N.J. Admin. Code § 5:21-6.2 - System planning, design, and placement
(a) The planning,
design, construction, installation, modification, and operation of any treatment
works or sanitary sewer system shall be in accordance with the flow and design
criteria set forth in N.J.A.C. 7:14A-23 and with the applicable NJDEP rules
implementing the New Jersey Water Pollution Control Act (N.J.S.A.
58:10A-1 et seq.) and the New Jersey Water Quality
Planning Act (N.J.S.A. 58:11A-1 et seq.); and, for
items not covered by NJDEP rules, with ASCE Manual on Engineering Practice No. 60,
incorporated herein by reference; and, in the Pinelands Area, with the Pinelands
Comprehensive Management Plan and, in the coastal area, with NJDEP rules
implementing the Coastal Area Facilities Review Act (N.J.S.A.
13:19-1 et seq.). Where the NJDEP accepts reduced
flows, those reduced flows shall also be accepted under these rules.
(b) Sanitary sewer pumping stations shall be
considered where gravity system design leads to excessive sewer depths which are not
economically justifiable and shall comply with
N.J.A.C.
7:14A-23.10, 11 and 12.
(c) System design and placement shall comply with
the following specifications:
1. Except where
otherwise specified by municipality or utility authority, sanitary sewer manholes,
when located within the municipal right-of-way, shall be at or near the center line
of the paved cartway, but at a five-foot minimum from the edge of the pavement.
Sanitary sewer mains shall be a minimum of 10 feet from the right-of-way
line.
2. Easements shall be in a form
approved by the utility authority or the municipal engineer and municipal attorney.
Easements shall be required for all sanitary sewer lines which are not within a
public right-of-way. Easements shall be a minimum of 20 feet wide for sanitary
sewers that are not more than 15 feet deep. For sewers that are more than 15 feet
deep, easements shall be a minimum of 30 feet wide. The depth of the sewer shall be
measured from the design invert of the pipe to the surface of the proposed final
grading. Where the easement is located adjacent to a right of way, the municipality
or authority may approve a narrower easement.
3. Common sewer laterals shall be permitted in
accordance with the Plumbing Subcode of the Uniform Construction Code (N.J.A.C.
5:23-3.15 ).
4. All sewers shall be designed to meet the New
Jersey Department of Environmental Protection's slope standards at
N.J.A.C.
7:14A-23.6(b).
5. Except where shallower depths are permitted by
the municipality or utility authority, sewer lines, including force mains and
laterals, shall be constructed at least three feet below the proposed grade (as
measured from the top of the pipe to the grade elevation).
6. Pipe materials used in the construction of
gravity sanitary sewers shall be reinforced concrete, ductile iron, PVC, corrugated
polypropylene, or clay pipe. All pipe and appurtenances shall comply with AWWA and
ASTM standards referenced in this paragraph, which are incorporated herein by
reference. Where PVC or polypropylene pipe is installed, a metallic locator tape
shall also be installed in the trench adjacent to the pipe.
i. Reinforced concrete pipe shall be used only in
sizes 24 inches and larger and shall meet all the requirements of ASTM C76. All pipe
shall be Class III strength installed with class C ordinary bedding, except in the
following conditions where stronger pipe may be required:
(1) For depths less than three feet, measured from
the top of the pipe, installed under traffic areas, Marston Class IV pipe shall be
required.
(2) The presence of clay
soils, poor bedding conditions, or other unusual loading conditions shall be given
special consideration and the developer shall submit an engineering analysis to the
municipality or authority for approval.
ii. PVC sewer pipe shall have bell and spigot ends
and O-ring rubber gasketed joints. PVC pipe and fittings shall conform to ASTM
D3034, with a minimum wall thickness designation of SDR 35 or shall conform to ASTM
F679, F789, F794, or F949 with a designated pipe stiffness of PS-46.
(1) The plastic material from which the pipe and
fittings are extruded shall be impact types of PVC, unplasticized, having high
mechanical strength and maximum chemical resistance conforming to Type 1, Grade 1 of
the specification for rigid polyvinyl chloride compounds, ASTM D1784.
