Nev. Admin. Code § 444.839 - Elevated mound system: Design criteria
1. An elevated
mound system must not be constructed on a slope that is:
(a) Greater than 6 percent, if the soils
comprising the slope have percolation rates that are slower than 60 minutes per
inch; or
(b) Greater than 12
percent, if the soils comprising the slope have percolation rates that are
equal to or faster than 60 minutes per inch.
2. At least 4 feet of unsaturated soil or
fill material, or any combination thereof, must be maintained between the top
of the seasonal high groundwater table or any impervious barrier such as
bedrock. On sloping sites, the depth of unsaturated soil and fill material must
be increased to maintain a level bed.
3. Percolation tests must be conducted at the
depth anticipated by the engineer as being the point of interface of the native
soil and sand fill, and at a depth of 20 inches below the surface of the native
soil. The size of the required basal area of the elevated mound system must be
based on the slowest percolation rate.
4. The fill material for the elevated mound
system must meet the following criteria:
Sieve Size | Percent by Weight Passing Sieve |
3/8 inch | 100 |
No. 4 | 95-100 |
No. 8 | 80-100 |
No. 16 | 45-85 |
No. 30 | 15-60 |
No. 50 | 3-15 |
No. 100 | 0-4 |
5.
Whenever practical, the bed for an elevated mound system must be a rectangular
bed with a long axis that is parallel to the contour of the slope to minimize
the possibility of seepage from the base of the elevated mound. The minimum
area of the bed must be based on an estimated flow of 150 gallons per day per
bedroom and a design application rate of 1.2 gallons per day per square foot.
The bed must be filled with at least 9 inches of clean, graded aggregate that
ranges in size from 3/4 to 2 1/2 inches.
6. The basal area of an elevated mound system
must be sufficiently large enough to absorb the wastewater before it reaches
the perimeter of the elevated mound to avoid the surfacing of the effluent. The
minimum basal area must be based on the minimum capacity for a septic tank
required by NAC 444.8306 and a design infiltration rate as follows:
Percolation Rate (minutes per inch) | Infiltration Rate (gallons per square foot) |
0-30 | 1.2 |
31-45 | .75 |
46-60 | .50 |
61-120 | .25 |
7.
If the site on which an elevated mound system will be located is:
(a) Flat, the entire basal area, calculated
as length multiplied by width, must be used to determine the area needed for
the elevated mound system.
(b)
Sloping, only the area below and down slope from the absorption bed, calculated
as W x (A + I), must be used to determine the area needed for the elevated
mound system, where:
(1) "W" equals the width
of the absorption bed;
(2) "A"
equals the length of the absorption bed; and
(3) "I" equals the required side slope of the
elevated mound system as measured from the edge of the absorption bed to the
perimeter of the mound in accordance with subsection 8.
8. The side slopes of the elevated
mound system must extend in a horizontal to vertical ratio that is at least 3
to 1. The entire absorption bed must be covered with at least 1 foot of
topsoil. The topsoil cap, which must be placed at the center of the mound, must
maintain a minimum slope of 2 percent away from the crown. Untreated building
paper, straw, geotextile fabric, or any similar covering approved by the health
authority, must be placed over the aggregate in the absorption bed before the
topsoil is placed.
9. At least one
observation standpipe which extends down to the fill sand must be installed in
the absorption bed.
10. The
following is a diagram of an elevated mound:
Click here to view image.
Click here to view image.
Notes
NRS 439.200, 444.650
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.