(A)
Section 901
General
(1)
901.1 Scope.
The
provisions of this rule shall specify where fire protection
systems are required and shall apply to the design, installation, inspection,
operation, testing and maintenance of all fire protection systems. The
requirements in this rule for fire protection systems in structures regulated
by the building code as listed in rule
1301:7-7-80
of the Administrative Code submitted for plan review in accordance with this
paragraph are subject to and do not supersede or otherwise conflict with the
requirements of paragraph (D)(2)(a)(104.2.1) of rule
1301:7-7-01
of the Administrative Code.
(2)
901.2
Construction documents.
Notwithstanding the requirements of paragraph
(D)(2)(a)(104.2.1) of rule
1301:7-7-01
of the Administrative Code, the fire code official shall have the
authority to require construction documents and calculations for all fire
protection systems and to require permits be obtained for the
installation, rehabilitation or modification of any fire protection system.
Construction documents for fire protection systems shall be submitted for
review prior to system installation. At locations or in structures not
regulated by the buildin code as listed in rule
1301:7-7-80
of the Administrative Code, the construction documents shall be reviewed and
approved by the fire code official prior to system
installation.
(3)
901.3 Permits.
Permits shall be required as set forth in rule
1301:7-7-01
of the Administrative Code and as required by the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(4)
901.4
Installation.
Fire protection systems
shall be maintained in accordance with the original installation standards for
that system. Required fire protection systems shall be
extended, altered or augmented as necessary to maintain and continue protection
where the building is altered, remodeled or added to. Alterations to fire
protection systems shall be done in accordance with the building code
as listed in rule
1301:7-7-80
of the Administrative Code and applicable standards.
(a)
901.4.1
Required fire protection systems.
Fire
protection systems required by this code or the building code as listed
in rule
1301:7-7-80
of the Administrative Code shall be installed, repaired, operated,
tested and maintained in accordance with this code. A fire protection system
for which a design option, exception or reduction to the provisions of this
code or the building code as listed in rule
1301:7-7-80
of the Administrative Code has been granted shall be considered a
required system.
(b)
901.4.2 Nonrequired fire protection
systems.
A fire protection system or
portion thereof not required by this code or the building code as
listed in rule
1301:7-7-80
of the Administrative Code shall be allowed to be furnished for
partial or complete protection provided such installed system meets the
applicable requirements of this code and the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(c)
901.4.3
Fire areas.
Where buildings, or portions
thereof, are divided into fire areas so as not to exceed the limits established
for requiring a fire protection system in accordance with this
rule, such fire areas shall be separated by fire barriers
constructed in accordance with section 707 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code or horizontal assemblies constructed in
accordance with section 711 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, or both, having a fire-resistance rating
of not less than that determined in accordance with section 707.3.10 of
the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(d)
901.4.4
Additional fire protection systems.
In
occupancies of a hazardous nature, where special hazards exist in addition to
the normal hazards of the occupancy, or where the fire code official determines
that access for fire apparatus is unduly difficult, the fire code official
shall have the authority to require additional safeguards. Such safeguards
include, but shall not be limited to, the following: automatic fire detection
systems, fire alarm systems, automatic fire-extinguishing systems, standpipe
systems, or portable or fixed extinguishers. Fire protection equipment required
under this paragraph shall be installed in accordance with
this code and the applicable referenced standards.
(e)
901.4.5
Appearance of equipment.
Any device that
has the physical appearance of life safety or fire protection equipment but
that does not perform that life safety or fire protection function shall be
prohibited.
(f)
901.4.6 Pump and riser room size.
Where provided, fire pump rooms and automatic sprinkler
system riser rooms shall be designed with adequate space for all equipment
necessary for the installation, as defined by the manufacturer, with sufficient
working space around the stationary equipment. Clearances around equipment to
elements of permanent construction, including other installed equipment and
appliances, shall be sufficient to allow inspection, service, repair or
replacement without removing such elements of permanent construction or
disabling the function of a required fire-resistance-rated assembly. Fire pump
and automatic sprinkler system riser rooms shall be provided with a door(s) and
an unobstructed passageway large enough to allow removal of the largest piece
of equipment.
(5)
901.5 Installation acceptance
testing.
Fire detection and alarm systems,
fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire
pump systems, private fire service mains and all other fire protection systems
and appurtenances thereto shall be subject to acceptance tests as contained in
the installation standards and as approved by the fire code official in
accordance with this code and the building official in accordance with section
901.5 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
1.
The fire code official shall be notified by the
responsible person of any scheduled acceptance testing of a fire protection
system not less than forty-eight hours prior to the occurrence of such
acceptance test Advanced notice of the test schedule shall be given to the
building official in accordance with section 901.5 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code.
2.
When
required by the fire code official all acceptance testing shall be conducted in
the presence of the fire code official.
3.
When
required by the fire code official all acceptance testing shall be conducted in
the presence of the person who installed the equipment or, if it is not
possible for the actual installer to be present the acceptance testing shall be
conducted in the presence of another qualified representative of the company
that installed the equipment.
(a)
901.5.1
Statement of compliance.
Before requesting
final inspection of the installation, where required by the
fire code official, the installing contractor shall furnish a written statement
to the fire code official that the subject fire protection system has been
installed in accordance with plans approved by the building code
official and has been tested in accordance with the manufacturer's
specifications and the appropriate installation standard. Any deviations from
the design standards shall be noted and copies of the approvals for such
deviations shall be attached to the written statement.
(b)
901.5.2
Occupancy.
It shall be
unlawful to occupy any portion of a building or structure until the required
fire detection, alarm and suppression systems have been tested,
inspected and approved by the fire code official in
accordance with this code and the building official in accordance with section
901.5 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(6)
901.6
Inspection, testing and maintenance.
Fire
detection, alarm and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative condition at all
times, and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected, tested and maintained or
removed. Any discontinuance or removal of nonrequired fire protection
equipment shall be approved by the fire code official. Such approval shall be
conditioned upon receipt of verification of building official determination
that such fire protection equipment is nonrequired.
(a)
901.6.1
Standards. Fire protection systems shall be inspected, tested and
maintained in accordance with the referenced standards listed in Table 901.6.1
of this rule.
Table 901.6.1
Fire protection system
maintenance standards
|
System
|
Standard
|
|
Portable fire
extinguishers
|
NFPA 10 as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Carbon dioxide
fire-extinguishing systems
|
NFPA 12 as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Halon 1301 fire-extinguishing
systems
|
NFPA 12A as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Dry-chemical extinguishing
systems
|
NFPA 17 as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Wet-chemical extinguishing
systems
|
NFPA 17A as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Water-based fire protection
systems
|
NFPA 25 as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Fire alarm systems
|
NFPA 72 as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Smoke and heat
vents
|
NFPA 204 as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Water-mist systems
|
NFPA 750 as listed in
rule
1301:7-7-80
of the Administrative Code
|
|
Clean-agent extinguishing
systems
|
NFPA 2001 as listed in
rule
1301:7-7-80
of the Administrative Code
|
(b)
901.6.2 Records.
Records of all system inspections, tests and
maintenance required by the referenced standards shall be maintained.