(2) Pipe shall be free from defects, such as
bubbles or other imperfections, in accordance with accepted commercial practice.
Test results demonstrating that the pipe meets ASTM D2444 for impact and ASTM D2321
for deflection and pipe stiffness, shall be provided when requested by the
municipality or utility authority.
(3)
Joints shall conform to ASTM D3212. Rubber ring gaskets shall conform to ASTM F477.
The gasket shall be the sole element depended upon to make the joint
watertight.
(4) The pipe shall be
installed as specified in ASTM D2321 and as specified in Figure 6.1. If used in
unstable soil or areas of excessive ground water, the designer will take special
precautions, such as poured concrete slabs.
(5) Bedding, haunching and initial backfill
material shall be placed in six-inch lifts and be Class IA, IB, or II embedment
material conforming with ASTM D2321, unless otherwise approved in writing by the
municipal or utility authority engineer. Soil aggregate I-8 conforming to Article
901.09, Table 901-2 of the New Jersey Department of Transportation's Standard
Specifications for Road and Bridge Construction when compacted to 95 percent maximum
dry density, and stone crushing conforming with AASHTO designation M43-88 (ASTM
designation D448) size no. 8, 1/8 inch to 3/8 inch (2.36 mm to 9.25 mm) meet this
requirement. All material shall be clean and free flowing and shall meet all ASTM
C33 specifications for quality and soundness.
iii. Ductile iron pipe shall be centrifugally cast
in metal or sand-lined molds to ANSI/AWWA C151/A21.51. Joints shall be rubber
gasketed joints that conform to ANSI/AWWA C111/A21.11 or flanged joints that comply
with ANSI/AWWA C115/A21.15. Pipe shall be a minimum of Class 50. The outside of the
pipe shall be coated with a uniform thickness of hot applied asphaltic coating. In
corrosive soils, pipe shall be encased in polyethylene in accordance with ANSI/AWWA
C105/A21.5. Ductile iron pipe shall be installed with Class C, Ordinary Bedding,
when site conditions allow. The inside shall be lined with cement in accordance with
ANSI/AWWA C104/A21.4 or, where hydrogen sulfide is present, ductile iron pipe with
polyethylene coating that protects the interior of the pipe shall be used.
iv. Clay pipe shall comply with ASTM
C700.
v. Corrugated polypropylene
sanitary sewer pipe shall have bell and spigot ends and O-ring rubber, gasket
joints. Polypropylene pipe and fittings shall conform to ASTM F2764 or ASTM F2736,
incorporated herein by reference, depending on size. Polypropylene pipe 12 to 60
inches shall meet or exceed the designated pipe stiffness of PS-46 when tested in
accordance with ASTM D2412, Standard Test Method for Determination of External
Loading Characteristics of Plastic Pipe by Parallel-Plate Loading, incorporated
herein by reference.
(1) Plastic material shall
conform to ASTM D4101, Standard Specification for Polypropylene Injection and
Extrusion Materials, incorporated herein by reference.
(2) Joints shall conform to ASTM D-3212, Standard
Specification for Joints for Drain and Sewer Plastic Pipe Using Flexible Elastomeric
Seals. Rubber ring gaskets must meet ASTM F477, Standard Specification for
Elastomeric Seals (Gaskets) for Joining Plastic Pipe.
(3) Installation shall be in accordance with ASTM
2321, Standard Specification for Underground Installation of Thermoplastic Pipe for
Sewers and Other Gravity-Flow Applications. Generally, plastic pipe should not be
used in conditions that expose it to constant hydrostatic pressure. If used in
unstable soil or areas of excessive groundwater, the designer will take special
precautions, such as poured concrete slabs.
