N.D. Admin Code 24.1-06-02-10 - (NEC 210) Branch circuits
Branch circuits shall comply with article 210, 2023 edition, National Electrical Code (first version, printed in 2022).
1. The total connected load shall be divided
as evenly as practicable, between the two ungrounded conductors of a three-wire
system and three conductors of a four-wire wye system.
2. In a dwelling unit, a separate circuit
with disconnect shall be provided for the purpose of operating or controlling
electrical equipment for primary source heating units. Wiring requirements for
fixed electrical space heating equipment is provided under article 424, 2023
edition, National Electrical Code, (first version, printed in 2022).
3. A minimum of six 20-amp small appliance
branch circuits shall be installed for counter receptacles in kitchens that are
used to serve public gatherings at schools, churches, lodges, and similar
buildings. Any island counter in these locations shall have at least one
receptacle.
4. In dwelling
occupancies. A minimum of three 20-amp small appliance branch circuits shall be
installed to supply receptacle outlets in kitchen, pantry, dining room, and
breakfast room. These circuits shall not supply other outlets and shall have
conductors not smaller than no. 12. Two of these circuits shall supply
receptacle outlets on or near work counter area and so arranged that adjacent
receptacles are not on the same circuit.
5. In dwelling occupancies, one 20-amp
bathroom circuit for receptacles shall not feed more than two
bathrooms.
6. Fifteen and twenty
ampere receptacles supplying sewer pumps and sump pumps shall not need arc
fault circuit protection, but shall be ground-fault protected or a single
receptacle on a dedicated circuit.
7. Fifteen and twenty ampere receptacles
supplying power for garage door openers located in attached or detached garages
associated with dwelling units shall be ground-fault protected or a single
receptacle installed.
8. Portable
cleaning equipment receptacle outlets shall be installed in corridors and
located so that no point in the corridor along the floor line, measured
horizontally, is more than twenty-five feet [7.62 meters] from an
outlet.
9. Exception: 2023 edition,
National Electrical Code (first version, printed in 2022), article
210.11(C)(4): Requirements shall not include buildings two hundred fifty square
feet [23.23 square meters] or smaller.
10. Exception: 2023 edition, National
Electrical Code (first version, printed in 2022), article 210.12(B): AFCI
protection is not required for the following:
a. Refrigeration appliances if a single
receptacle on a dedicated circuit is installed;
b. Furnaces used for main heating
source.
11. Exception:
2023 edition, National Electrical Code (first version, printed in 2022),
article 210.8(A): GFCI protection shall not be required for refrigeration
appliances in dwelling units if a single receptacle on an individual branch
circuit is installed.
12.
Exception: 2023 edition, National Electrical Code (first version, printed in
2022), article 210.52(C)(2), island and peninsular countertops and work
surfaces: receptacle outlets shall be permitted to be located not more than
twelve inches [30.48 centimeters] below the countertop or work surface.
Receptacles installed below a countertop or work surface shall not be located
where the countertop or work surface extends more than six inches [15.24
centimeters] beyond its support base.
Notes
General Authority: NDCC 43-09-05
Law Implemented: NDCC 43-09-21, 43-09-22
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Branch circuits shall comply with article 210, 2017 edition, National Electrical Code.
1. The total connected load shall be divided as evenly as practicable, between the two ungrounded conductors of a threewire system and three conductors of a four-wire wye system.
2. In a dwelling unit, a separate circuit with disconnect shall be provided for the purpose of operating or controlling electrical equipment for primary source heating units. Wiring requirements for fixed electrical space heating equipment is provided under article 424, 2020 edition, National Electrical Code.
3. A minimum of six 20-amp small appliance branch circuits shall be installed for counter receptacles in kitchens that may be used to serve public gatherings at schools, churches, lodges, and similar buildings. Any island counter in these locations shall have at least one receptacle.
4. In dwelling occupancies. A minimum of three 20-amp small appliance branch circuits shall be installed to supply receptacle outlets in kitchen, pantry, dining room, and breakfast room. These circuits shall not supply other outlets and shall have conductors not smaller than no. 12. Two of these circuits shall supply receptacle outlets on or near work counter area and so arranged that adjacent receptacles are not on the same circuit.
5. In dwelling occupancies, one 20-amp bathroom circuit for receptacles shall not feed more than two bathrooms.
6. Fifteen and twenty ampere receptacles supplying sewer pumps and sump pumps shall not need arc fault circuit protection, but shall be ground-fault protected or a single receptacle on a dedicated circuit.
7. Fifteen and twenty ampere receptacles supplying power for garage door openers located in attached or detached garages associated with dwelling units shall be ground-fault protected or a single receptacle installed.
8. Portable cleaning equipment receptacle outlets shall be installed in corridors and located so that no point in the corridor along the floor line, measured horizontally, is more than twenty-five feet [7.62 meters] from an outlet.
9. Exception: 2017 edition, National Electrical Code, article 210.11(C)(4): Requirements shall not include buildings two hundred fifty square feet or smaller.
10. Exception: 2020 edition, National Electrical Code, article 210.12(A): AFCI protection is not required for the following:
a. Refrigeration appliances if a single receptacle on a dedicated circuit is installed;
b. Furnaces used for main heating source.
Notes
General Authority: NDCC 43-09-05
Law Implemented: NDCC 43-09-21, 43-09-22