(i)
901.6.2.1
Records information. Initial records shall include the name of the
installation contractor, type of components installed, the
manufacturer of the components, location and number of components installed per
floor. Records shall also include the manufacturer's operation and maintenance
instruction manuals. Such records shall be maintained for the life of the
installation. Acceptance testing records (original documents) shall be
retained for the life of the system.
(c)
901.6.3 Annual inspection tag for fire protection
systems.
An inspection
tag shall be attached to each fire protection system near the main control
valve, main panel, or other such appropriate and visible location as determined
by the fire code official. The annual inspection tag shall contain the
following information:
1.
The individual performing the work and the
state fire marshal installer certification number(s) (when
applicable);
2.
Date of test;
3.
Results of
inspection and test;
4.
Deficiencies or impairments noted (yes or
no).
(i)
901.6.3.1
When a
sprinkler or standpipe system is found impaired or out of service, the tag
requirement shall include an impairment tag in accordance with NFPA 25 as
listed in rule
1301:7-7-80
of the Administrative Code.
(7)
901.7 Systems out of service. Where a
required fire protection system is out of service, the fire department and the
fire code official shall be notified immediately and, where required by the
fire code official, the building shall be either evacuated or an approved fire
watch shall be provided for all occupants left unprotected by the shutdown
until the fire protection system has been returned to service.
Where utilized, fire watches shall be
provided with not less than one approved means for notification of the fire
department and their only duty shall be to perform constant patrols of the
protected premises and keep watch for fires.
(a)
901.7.1
Impairment coordinator.
The building owner
shall assign an impairment coordinator to comply with the requirements of this
paragraph. In the absence of a specific designee, the owner
shall be considered the impairment coordinator.
(b)
901.7.2 Tag
required.
A tag shall be used to indicate
that a system, or portion thereof, has been removed from
service.
(c)
901.7.3 Placement of tag.
The tag shall be posted at each fire department
connection, system control valve, fire alarm control unit, fire alarm
annunciator and fire command center, indicating which system, or part thereof,
has been removed from service. The fire code official shall specify where the
tag is to be placed.
(d)
901.7.4 Preplanned impairment
programs.
Preplanned impairments shall be
authorized by the impairment coordinator. Before authorization is given, a
designated individual shall be responsible for verifying that all of the
following procedures have been implemented:
(i)
The extent and
expected duration of the impairment have been determined.
(ii)
The areas or
buildings involved have been inspected and the increased risks
determined.
(iii)
Recommendations have been submitted to management or
building owner/manager.
(iv)
The fire department has been notified.
(v)
The insurance
carrier, the alarm company, the building owner/manager and other authorities
having jurisdiction have been notified.
(vi)
The supervisors
in the areas to be affected have been notified.
(vii)
A tag
impairment system has been implemented.
(viii)
Necessary
tools and materials have been assembled on the impairment site.
(e)
901.7.5 Emergency impairments.
Where unplanned impairments occur, appropriate
emergency action shall be taken to minimize potential injury and damage. The
impairment coordinator shall implement the steps outlined in
paragraph (A)(7)(d)(901.7.4) of this
rule.
(f)
901.7.6 Restoring systems to service.
When impaired equipment is restored to normal working
order, the impairment coordinator shall verify that all of the following
procedures have been implemented:
(i)
Necessary inspections and tests have been conducted to
verify that affected systems are operational.
(ii)
Supervisors have
been advised that protection is restored.
(iii)
The fire
department has been advised that protection is restored.
(iv)
The building
owner/manager, insurance carrier, alarm company and other involved parties have
been advised that protection is restored.
(v)
The impairment
tag has been removed.
(8)
901.8
Removal of or tampering with equipment. It shall be unlawful for any
person to remove, tamper with or otherwise disturb any fire hydrant, fire
detection and alarm system, fire suppression system or other fire appliance
required by this code except for the purpose of extinguishing fire, training
purposes, recharging or making necessary repairs or where approved by the fire
code official.
(a)
901.8.1 Removal of or tampering with
appurtenances.
Locks, gates, doors,
barricades, chains, enclosures, signs, tags or seals that have
been installed by or at the direction of the fire code official shall not be
removed, unlocked, destroyed, tampered with or otherwise vandalized in any
manner.
(b)
901.8.2 Removal of existing occupant-use hose
lines.
The fire code official is
authorized to permit the removal of existing occupant-use hoses lines where all
of the following conditions exist:
(i)
Installation is not required by this code or the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
The hose line
would not be utilized by trained personnel or the fire
department.
(iii)
The remaining outlets are compatible with local fire
department fittings.
(c)
901.8.3 Notification of termination of supervisory
services.
The responsible
person shall notify the local fire code official of the termination of any
supervisory service within twenty-four (24) hours of such
termination.
(9)
901.9
Termination of monitoring service.
For
fire alarm systems required to be monitored by this code, notice shall be made
to the fire code official whenever alarm monitoring services are terminated.
Notice shall be made in writing, to the fire code official by the monitoring
service provider being terminated.
(10)
901.10 Recall of fire protection
components.
Any fire protection system
component regulated by this code that is the subject of a voluntary or
mandatory recall under federal law shall be replaced with approved, listed
components in compliance with the referenced standards of this code. The fire
code official shall be notified in writing by the building owner when the
recalled component parts have been replaced.
(B)
Section 902
Definitions
(1)
902.1 Definitions. The following terms are
defined in rule
1301:7-7-02 of the
Administrative Code.
"Alarm notification
appliance."
"Alarm
signal."
"Alarm verification
feature."
"Annunciator."
"Audible alarm notification
appliance."
"Automatic."
"Automatic fire-extinguishing
system."
"Automatic smoke detection
system."
"Automatic sprinkler
system."
"Automatic water mist
system."
"Average ambient sound
level."
"Carbon dioxide extinguishing
system."
"Clean
agent."
"Commercial motor
vehicle."
"Constantly attended
location."
"Deluge
system."
"Detector,
heat."
"Dry-chemical extinguishing
agent."
"Elevator
group."
"Emergency alarm
system."
"Emergency voice/alarm
communications."
"Fire alarm box,
manual."
"Fire alarm system."
"Fire area."
"Fire detector,
automatic."
"Fire protection
system."
"Fire safety
functions."
"Fixed base operator
(FBO)."
"Foam-extinguishing
system."
"Halogenated extinguishing
system."
"Impairment
coordinator."
"Initiating
device."
"Manual fire alarm
box."
"Multiple-station alarm
device."
"Multiple-station smoke
alarm."
"Notification
zone."
"Nuisance
alarm."
"Private
garage."
"Record
drawings."
"Single-station smoke
alarm."
"Sleeping
unit."
"Smoke
alarm."
"Smoke
detector."
"Standpipe system, classes
of."
"Class I
system."
"Class II
system."
"Class III system."
"Standpipes, types of."
"Automatic dry."
"Automatic wet."
"Manual dry."
"Manual wet."
"Semiautomatic
dry."
"Supervising
station."
"Supervisory
service."
"Supervisory
signal."
"Supervisory signal-initiating
device."
"Tires, bulk storage
of."
"Transient
aircraft."
"Trouble
signal."
"Visible alarm notification
appliance."
