a prefabricated chimney.
(8) All furnaces shall be inspected on an annual basis by a licensed inspector. A copy of the inspection must be made available to the qualified fire inspector or the department's licensing authority upon request.
(9) A carbon monoxide detector, bearing a safety certification mark of a recognized testing laboratory such as UL (Underwriters Laboratories) or ETL (Electro technical Laboratory), shall be placed on all levels approved for child care and in all furnace zones.

Notes

Mich. Admin. Code R. 400.4552
1983 AACS; 2015 MR 9, Eff. June 8, 2015

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.