Mich. Admin. Code R. 408.15321 - Electrical hazards

Rule 5321.

(1) An electric conductor or communication line shall be considered energized unless the systems utility or owner indicates otherwise and they have visibly grounded the conductor or line.
(2) The location of underground utilities shall be determined before any digging or ditching operations are started.
(3) A tree worker or qualified line clearance tree trimmer shall not make a direct contact with an energized conductor.
(4) A tree worker shall maintain his body and tools not less than the distance prescribed in table 1 from an energized conductor. If these clearances cannot be maintained, the systems operator or owner shall be contacted to deenergize the conductor or provide protective measures or devices before the work is started.
(5) A qualified line clearance tree trimmer shall maintain his body and tools not less than the distance prescribed in table 2 from an energized conductor, except the trimmer may remove branches hanging on a conductor using approved insulated tools and equipment when the voltage is below 10 kv.
(6) A branch hanging on a conductor energized at more than 10 kv shall be removed after the line is deenergized or removed by an authorized and trained systems operator employee or owner employee using approved protective tools and equipment.

TABLE 1

Minimum Working Distances for Tree Workers

Voltage Minimum Distance
0 to 300 volts 1 foot (.305 M)
301 to 750 volts 2 feet (.610 M)
751 to 50 kv 10 feet (3.05 M)
50 kv or more .4 inch per 100 volts

TABLE 2

Minimum Working Distances for Qualified Line Clearance Tree Trimmers

Voltage Range (phase to phase) Minimum Working Distance
O to 750 v 1 ft. ( .305 M)
751 to 35 kv 2 ft. 4 in. ( .711 M)
35.1 kv to 46.0 kv 2 ft. 6 in. ( .762 M)
46.1 kv to 72.5 kv 3 ft. 0 in. ( .914 M)
72.6 kv to 121.0 kv 3 ft. 4 in. (1.016 M)
138.0 kv to 145.0 kv 3 ft. 6 in. (1.067 M)
161.0 kv to 169.0 kv 3 ft. 8 in. (1.118 M)
230.0 kv to 242.0 kv 5 ft. 0 in. (1.524 M)
345.0 kv to 362.0 kv 7 ft. 0 in. (2.134 M)
500.0 kv to 552.0 kv 11 ft. 0 in. (3.453 M)
700.0 kv to 765.0 kv 15 ft. 0 in. (4.572 M)

Notes

Mich. Admin. Code R. 408.15321
1979 AC

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.