"Wet-chemical extinguishing
agent."
"Wireless protection
system."
"Zone."
"Zone,
notification."
(C)
Section 903
Automatic sprinkler systems
(1)
903.1
General.
Automatic sprinkler systems shall
comply with this paragraph.
(a)
903.1.1
Alternative protection. Alternative automatic fire-extinguishing systems
complying with paragraph (D)(904) of this rule may be
installed in lieu of automatic sprinkler protection where recognized
by the applicable standard and approved by the fire code official
pursuant to paragraph (A)(1)( 901.1) of this rule. At
locations or in structures not regulated by the building code as listed in rule
1301:7-7-80
of the Administrative Code, the alternative automatic fire-extinguishing system
shall be approved by the fire code official prior to system
installation.
(2)
903.2 Where
required.
Approved automatic sprinkler
systems in new buildings and structures shall be provided in the locations
where required by the building code as listed in rule
1301:7-7-80
of the Administrative Code and as described in this paragraph.
The requirements for automatic sprinkler systems in new buildings contained in
this rule are subject to and do not supersede or otherwise conflict with the
requirements of paragraph (D)(2)(a)(104.2.1) of rule
1301:7-7-01
of the Administrative Code.
Exception:
Spaces or areas in telecommunications buildings used
exclusively for telecommunications equipment, associated electrical power
distribution equipment, batteries and standby engines, provided those spaces or
areas are equipped throughout with an automatic smoke detection system in
accordance with paragraph (G)(2)( 907.2) of this
rule and are separated from the remainder of the building by not less
than 1-hour fire barriers constructed in accordance with section 707 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code or not less than 2-hour horizontal
assemblies constructed in accordance with section 711 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code, or both.
(a)
903.2.1
Group A. An automatic sprinkler system shall be provided throughout
buildings and portions thereof used as Group A occupancies as provided in this
paragraph. For Group A-1, A-2, A-3 and A-4 occupancies, the
automatic sprinkler system shall be provided throughout the story where the
fire area containing the Group A-1, A-2, A-3 or A-4 occupancy is located, and
throughout all stories from the Group A occupancy to, and including, the levels
of exit discharge serving the Group A occupancy. For Group A-5 occupancies, the
automatic sprinkler system shall be provided in the spaces indicated in
paragraph (C)(2)(a)(iv)(903.2.1.5) of this
rule.
(i)
903.2.1.1 Group A-1. An automatic
sprinkler system shall be provided for fire areas containing Group A-1
occupancies and intervening floors of the building where one of the following
conditions exists:
(a)
The fire area exceeds 12,000 square feet (1115
m2).
(b)
The fire area has
an occupant load of 300 or more.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
(d)
The fire area contains a multi-theater
complex.
(ii)
903.2.1.2 Group A-2. An automatic
sprinkler system shall be provided for fire areas containing Group A-2
occupancies and intervening floors of the building where one of the following
conditions exists:
(a)
The fire area exceeds 5,000 square feet (464
m2).
(b)
The fire area has
an occupant load of 100 or more.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
(iii)
903.2.1.3 Group A-3. An automatic
sprinkler system shall be provided for fire areas containing Group A-3
occupancies and intervening floors of the building where one of the following
conditions exists:
(a)
The fire area exceeds 12,000 square feet (1115
m2).
Exception:
Fire areas used exclusively for religious worship services
with fixed seating.
(b)
The fire area has
an occupant load of 300 or more.
Exceptions:
1.
Fire areas
used primarily for worship with fixed seating.
2.
Fire areas
without fixed seating not used for exhibition or
display.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
Exception:
Areas used exclusively as participant sports areas where the
main floor area is located at the same level as the level of exit discharge of
the main entrance and exit.
(iv)
903.2.1.4
Group A-4. An automatic sprinkler system shall be provided for fire
areas containing Group A-4 occupancies and intervening floors of the building
where one of the following conditions exists:
(a)
The fire area
exceeds 12,000 square feet (1115
m2).
(b)
The fire area has
an occupant load of 300 or more.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
Exception:
Areas used exclusively as participant sport areas where the
main floor area is located at the same level as the level of exit discharge of
the main entrance and exit.
(v)
903.2.1.5
Group A-5. An automatic sprinkler system shall be provided for Group A-5
occupancies in the following areas: concession stands, retail areas, press
boxes and other accessory use areas in excess of 1,000 square feet (93
m2).
(vi)
903.2.1.6
Assembly occupancies on roofs. Where an occupied roof has an assembly
occupancy with an occupant load exceeding 100 for Group A-2 and 300 for other
Group A occupancies, all floors between the occupied roof and the level of exit
discharge shall be equipped with an automatic sprinkler system in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) or
(C)(3)(a)(ii)(903.3.1.2) of this rule.
Exception:
Open parking garages of Type I or Type II
construction.
(vii)
903.2.1.7 Multiple fire areas. An
automatic sprinkler system shall be provided where multiple fire areas of Group
A-1, A-2, A-3 or A-4 occupancies share exit or exit access components and the
combined occupant load of these fire areas is 300 or more.
(b)
903.2.2 Ambulatory care facilities.
An automatic sprinkler system shall be installed
throughout the entire floor containing an ambulatory care facility where either
of the following conditions exist at any time:
(i)
Four or more care
recipients are incapable of self-preservation, whether rendered incapable by
staff or staff has accepted responsibility for care recipients already
incapable.
(ii)
One or more care recipients that are incapable of
self-preservation are located at other than the level of exit discharge serving
such facility.
In buildings where ambulatory care is
provided on levels other than the level of exit discharge, an automatic
sprinkler system shall be installed throughout the entire floor where such care
is provided as well as all floors below, and all floors between the level of
ambulatory care and the nearest level of exit discharge, including the level of
exit discharge.
(c)
903.2.3
Group E.
An automatic sprinkler system
shall be provided for Group E occupancies as follows:
(i)
Throughout all
Group E fire areas greater than 20,000 square feet
(1858 m2) in area.
(ii)
Throughout every
portion of educational buildings below the lowest level of exit discharge
serving that portion of the building.
Exception:
An automatic sprinkler system is not required in any
area below the lowest level of exit discharge serving that area where every
classroom throughout the building has not fewer than one exterior exit door at
ground level.
(iii)
Throughout every portion of Group E day care
facilities - 21/2 years or less of age.
Exception:
An automatic sprinkler system is not required in day care
facilities that provide care for more than five but no more than 100 children
21/2 years or less of age and the day care facilities are at the level of exit
discharge and where every room where care is provided has no fewer than one
exterior exit door for which the exit access and exit discharge do not require
the traversing of stairs.
(d)
903.2.4
Group F-1.
An automatic sprinkler system
shall be provided throughout all buildings containing a Group F-1 occupancy
where one of the following conditions exists:
1.
A Group F-1 fire
area exceeds 12,000 square feet (1115
m2).
2.
A Group F-1 fire
area is located more than three stories above grade plane.
3.
The combined area
of all Group F-1 fire areas on all floors, including any mezzanines, exceeds
24,000 square feet (2230 m2).
4.
A Group F-1
occupancy used for the manufacture of upholstered furniture or mattresses
exceeds 2,500 square feet (232 m2).
