Mich. Admin. Code R. 408.30870 - NFPA code; adoption by reference

Rule 870 Section 230.85 is added to the code to read as follows:

230.85 Emergency disconnects. For 1- and 2-family dwelling units, an emergency disconnecting means shall be installed.
(A) General.
(1) Location. The disconnecting means shall be installed in a readily accessible outdoor location on or within sight of the dwelling unit.

Exception: Where the requirements of section 225.41 are met, this section shall not apply.

(2) Rating. The disconnecting means shall have a short-circuit current rating equal to or greater than the available fault current.
(3) Grouping. If more than 1 disconnecting means are provided, they shall be grouped.
(B) Disconnects. Each disconnect shall be a service disconnect.
(C) Replacement. Where service equipment is replaced, all of the requirements of this section shall apply.

Exception: Where only meter sockets, service entrance conductors, or related raceways and fittings are replaced, the requirements of this section shall not apply.

(D) Identification of other isolation disconnects. Where equipment for isolation of other energy source systems is not located adjacent to the emergency disconnect required by this section, a plaque or directory identifying the location of all equipment for isolation of other energy sources shall be located adjacent to the disconnecting means required by this section.
(E) Marking.
(1) Marking text. The service disconnecting means shall be marked as follows: "EMERGENCY DISCONNECT, SERVICE DISCONNECT".

Notes

Mich. Admin. Code R. 408.30870
1988 AACS; 1991 AACS; 1997 AACS; 2009 AACS; 2013 AACS; 2015 AACS; 2019 AACS; 2023 MR 22, Eff. 3/12/2024

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.