(4) Bedding, haunching, and initial backfill
material shall be placed in six-inch lifts and be Class IA, IB, or II embedment
material conforming with ASTM D2321, unless otherwise approved by the municipal or
utility authority engineer. Soil aggregate I-8 conforming to Article 901.09, Table
901-2 of the New Jersey Department of Transportation's Standard Specifications for
Road and Bridge Construction when compacted to 95 percent maximum dry density, and
stone crushing conforming with AASHTO designation M43-88 (ASTM designation D448)
size no. 8, 1/8 inch to 3/8 inch (2.36 mm to 9.25 mm) meet this requirement. All
material shall be clean and free flowing, and shall meet all ASTM C33 specifications
for quality and soundness.
7. Inverted siphons and outfalls shall be
constructed of ductile iron pipe or PVC pipe, as specified above. Inverted siphons
shall consist of a minimum of two pipes with provisions for flushing. Flow control
gates shall be provided in the chambers.
8. Force mains shall be designed in accordance
with the requirements of N.J.A.C. 7:14A-23. Force mains shall be constructed of
ductile iron pipe, as specified above, or PVC pipe that meets ASTM D1785, ASTM D2241
or AWWA C909. Where PVC pipe is installed, a metallic locator tape also shall be
installed in the trench adjacent to the pipe.
9. In addition to the pipe materials at
N.J.A.C.
7:14A-23.6(b)5, PVC pipe shall be
considered a suitable material.
10. For
other than PVC pipe, pipe and manhole bedding shall be provided as specified in
"Gravity Sanitary Sewer Design and Construction, ASCE Manual and Reports on
Engineering Practice No. 60," prepared by the Joint Task Force of the American
Society of Civil Engineers and Water Pollution Control Federation, New York, 1969.
Any pipe material not covered by this manual shall be installed in accordance with
the manufacturer's recommendations.
i. The
municipality or the authority may require the developer to provide an opinion of a
professional engineer regarding the suitability of the on-site material to be used
as backfill. The municipality or authority shall rely on this opinion.
ii. Where the on-site material is deemed suitable,
the opinion shall specify the appropriate installation methods for the material.
Where the on-site material is deemed not suitable, the opinion shall specify
modification or replacement of the material and the appropriate installation methods
for the specified material.
11. Manholes shall comply with the standards in
ASCE Manual on Engineering Practice No. 60, and shall meet the following
requirements:
i. Manholes shall be precast concrete
or concrete block. Manhole barrels shall be a minimum of four feet in diameter when
serving sewers 24 inches or less in diameter, and shall be a minimum of five feet in
diameter when serving sewers greater than 24 inches in diameter. Where manholes are
precast, the base and first section shall be monolithically cast. Concrete block
shall be coated with two coats of Portland cement mortar. Precast concrete or
concrete block shall be sealed with two coats of an acceptable waterproofing tar,
asphalt, or polyplastic alloy, with enough time allowed between the seal coats to
bond.
ii. Masonry brick, concrete block,
or half rings may be used to make vertical adjustments to rims.
iii. Where pipe size varies, crowns of pipes shall
be matched, except in special conditions, as required by applicable NJDEP
rules.
iv. If precast manhole barrels
and cones are used, they shall conform to ASTM C478, with round rubber gasketed
joints conforming to ASTM C443. Maximum absorption shall be nine percent, in
accordance with ASTM C478, method A. Cracked manholes shall not be used. The top
riser section of precast manholes shall terminate less than 18 inches below the
finished grade to provide for proper adjustment.
v. Manhole frames and covers shall be of cast iron
conforming to ASTM A48, Class 30 or ductile iron conforming to ASTM 536, and shall
be suitable for H-20 loading capacity. All manhole covers in unpaved rights-of-way
or in remote areas shall be provided with a locking device, as specified by the
municipality or utility authority. The words " SANITARY SEWER" shall be cast
integrally into the manhole cover.
vi.
Manholes shall be supplied with flexible, watertight adapters, such as inserts or
gaskets, conforming to ASTM C923 and suitable for the pipe materials used.
vii. Masonry units shall conform to the following
requirements:
(1) Clay or shale brick shall conform
to AASHTO M114, grade MW, with the following modifications:
(A) The length of the brick shall be not less than
7.75 inches and shall be not more than 8.25 inches. The width of the brick shall be
not less than 3.50 inches and not more than 3.88 inches. The depth of the brick
shall be not less than 2.10 inches and not more than 2.38 inches.