(i)
903.2.4.1
Woodworking operations. An automatic sprinkler system shall be provided
throughout all Group F-1 occupancy fire areas that contain woodworking
operations in excess of 2,500 square feet in area (232
m2) that generate finely divided combustible waste
or use finely divided combustible materials.
(e)
903.2.5 Group H.
Automatic sprinkler systems shall be provided in high-hazard
occupancies as required in paragraphs (C)(2)(e)(i)(903.2.5.1)
to (C)(2)(e)(iii)(903.2.5.3) of this
rule.
(i)
903.2.5.1 General. An automatic sprinkler
system shall be installed in Group H occupancies.
(ii)
903.2.5.2
Group H-5 occupancies. An automatic sprinkler system shall be installed
throughout buildings containing Group H-5 occupancies. The design of the
sprinkler system shall be not less than that required under the
building code as listed in rule
1301:7-7-80
of the Administrative Code for the occupancy hazard classifications in
accordance with Table 903.2.5.2 of this rule.
Where the design area of the sprinkler
system consists of a corridor protected by one row of sprinklers, the maximum
number of sprinklers required to be calculated is 13.
Table
903.2.5.2
Group H-5 sprinkler design
criteria
|
Location
|
Occupancy hazard
classification
|
|
Fabrication areas
|
Ordinary hazard group
2
|
|
Service corridors
|
Ordinary hazard group
2
|
|
Storage rooms without
dispensing
|
Ordinary hazard group
2
|
|
Storage rooms with
dispensing
|
Extra hazard group
2
|
|
Corridors
|
Ordinary hazard group
2
|
(iii)
903.2.5.3 Pyroxylin plastics. An automatic
sprinkler system shall be provided in buildings, or portions thereof, where
cellulose nitrate film or pyroxylin plastics are manufactured, stored or
handled in quantities exceeding 100 pounds (45 kg).
(f)
903.2.6
Group I.
An automatic sprinkler system
shall be provided throughout buildings with a Group I fire area.
Exceptions:
1.
An automatic
sprinkler system installed in accordance with paragraph
(C)(3)(a)(ii)(903.3.1.2) of this rule shall be permitted in
Group I-1 Condition 1 facilities.
2.
An automatic
sprinkler system is not required where Group I-4 day care facilities are at the
level of exit discharge and where every room where care is provided has not
fewer than one exterior exit door.
3.
In buildings where
Group I-4 day care is provided on levels other than the level of exit
discharge, an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) of this
rule shall be installed on the entire floor where care is provided,
all floors between the level of care and the level of exit discharge and all
floors below the level of exit discharge other than areas classified as an open
parking garage.
4.
An automatic sprinkler system is not required
in day care facilities that provide care for more than five but no more than
100 children 21/2 years or less of age and the day care facilities are at the
level of exit discharge and where every room where care is provided has no
fewer than one exterior exit door for which the exit access and exit discharge
do not require the traversing of stairs.
(g)
903.2.7
Group M.
An automatic sprinkler system
shall be provided throughout buildings containing a Group M occupancy where one
of the following conditions exists:
1.
A Group M fire area exceeds 12,000 square feet (1115
m2).
2.
A Group M fire
area is located more than three stories above grade plane.
3.
The combined area
of all Group M fire areas on all floors, including any mezzanines, exceeds
24,000 square feet (2230 m2).
4.
A Group M
occupancy used for the display and sale of upholstered furniture or mattresses
exceeds 5,000 square feet (464 m2).
(i)
903.2.7.1
High-piled storage. An automatic sprinkler system shall be provided as
required in rule
1301:7-7-32
of the Administrative Code in all buildings of Group M where storage
of merchandise is in high-piled or rack storage
arrays.
(h)
903.2.8
Group R. An automatic sprinkler system installed in accordance with
paragraph (C)(3)( 903.3) of this rule shall
be provided throughout all buildings with a Group R fire area.
Exception: Group
R-2.
An automatic
sprinkler system is not required in buildings of Group R-2 permitted to have a
single exit per section 1006.3.2 of the building code as listed in rule
1301:7-7-80
of the Administrative Code where:
1.
The
building is not used as an "SRO" occupancy as defined in rule
1301:7-7-02 of the
Administrative Code, and
2.
The exit
is constructed as an exterior stair per section 1027 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code, and
3.
The
dwelling units egress directly into an exit, and,
4.
Two-hour
fire barriers divide the building into fire areas with a maximum of two
dwelling units per floor and not more than six dwelling units per fire area,
and
5.
All dwelling units in the fire area must have separations as
required by section 708.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code for dwelling units, and
6.
The
building is limited to a basement and two stories above grade plane,
and
7.
The building contains no more than four dwelling units
per floor and no more than twelve dwelling units per building.
(i)
903.2.8.1
Group R-3. An automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(iii)(903.3.1.3) of this
rule shall be permitted in Group R-3 occupancies.
(ii)
[F]
903.2.8.2 Group R-4 Condition 1. An automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(iii)(903.3.1.3)
of this rule shall be permitted in Group R-4 Condition 1
occupancies.
(iii)
[F] 903.2.8.3 Group R-4 Condition 2. An
automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(ii)(903.3.1.2) of this
rule shall be permitted in Group R-4 Condition 2 occupancies. Attics
shall be protected in accordance with paragraph
(C)(2)(g)(iii)(a)(903.2.8.3.1) or
(C)(2)(g)(iii)(b)(903.2.8.3.2) of this
rule.
(a)
[F] 903.2.8.3.1 Attics used for living purposes,
storage or fuel-fired equipment. Attics used for living purposes,
storage or fuel-fired equipment shall be protected throughout with an automatic
sprinkler system installed in accordance with paragraph
(C)(3)(a)(ii)(903.3.1.2) of this rule.
(b)
[F]
903.2.8.3.2 Attics not used for living purposes, storage or fuel-fired
equipment.
Attics not used for living
purposes, storage or fuel-fired equipment shall be protected in accordance with
one of the following:
(i)
Attics protected throughout by a heat detector system
arranged to activate the building fire alarm system in accordance with
paragraph (G)(2)(j)(907.2.10) of this
rule.
(ii)
Attics constructed of noncombustible
materials.
(iii)
Attics constructed of fire-retardant-treated wood
framing complying with section 2303.2 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(iv)
The automatic
sprinkler system shall be extended to provide protection throughout the attic
space.
(iv)
903.2.8.4 Care facilities. An automatic
sprinkler system installed in accordance with paragraph
(C)(3)(a)(iii)(903.3.1.3) of this rule shall be permitted in
care facilities with five or fewer individuals in a single-family
dwelling.
(i)
903.2.9
Group S-1. An automatic sprinkler system shall be provided throughout
all buildings containing a Group S-1 occupancy where one of the following
conditions exists:
1.
A Group S-1 fire area exceeds 12,000 square feet (1115
m2).
2.
A Group S-1 fire
area is located more than three stories above grade plane.
3.
The combined area
of all Group S-1 fire areas on all floors, including any mezzanines, exceeds
24,000 square feet (2230 m2).
4.
A Group S-1 fire
area used for the storage of commercial motor vehicles where the fire area
exceeds 5,000 square feet (464 m2).
