Mich. Admin. Code R. 408.10833 - Installation
Rule 833.
(1)
An extinguisher shall be installed securely on a hanger, in a bracket, or
mounted in a cabinet unless it is wheeled type or cart mounted. A means shall
be used to indicate the location of an extinguisher mounted in a cabinet or on
a shelf. The extinguisher shall be placed so that the operating instructions
face outward.
(2) An extinguisher
having a gross weight of not more than 40 pounds shall be installed so that the
top is not more than 5 feet above the floor. An extinguisher having a gross
weight of more than 40 pounds, except a wheeled type or cart mounted
extinguisher, shall be installed so that the top is not more than 3 1/2 feet
above the floor. An extinguisher, except a wheeled type or cart mounted
extinguisher, shall be installed so that the bottom is not less than 4 inches
from the floor.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.