Minn. R. agency 151, ch. 1370, pt. 1370.0210 - ILLUMINATION
Subpart 1.
Minimum illumination.
At least five foot candles of illumination must be provided at floor level inside the storm shelter and at exits.
Subp. 2.
Source.
An emergency lighting system must be supplied from storage batteries or an on-site generator installed in accordance with the requirements of chapter 1315.