5.
A Group S-1
occupancy used for the storage of upholstered furniture or mattresses exceeds
2,500 square feet (232 m2).
(i)
903.2.9.1
Repair garages. An automatic sprinkler system shall be provided
throughout all buildings used as repair garages in accordance with section
406.8 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, as shown:
(a)
Buildings having
two or more stories above grade plane, including basements, with a fire area
containing a repair garage exceeding 10,000 square feet (929
m2).
(b)
Buildings no more
than one story above grade plane, with a fire area containing a repair garage
exceeding 12,000 square feet (1115
m2).
(c)
Buildings with
repair garages servicing vehicles parked in basements.
(d)
A Group S-1 fire
area used for the repair of commercial motor vehicles where the fire area
exceeds 5,000 square feet (464
m2).
(ii)
903.2.9.2
Bulk storage of tires. Buildings and structures where the area for the
storage of tires exceeds 20,000 cubic feet (566 m3)
shall be equipped throughout with an automatic sprinkler system in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) of this
rule.
(j)
903.2.10
Group S-2 enclosed parking garages. An automatic sprinkler system shall
be provided throughout buildings classified as enclosed parking garages in
accordance with section 406.6 of the building code as listed in rule
1301:7-7-80
of the Administrative Code where either of the following conditions
exists.
1.
Where
the fire area of the enclosed parking garage exceeds 12,000 square feet (1115
m2).
2.
Where the enclosed
parking garage is located beneath other groups.
Exception:
Enclosed parking garages located beneath Group R-3
occupancies.
(i)
903.2.10.1 Commercial parking garages. An
automatic sprinkler system shall be provided throughout buildings used for
storage of commercial motor vehicles where the fire area exceeds 5,000 square
feet (464 m2).
(k)
903.2.11
Specific buildings areas and hazards. In all occupancies other than
Group U, an automatic sprinkler system shall be installed for building design
or hazards in the locations set forth in paragraphs
(C)(2)(k)(i)(903.2.11.1) to (C)(2)(k)(vi)(903.2.11.6)
of this rule.
(i)
903.2.11.1 Stories without openings. An
automatic sprinkler system shall be installed throughout all stories, including
basements, of all buildings where the floor area exceeds 1,500 square feet (
139.4 m2) and where there is not provided not fewer
than one of the following types of exterior wall openings:
1.
Openings below
grade that lead directly to ground level by an exterior stairway complying with
paragraph (K)(1011) of rule
1301:7-7-10 of
the Administrative Code or an outside ramp complying with
paragraph (L)(1012) of rule
1301:7-7-10 of
the Administrative Code. Openings shall be located in each 50 linear
feet (15 240 mm), or fraction thereof, of exterior wall in the story on at
least one side. The required openings shall be distributed such that the lineal
distance between adjacent openings does not exceed 50 feet (15 240
mm).
2.
Openings entirely above the adjoining ground level
totaling not less than 20 square feet ( 1.86 m2) in
each 50 linear feet (15 240 mm), or fraction thereof, of exterior wall in the
story on at least one side. The required openings shall be distributed such
that the lineal distance between adjacent openings does not exceed 50 feet (15
240 mm). The height of the bottom of the clear opening shall not exceed 44
inches (1118 mm) measured from the floor.
(a)
903.2.11.1.1 Opening dimensions and access.
Openings shall have a minimum dimension of not less
than 30 inches (762 mm). Such openings shall be accessible to the fire
department from the exterior and shall not be obstructed in a manner that
fire-fighting or rescue cannot be accomplished from the
exterior.
(b)
903.2.11.1.2 Openings on one side only.
Where openings in a story are provided on only one side
and the opposite wall of such story is more than 75 feet (22 860 mm) from such
openings, the story shall be equipped throughout with an approved automatic
sprinkler system or openings as specified above shall be provided on not fewer
than two sides of the story.
(c)
903.2.11.1.3 Basements.
Where any portion of a basement is located more than 75 feet
(22 860 mm) from openings required by paragraph
(C)(2)(k)(i)(903.2.11.1) of this rule, the basement shall be
equipped throughout with an approved automatic sprinkler
system.
(ii)
903.2.11.2
Rubbish and linen chutes. An automatic sprinkler system shall be
installed at the top of rubbish and linen chutes and in their terminal rooms.
Chutes shall have additional sprinkler heads installed at alternate floors and
at the lowest intake. Where a rubbish chute extends through a building more
than one floor below the lowest intake, the extension shall have sprinklers
installed that are recessed from the drop area of the chute and protected from
freezing in accordance with paragraph (C)(3)(a)(i)(903.3.1.1)
of this rule.
Such sprinklers shall be installed at
alternate floors beginning with the second level below the last intake and
ending with the floor above the discharge. Chute sprinklers shall be accessible
for servicing.
(iii)
903.2.11.3 Buildings 55 feet or more in
height. An automatic sprinkler system shall be installed throughout
buildings that have one or more stories with an occupant load of 30 or more
located 55 feet (16 764 mm) or more above the lowest level of fire department
vehicle access, measured to the finished floor.
Exceptions:
1.
Open parking
structures.
2.
Occupancies in Group F-2.
(iv)
903.2.11.4
Ducts conveying hazardous exhausts. Where required by the
mechanical code as listed in rule
1301:7-7-80
of the Administrative Code, automatic sprinklers shall be provided in
ducts conveying hazardous exhaust, flammable or combustible materials.
Exception:
Ducts where the largest cross-sectional diameter of the
duct is less than 10 inches (254 mm).
(v)
903.2.11.5
Commercial cooking operations. An automatic sprinkler system shall be
installed in commercial kitchen exhaust hood and duct systems where an
automatic sprinkler system is used to comply with paragraph (D)(904) of
this rule.
(vi)
903.2.11.6 Other required suppression
systems. In addition to the requirements of paragraph
(C)(2)( 903.2) of this rule, the provisions indicated in
Table 903.2.11.6 of this rule require the installation of a
fire suppression system for certain buildings and areas.
