N.J. Admin. Code § 7:10-12.33 - Chemical and physical treatment
(a) General requirements
for chemical and physical treatment are as follows:
1. A public noncommunity water system using a
surface water source is subject to the requirements of
7:10-11.8, 11.12, 11.13 and
11.14.
2. Treatment facilities shall be
capable of producing water that meets the applicable State primary and/or secondary
drinking water regulations at N.J.A.C. 7:10-5 and 7.
3. Treatment units shall be of sufficient capacity
to produce the daily volumes of water required pursuant to
7:10-12.7.
4. All filter shells, ion-exchange pressure tanks
and chemical solution feed drums shall be constructed of corrosion resistant
materials or contain non-corrodible liners.
5. Point of entry treatment (POET) devices may be
used to treat water in any public noncommunity or nonpublic water system. The
Department recommends that such devices be certified to meet appropriate ANSI/NSF
standards 42, 44, 53, 55, 58, and 62 as amended and supplemented, or the equivalent.
POET devices shall also meet ANSI/NSF Standard 61 if used in public noncommunity
water systems. In addition, POET devices shall meet the following requirements:
i. Each device shall be equipped with sampling
water taps before and after the point at which treatment is applied;
ii. The manufacturer's specifications and the
owner's manual for operation and maintenance of each POET device shall be available
on-site at all times;
iii. The owner of
the water system shall conduct an efficiency test of the device upon its
installation. The administrative authority may require the owner of the public
noncommunity water system to conduct periodic water quality testing in addition to
the quarterly monitoring required under
7:10-5.2(a)13 if the
POET device is installed to remove primary contaminants.
6. Wastewater resulting from the backwashing or
regeneration of filter media and/or ion exchange resin shall not be discharged to a
sanitary sewer system except in accordance with the New Jersey Pollutant Discharge
Elimination System rules, N.J.A.C. 7:14A, and with written approval from the
appropriate sewerage authority.
(b) Regulations for corrosion control are as
follows:
1. pH adjustment for corrosion control is
recommended when the pH of the raw water is less than 6.5. The pH adjustment system
used for corrosion control shall be capable of raising the pH to a minimum of 7.5
units.
2. A neutralizing filter
consisting of a bed of graded limestone may be used to adjust pH.
3. Injection of alkaline chemicals may be used to
adjust pH only if the following conditions are met:
i. Only soda-ash, lime, or caustic soda shall be
fed by means of a positive displacement pump. Due to safety considerations, the
Department does not recommend using caustic soda in small water systems and single
dwelling water supply systems.
ii.
Operation of the feed pump shall be synchronized with the operation with the well
pump.
iii. Safety equipment including
respirator, gloves, apron, shower and eye wash facilities shall be
provided.
(c)
Regulations for removal of iron and manganese are as follows:
1. Iron and manganese removal units shall include
an oxidizing process (natural precipitation or chemical precipitation) followed by a
filtration process.
2. Iron and
manganese removal units which include an open aeration process shall be designed and
constructed so as to minimize dust pickup. All air which enters the oxidizing unit
shall pass through a corrosion-resistant screen of not less than 24 mesh in order to
prevent the entry of insects. Forced air which enters the oxidizing unit shall pass
through air particulate filters.
3. Iron
and manganese removal units which include an ion exchange process (for example,
water softening) shall be designed and constructed such that the treated water will
not contain a sodium concentration in excess of 50 mg/l pursuant to N.J.A.C. 7:10-7.
The treated water shall not be softened to zero hardness. Potassium regenerant may
be used as an alternative to sodium regenerant.
(d) Packed column aeration (PCA) units or
equivalent air strippers shall be capable of removing volatile organic compounds
(VOCs) from at least twice the maximum levels found in the water to below the
applicable MCLs. If the PCA unit is followed by a granular activated carbon (GAC)
unit(s), the removal of VOCs may be achieved through the combined use of both
treatment units.
1. Each air intake on forced
aeration or mechanically induced aeration systems must be equipped with an air
particulate filter.
2. Taps by which
water can be sampled shall be placed before and after the PCA unit.
(e) Granular activated carbon (GAC)
units used for the removal of VOCs shall meet with the following requirements:
1. Each GAC unit shall have a minimum carbon life
(prior to VOCs breakthrough) of three months;
2. Taps by which water can be sampled shall be
placed before and after each GAC unit tank; and
3. Only virgin GAC shall be used, except
regenerated GAC may be used if such GAC was used previously only in potable water
treatment plants and regenerated in facilities used only for potable water treatment
plant filter media.
(f) Any
type of water treatment not described in (a) through (e) above shall meet the
requirements of 7:10-11.15, as applicable.
Notes
See: 36 New Jersey Register 295(a), 36 New Jersey Register 5383(b).
In (a)5, rewrote iii.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.