(B) The maximum water absorption, by five hour
boiling, shall be 14 percent based on the average of five bricks, and shall be 16
percent for individual bricks.
(2) Concrete block shall be solid, precast
segmental concrete masonry units. Portland cement shall conform to ASTM C150.
Concrete block shall conform to the following dimensional requirements:
(A) The blocks shall be either rectangular in
shape, or shall be curved blocks with the inside and outside surfaces curved to the
required radii, whichever is appropriate to the shape of the structure. The length
shall be not less than 12 inches and not more than 18 inches. The height shall be
not less than five inches and not more than eight inches. The width shall be not
less than eight inches. Blocks of special shapes and heights may be used to allow
for the reduction of cross sectional area at the cones or tops of manholes, or may
be used in the top courses of all structures so that the head castings shall be set
at the required elevation on a mortar bed not more than one-half inch thick without
cutting the blocks. All blocks shall have an interlocking-type joint at the ends, so
as to form a strong, rigid structure. All blocks shall be sound and free from all
cracks or other defects.
(3)
Concrete brick shall conform to the requirements of vii(2)(A) above except that the
dimensions shall conform to the requirements for clay or shale brick in vii(1)(A)
above.
12.
Laterals and cleanouts shall comply with the following:
i. The house connection or lateral from the street
main to the cleanout shall be considered an integral part of the sanitary sewer
system. The type of material used for the house connection shall be as follows:
four-inch cast iron soil pipe, extra heavy; four-inch PVC pipe, Schedule 40 or SDR
35; four-inch ABS plastic pipe, SDR 35; or four-inch ductile iron pipe. Common
laterals for multifamily units shall be designed to have adequate conveyance
capacity.
ii. Wye connections shall be
the same material as the sewer main. Saddles shall be used only for connection to an
existing main.
iii. Bends in house
connection lines shall be made using standard fittings. A riser with a cleanout
shall be provided in the lateral between the edge of the pavement and property line
or within a designated easement as determined by the municipality.
iv. Inspection cleanouts or observation tees
within the easement or right-of-way shall be fitted with either a metallic cap or a
nonmetal cap fitted with a metallic plug that is suitable for locating the cleanout.
Caps shall have a depressed or inverted nut. The inspection cleanout or observation
tee shall be placed between the curb or edge of pavement and property line or within
a designated easement.
v. Connections
beyond the cleanout are under the jurisdiction of the Plumbing Subcode of the
Uniform Construction Code (N.J.A.C. 5:23-3.15 )
through the Plumbing Subcode official. The pipe size and specifications shall comply
with the regulations and requirements of the Plumbing Subcode of the Uniform
Construction Code.
vi. As-built drawings
that include the location of plumbing wyes, as supplied by the contractor, shall be
submitted to the municipal engineer.
Data in image
Notes
See: 29 N.J.R. 1296(a).
Amended by R.1999 d.374, effective
See: 31 N.J.R. 477(a), 31 N.J.R. 3259(a).
Rewrote the section.
Administrative correction.
See: 32 N.J.R. 684(b).
Amended by R.2000 d.480, effective
See: 32 N.J.R. 2670(b), 32 N.J.R. 4277(a).
In (c), rewrote 3, inserted last sentence of introductory paragraph to 6, rewrote 6ii(4) and (5), inserted reference to AWWA C909 and inserted last sentence in 8, and rewrote 11v; and amended Figure 6.1.
Amended by R.2008 d.26, effective
See: 39 N.J.R. 4363(a), 40 N.J.R. 613(a).
In (c)6ii(5), deleted "1989" preceding "New Jersey".
Amended by R.2011 d.136, effective
See: 43 N.J.R. 236(a), 43 N.J.R. 1249(a).
In the introductory paragraph of (c)6, inserted "corrugated polypropylene" and "or polypropylene"; in (c)6ii(4), rewrote the last sentence; and added (c)6v.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.