Table
903.2.11.6
Additional required
fire-extinguishing systems
|
Section
|
Subject
|
|
914.2.1
|
Covered and open mall
buildings
|
|
914.3.1
|
High rise
buildings
|
|
914.4.1
|
Atriums
|
|
914.5.1
|
Underground
structures
|
|
914.6.1
|
Stages
|
|
914.7.1
|
Special amusement
buildings
|
|
914.8.2
|
Airport traffic control
towers
|
|
914.8.3, 914.8.6
|
Aircraft hangars
|
|
914.9
|
Flammable finishes
|
|
914.10
|
Drying rooms
|
|
914.11.1
|
Ambulatory care
facilities
|
|
1029.6.2.3
|
Smoke-protected assembly
seating
|
|
1103.5.1
|
Pyroxylin plastic storage in
existing buildings
|
|
1103.5.2
|
Existing Group I-2
occupancies
|
|
1103.5.3
|
Existing Group I-2 Condition 2
occupancies
|
|
1103.5.4
|
Pyroxylin plastics
|
|
2108.2
|
Dry cleaning
plants
|
|
2108.3
|
Dry cleaning
machines
|
|
2309.3.2.6.2
|
Hydrogen motor fuel-dispensing
area canopies
|
|
2404.2
|
Spray finishing in Group A, E,
I or R
|
|
2404.4
|
Spray booths and spray
rooms
|
|
2405.2
|
Dip-tank rooms in Group A, I or
R
|
|
2405.4.1
|
Dip tanks
|
|
2405.9.4
|
Hardening and tempering
tanks
|
|
2703.10
|
HPM facilities
|
|
2703.10.1.1
|
HPM work station
exhaust
|
|
2703.10.2
|
HPM gas cabinets and exhausted
enclosures
|
|
2703.10.3
|
HPM exit access
corridor
|
|
2703.10.4
|
HPM exhaust ducts
|
|
2703.10.4.1
|
HPM noncombustible
ducts
|
|
2703.10.4.2
|
HPM combustible
ducts
|
|
2807.3
|
Lumber production conveyor
enclosures
|
|
2808.7
|
Recycling facility conveyor
enclosures
|
|
3006.1
|
Class A and B
ovens
|
|
3006.2
|
Class C and D
ovens
|
|
Table 3206.2
|
Storage fire
protection
|
|
3206.4
|
Storage
|
|
3704.5
|
Storage of more than 1,000
cubic feet of loose combustible fibers
|
|
5003.8.4.1
|
Gas rooms
|
|
5003.8.5.3
|
Exhausted
enclosures
|
|
5004.5
|
Indoor storage of hazardous
materials
|
|
5005.1.8
|
Indoor dispensing of hazardous
materials
|
|
5104.4.1
|
Aerosol warehouses
|
|
5106.3.2
|
Aerosol display and
merchandising areas
|
|
5306.2.1
|
Exterior medical gas storage
room
|
|
5306.2.2
|
Interior medical gas storage
room
|
|
5306.2.3
|
Medical gas storage
cabinet
|
|
5606.5.2.1
|
Storage of smokeless
propellant
|
|
5606.5.2.3
|
Storage of small arms
primers
|
|
5704.3.7.5.1
|
Flammable and combustible
liquid storage rooms
|
|
5704.3.8.4
|
Flammable and combustible
liquid storage warehouses
|
|
5705.3.7.3
|
Flammable and combustible
liquid Group H-2 or H-3 areas
|
|
6004.1.2
|
Gas cabinets for highly toxic
and toxic gas
|
|
6004.1.3
|
Exhausted enclosures for highly
toxic and toxic gas
|
|
6004.2.2.6
|
Gas rooms for highly toxic and
toxic gas
|
|
6004.3.3
|
Outdoor storage for highly
toxic and toxic gas
|
|
6504.1.1
|
Pyroxylin plastic storage
cabinets
|
|
6504.1.3
|
Pyroxylin plastic storage
vaults
|
|
6504.2
|
Pyroxylin plastic storage and
manufacturing
|
|
The building code as
listed in rule
1301:7-7-80
of the Administrative Code
|
Sprinkler system
requirements as set forth in section 903.2.11.6 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code
|
For SI: 1 cubic foot = 0.023
m3.
(l)
903.2.12
During construction. Automatic sprinkler systems required during
construction, alteration and demolition operations shall be provided in
accordance with paragraph (M)(3313) of rule
1301:7-7-33
of the Administrative Code.
(3)
903.3
Installation requirements. Automatic sprinkler systems shall be designed
and installed in accordance with paragraphs (C)(3)(a)(903.3.1)
to (C)(3)(h)(903.3.8) of this rule.
(a)
903.3.1
Standards. Sprinkler systems shall be designed and installed in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of
this rule, unless otherwise permitted by paragraphs
(C)(3)(a)(ii)(903.3.1.2) and (C)(3)(a)(iii)(903.3.1.3) of this
rule and other rules of this code, as
applicable.
(i)
903.3.1.1 NFPA 13 sprinkler systems. Where the
provisions of this code require that a building or portion thereof be equipped
throughout with an automatic sprinkler system in accordance with this
paragraph, sprinklers shall be installed throughout in
accordance with NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code except as provided in
paragraph (C)(3)(a)(i)(a)(903.3.1.1.1) and
(C)(3)(a)(i)(b) (9033.1.1.2) of this rule.
(a)
903.3.1.1.1
Exempt locations.
Automatic sprinklers
shall not be required in the following rooms or areas where such rooms or areas
are protected with an approved automatic fire detection system in accordance
with paragraph (G)(2)( 907.2) of this rule
that will respond to visible or invisible particles of combustion. Sprinklers
shall not be omitted from a room merely because it is damp, of
fire-resistance-rated construction or contains electrical equipment.
(i)
A room where the
application of water, or flame and water, constitutes a serious life or fire
hazard.
(ii)
A room or space where sprinklers are considered
undesirable because of the nature of the contents, where approved by the fire
code official pursuant to paragraph (A)(1)( 901.1) of
this rule. At locations or in structures not regulated by the building code as
listed in rule
1301:7-7-80
of the Administrative Code, the exempt location shall be approved by the fire
code official prior to system installation.
(iii)
Generator and
transformer rooms separated from the remainder of the building by walls and
floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not
less than 2 hours.
(iv)
Rooms or areas that are of noncombustible construction
with wholly noncombustible contents.
(v)
Fire service
access elevator machine rooms and machinery spaces.
(vi)
Machine rooms,
machinery spaces, control rooms and control spaces associated with occupant
evacuation elevators designed in accordance with section 3008 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
903.3.1.1.2
Bathrooms.
In Group R occupancies, other
than Group R-4 occupancies, sprinklers shall not be required in bathrooms that
do not exceed 55 square feet (5 m2) in area and are
located within individual dwelling units or sleeping units, provided that walls
and ceilings, including the walls and ceilings behind a shower enclosure or
tub, are of non-combustible or limited-combustible materials with a 15-minute
thermal barrier rating.
(ii)
903.3.1.2
NFPA 13R sprinkler systems. Automatic sprinkler systems in Group
I-1, I-4 and R occupancies up to and including four stories in
height in buildings not exceeding 60 feet (18 288 mm) in height above grade
plane shall be permitted to be installed throughout in accordance with NFPA 13R
as listed in rule
1301:7-7-80
of the Administrative Code.
The number of stories of Group R
occupancies constructed in accordance with sections 510.2 and 510.4 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code shall be measured from the horizontal
assembly creating separate buildings.
(a)
903.3.1.2.1
Balconies and decks.
Sprinkler protection
shall be provided for exterior balconies, decks and ground floor patios of
dwelling units and sleeping units where the building is of Type V construction,
provided there is a roof or deck above. Sidewall sprinklers that are used to
protect such areas shall be permitted to be located such that their deflectors
are within 1 inch (25 mm) to 6 inches (152 mm) below the structural members and
a maximum distance of 14 inches (356 mm) below the deck of the exterior
balconies and decks that are constructed of open wood joist
construction.
(b)
903.3.1.2.2 Open-ended corridors.
Sprinkler protection shall be provided in open-ended
corridors and associated exterior stairways and ramps as specified in
paragraph (AA)(6)( 1027.6), Exception 3 of rule
1301:7-7-10 of
the Administrative Code.
