19 CSR 30-22.010 - General Design and Construction Standards for Rehabilitation Hospitals
PUBLISHERS NOTE: The publication of the full text of the material that the adopting agency has incorporated by reference in this rule would be unduly cumbersome or expensive. Therefore, the full text of that material will be made available to any interested person at both the Office of the Secretary of State and the office of the adopting agency, pursuant to section 536.031.4, RSMo. Such material will be provided at the cost established by state law.
TABLE I
PRESSURE RELATIONSHIPS AND VENTILATION OF CERTAIN HOSPITAL AREAS
|
Area Designation |
Relationship to Adjacent Areas |
Pressure Air From Outdoors |
All Supply Changes of Outdoor Air Per Hour |
Minimum Air Air Changes Per Hour |
Minimum Total Exhausted Directly to Outdoors |
All Air Recirculated Within Room |
|
Intensive care |
+ |
- |
2 |
6 |
- |
No |
|
Patient room |
0 |
- |
2 |
2 |
- |
- |
|
Patient area corridor |
0 |
- |
2 |
4 |
- |
- |
|
Isolation room |
0 |
- |
2 |
6 |
Yes |
No |
|
Isolation anteroom |
0 |
- |
2 |
6 |
Yes |
No |
|
Treatment room |
0 |
- |
2 |
6 |
- |
No |
|
X-ray, fluoroscopy room |
- |
- |
2 |
6 |
Yes |
No |
|
Physical therapy & hydrotherapy |
- |
- |
2 |
6 |
- |
- |
|
Soiled workroom |
- |
- |
2 |
4 |
- |
No |
|
Clean workroom |
+ |
- |
2 |
4 |
- |
- |
|
Autopsy and darkroom |
- |
- |
2 |
12 |
Yes |
No |
|
Toilet room |
- |
- |
- |
10 |
Yes |
No |
|
Bedpan room |
- |
- |
- |
10 |
Yes |
No |
|
Bathroom |
- |
- |
- |
10 |
Yes |
No |
|
Janitor's closet |
- |
- |
- |
10 |
Yes |
No |
|
Sterilizer equipment room |
- |
- |
- |
10 |
Yes |
No |
|
Linen and trash chute roo |
ms- |
- |
- |
10 |
Yes |
No |
|
Laboratory, general |
- |
- |
2 |
6 |
- |
- |
|
Food preparation centers |
0 |
- |
2 |
10 |
Yes |
No |
|
Dishwashing room |
- |
- |
- |
10 |
Yes |
No |
|
Dietary day storage |
0 |
- |
- |
2 |
- |
No |
|
Laundry, general |
0 |
- |
2 |
10 |
Yes |
No |
|
Soiled linen sorting and storage |
- |
- |
- |
10 |
Yes |
No |
|
Clean linen storage |
+ |
- |
2 |
2 |
- |
- |
|
Central medical and surgical supply |
||||||
|
Soiled or decontamination room |
- |
- |
2 |
4 |
- |
No |
|
Clean workroom |
+ |
- |
2 |
4 |
- |
- |
|
Unsterile supply storage |
0 |
- |
2 |
2 |
- |
- |
|
+=Positive |
-=Negative |
0=Equal |
-=Optional |
Stop valves shall be provided at each fixture.
|
Clinical |
Use Dietary |
Laundry |
|
|
gal/hr/bed |
6 1/2 |
4 |
4 1/2 |
|
Temp °F |
110° |
180° |
180° |
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.