Mich. Admin. Code R. 408.7102 - Inspection and tests

Rule 102.

(1) An existing installation and a new elevator installation, after being placed in service, shall be subjected to maintenance inspections and tests.
(2) Maintenance inspections and tests of elevator car and counterweight safeties and governors shall be made at intervals of not more than 12 months.
(3) The owner or owner's authorized agent shall have maintenance inspections and tests made by a person qualified to perform them in the presence of an inspector in the employ of or authorized by the department, except where such an inspector is not available. When the required tests are made, the person or firm conducting the tests shall do both of the following:
(a) Submit to the department a statement upon a form furnished by it certifying that the tests have been conducted and further certifying to the results thereof.
(b) Attach to the governor rope a tag marked to show the date of the test and the name of the person or firm who conducted it.
(4) The distance between any 100 continuous links of roller chain, measured from centerline of pin, shall not be more than + or - 1% of the rated pitch of the chain being tested. For example, 100 links of standard series single strand #40 roller chain, which has a pitch length of 1/2 inch shall not be more than 50 1/2 inches or less than 49 1/2 inches.
(5) The inspection of chain links shall be made at not less than 3 points picked at random.