(iii)
903.3.1.3
NFPA 13D sprinkler systems. Automatic sprinkler systems
installed in buildings of Groups I-1, R-3, Group R-4 Condition 1 and
townhouses shall be permitted to be installed throughout in accordance
with NFPA 13D as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
903.3.2
Quick-response and residential sprinklers.
Where automatic sprinkler systems are required by this code,
quick-response or residential automatic sprinklers shall be installed in all of
the following areas in accordance with paragraph
(C)(3)(a)(903.3.1) of this rule and their listings:
(i)
Throughout all
spaces within a smoke compartment containing care recipient sleeping units in
Group I-2 in accordance with the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(ii)
Throughout all
spaces within a smoke compartment containing treatment rooms in ambulatory care
facilities.
(iii)
Dwelling units and sleeping units in Group I-1 and R
occupancies.
(iv)
Light-hazard occupancies as defined in NFPA 13
as listed in rule
1301:7-7-80
of the Administrative Code.
(c)
903.3.3
Obstructed locations.
Automatic sprinklers
shall be installed with due regard to obstructions that will delay activation
or obstruct the water distribution pattern. Automatic sprinklers shall be
installed in or under covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914
mm) clearance shall be maintained between automatic sprinklers and the top of
piles of combustible fibers.
Exception:
Kitchen equipment under exhaust hoods protected with a
fire-extinguishing system in accordance with paragraph
(D)(904) of this rule.
(d)
903.3.4
Actuation.
Automatic sprinkler systems
shall be automatically actuated unless specifically provided for in this
code.
(e)
903.3.5 Water supplies.
Water supplies for automatic sprinkler systems shall comply
with this paragraph and the standards referenced in
paragraph (C)(3)(a)(903.3.1) of this rule.
The potable water supply shall be protected against backflow in accordance with
the requirements of this paragraph and the plumbing
code as listed in rule
1301:7-7-80
of the Administrative Code. For connections to public waterworks
systems, the water supply test used for design of fire protection systems shall
be adjusted to account for seasonal and daily pressure fluctuations based on
information from the water supply authority and as approved by the fire code
official.
(i)
903.3.5.1 Domestic services. Where the domestic
service provides the water supply for the automatic sprinkler system, the
supply shall be in accordance with this
paragraph.
(ii)
903.3.5.2
Residential combination services. A single combination water supply
shall be allowed provided that the domestic demand is added to the sprinkler
demand as required by NFPA 13R as listed in rule
1301:7-7-80
of the Administrative Code.
(f)
903.3.6
Hose threads.
Fire hose threads and
fittings used in connection with automatic sprinkler systems shall be as
prescribed by the fire code official.
(g)
903.3.7
Fire department connections.
Fire
department connections for automatic sprinkler systems shall be installed in
accordance with paragraph (L)(912) of this
rule.
(i)
903.3.7.1 Locking fire department
connection ("FDC") caps.
Where required by the fire
code official and the responding fire department carries appropriate key
wrenches for removal, locking "FDC" caps on fire department connections for
water-based fire protection systems shall be provided.
(h)
903.3.8 Limited area sprinkler systems.
Limited area sprinkler systems shall be in accordance with the standards listed
in paragraph (C)(3)(a)(903.3.1) of this rule
except as provided in paragraphs (C)(3)(h)(i)(903.3.8.1)
to (C)(3)(h)(v)(903.3.8.5) of this
rule.
(i)
903.3.8.1 Number of sprinklers. Limited
area sprinkler systems shall not exceed nineteen sprinklers in
any single fire area.
(ii)
903.3.8.2 Occupancy hazard classification.
Only areas classified by NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code as Light Hazard or Ordinary Hazard Group 1
shall be permitted to be protected by limited area sprinkler
systems.
(iii)
903.3.8.3 Piping arrangement. Where a
limited area sprinkler system is installed in a building with an automatic wet
standpipe system, sprinklers shall be supplied by the standpipe system. Where a
limited area sprinkler system is installed in a building without an automatic
wet standpipe system, water shall be permitted to be supplied by the plumbing
system provided that the plumbing system is capable of simultaneously supplying
domestic and sprinkler demands.
(iv)
903.3.8.4
Supervision. Control valves shall not be installed between the water
supply and sprinklers unless the valves are of an approved indicating type that
are supervised or secured in the open position.
(v)
903.3.8.5
Calculations. Hydraulic calculations in accordance with NFPA 13
as listed in rule
1301:7-7-80
of the Administrative Code shall be provided to demonstrate that the
available water flow and pressure are adequate to supply all sprinklers
installed in any single fire area with discharge densities corresponding to the
hazard classification.
(4)
903.4
Sprinkler system supervision and alarms. Valves controlling the water
supply for automatic sprinkler systems, pumps, tanks, water levels and
temperatures, critical air pressures and waterflow switches on all sprinkler
systems shall be electrically supervised by a listed fire alarm control
unit.
Exceptions:
1.
Limited area
systems in accordance with paragraph (C)(3)(h)(903.3.8)
of this rule.
2.
Automatic
sprinkler systems installed in accordance with NFPA 13R as listed in
rule
1301:7-7-80
of the Administrative Code where a common supply main is used to
supply both domestic water and the automatic sprinkler system, and a separate
shutoff valve for the automatic sprinkler system is not
provided.
3.
Jockey pump control valves that are sealed or locked in
the open position.
4.
Control valves to commercial kitchen hoods, paint spray
booths or dip tanks that are sealed or locked in the open
position.
5.
Valves controlling the fuel supply to fire pump engines
that are sealed or locked in the open position.
6.
Trim valves to
pressure switches in dry, pre-action and deluge sprinkler systems that are
sealed or locked in the open position.
(a)
903.4.1
Monitoring.
Alarm, supervisory and trouble
signals shall be distinctly different and shall be automatically transmitted to
an approved supervising station or, where approved by the fire code official
pursuant to paragraph (A)(1)( 901.1) of this
rule, shall sound an audible signal at a constantly attended location.
At locations or in structures not regulated by the building code as
listed in rule
1301:7-7-80
of the Administrative Code, the constantly attended location shall be approved
by the fire code official prior to system installation.
Exceptions:
1.
Underground key or
hub valves in roadway boxes provided by the municipality or public utility are
not required to be monitored.
2.
Backflow
prevention device test valves located in limited area sprinkler system supply
piping shall be locked in the open position. In occupancies required to be
equipped with a fire alarm system, the backflow preventer valves shall be
electrically supervised by a tamper switch installed in accordance with NFPA 72
as listed in rule
1301:7-7-80
of the Administrative Code and separately
annunciated.
(b)
903.4.2 Alarms.
An approved audible device, located on the exterior of
the building in an approved location, shall be connected to each automatic
sprinkler system. Such sprinkler waterflow alarm devices shall be activated by
water flow equivalent to the flow of a single sprinkler of the smallest orifice
size installed in the system. Where a fire alarm system is installed, actuation
of the automatic sprinkler system shall actuate the building fire alarm
system.
Exception:
Waterflow alarms are not required for limited area sprinkler
systems installed in accordance with paragraph (C)(3)(e)(i)(a)(903.3.5.1.1) of
this rule.
(c)
903.4.3
Floor control valves.
Approved supervised
indicating control valves shall be provided at the point of connection to the
riser on each floor in high-rise buildings.
(5)
903.5
Testing and maintenance.
Sprinkler systems
shall be tested and maintained in accordance with paragraph
(A)(901) of this rule.
(6)
903.6 Where
required in existing buildings and structures.
An automatic sprinkler system shall be provided in
existing buildings and structures where required in rule
1301:7-7-11
of the Administrative Code.
(D)
Section 904
Alternative automatic fire-extinguishing systems
(1)
904.1
General.
Automatic fire-extinguishing
systems, other than automatic sprinkler systems, shall be designed, installed,
inspected, tested and maintained in accordance with the provisions of this
paragraph and the applicable referenced standards.
(a)
904.1.1
Certification of service personnel for fire-extinguishing equipment.
Service personnel providing or conducting maintenance on automatic
fire-extinguishing systems, other than automatic sprinkler systems, shall
possess a valid certificate issued by an approved governmental agency, or other
approved organization for the type of system and work
performed.
(2)
904.2 Where permitted.
Automatic fire-extinguishing systems installed as an
alternative to the required automatic sprinkler systems of
paragraph (C)(903) of this rule shall be
approved by the fire code official pursuant to paragraph
(A)(1)( 901.1) of this rule. At locations or in structures not
regulated by the building code as listed in rule
1301:7-7-80
of the Administrative Code, the alternative automatic fire-extinguishing system
shall be approved by the fire code official prior to system
installation.
(a)
904.2.1 Restriction on using automatic sprinkler system
exceptions or reductions.
Automatic
fire-extinguishing systems shall not be considered alternatives for the
purposes of exceptions or reductions allowed for automatic sprinkler system or
by other requirements of this code.
(b)
904.2.2
Commercial hood and duct systems.
Each
required commercial kitchen exhaust hood and duct system required by
paragraph (I)(609) of rule
1301:7-7-06
of the Administrative Code to have a Type I hood shall be protected
with an approved automatic fire-extinguishing system installed in accordance
with this code.
(3)
904.3 Installation.
Automatic fire-extinguishing systems shall be installed
in accordance with this paragraph.
(a)
904.3.1
Electrical wiring.
Electrical wiring shall
be in accordance with NFPA 70 as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
904.3.2
Actuation.
Automatic fire-extinguishing
systems shall be automatically actuated and provided with a manual means of
actuation in accordance with paragraph (D)(12)(a)(904.12.1)
of this rule.
(c)
904.3.3
System interlocking.
Automatic equipment
interlocks with fuel shutoffs, ventilation controls, door closers, window
shutters, conveyor openings, smoke and heat vents and other features necessary
for proper operation of the fire-extinguishing system shall be provided as
required by the design and installation standard utilized for the
hazard.
(d)
904.3.4 Alarms and warning signs.
Where alarms are required to indicate the operation of
automatic fire-extinguishing systems, distinctive audible, visible alarms and
warning signs shall be provided to warn of pending agent discharge. Where
exposure to automatic-extinguishing agents poses a hazard to persons and a
delay is required to ensure the evacuation of occupants before agent discharge,
a separate warning signal shall be provided to alert occupants once agent
discharge has begun. Audible signals shall be in accordance with
paragraph
(G)(5)(b)(907.5.2) of this
rule.
(e)
904.3.5 Monitoring.
Where a building fire alarm system is installed, automatic
fire-extinguishing systems shall be monitored by the building fire alarm system
in accordance with NFPA 72 as listed in rule
1301:7-7-80
of the Administrative Code.
(4)
904.4
Inspection and testing.
Automatic
fire-extinguishing systems shall be inspected and tested in accordance with the
provisions of this paragraph prior to acceptance.
(a)
904.4.1
Inspection. Prior to conducting final acceptance tests, the following
items shall be inspected:
(i)
Hazard specification for consistency with design
hazard.
(ii)
Type, location and spacing of automatic- and
manual-initiating devices.
(iii)
Size, placement
and position of nozzles or discharge orifices.
(iv)
Location and
identification of audible and visible alarm devices.
(v)
Identification of
devices with proper designations.
(vi)
Operating
instructions.
(b)
904.4.2 Alarm testing.
Notification appliances, connections to fire alarm
systems and connections to approved supervising stations shall be tested in
accordance with this paragraph and paragraph
(G)(907) of this rule to verify proper operation.
(i)
904.4.2.1
Audible and visible signals. The audibility and visibility of
notification appliances signaling agent discharge or system operation, where
required, shall be verified.
(c)
904.4.3
Monitor testing.
Connections to protected
premises and supervising station fire alarm systems shall be tested to verify
proper identification and retransmission of alarms from automatic
fire-extinguishing systems.
(5)
904.5
Wet-chemical systems.
Wet-chemical
extinguishing systems shall be installed, maintained, periodically inspected
and tested in accordance with NFPA 17A as listed in rule
1301:7-7-80
of the Administrative Code and their listing. Records of inspections
and testing shall be maintained.
(a)
904.5.1 System test.
Systems shall be inspected and tested for proper
operation at six-month intervals. Tests shall include a check of the detection
system, alarms and releasing devices, including manual stations and other
associated equipment. Extinguishing system units shall be weighed and the
required amount of agent verified. Stored pressure-type units shall be checked
for the required pressure. The cartridge of cartridge-operated units shall be
weighed and replaced at intervals indicated by the
manufacturer.
(b)
904.5.2 Fusible link maintenance.
Fixed temperature-sensing elements shall be maintained
in accordance with NFPA 17A as listed in rule
1301:7-7-80
of the Administrative Code to ensure proper operation of the
system.
(6)
904.6 Dry-chemical systems.
Dry-chemical extinguishing systems shall be installed,
maintained, periodically inspected and tested in accordance with NFPA 17
as listed in rule
1301:7-7-80
of the Administrative Code and their listing. Records of inspections
and testing shall be maintained.
(a)
904.6.1 System test.
Systems shall be inspected and tested for proper
operation at six-month intervals. Tests shall include a check of the detection
system, alarms and releasing devices, including manual stations and other
associated equipment. Extinguishing system units shall be weighed, and the
required amount of agent verified. Stored pressure-type units shall be checked
for the required pressure. The cartridge of cartridge-operated units shall be
weighed and replaced at intervals indicated by the
manufacturer.
(b)
904.6.2 Fusible link maintenance.
Fixed temperature-sensing elements shall be maintained
to ensure proper operation of the system.
(7)
904.7 Foam
systems.
Foam-extinguishing systems shall
be installed, maintained, periodically inspected and tested in accordance with
NFPA 11 and NFPA 16 as listed in rule
1301:7-7-80
of the Administrative Code and their listing. Records of inspections
and testing shall be maintained.
(a)
904.7.1 System test. Foam-extinguishing
systems shall be inspected and tested at intervals in accordance with NFPA 25
as listed in rule
1301:7-7-80
of the Administrative Code.
(8)
904.8
Carbon dioxide systems.
Carbon dioxide
extinguishing systems shall be installed, maintained, periodically inspected
and tested in accordance with NFPA 12 as listed in rule
1301:7-7-80
of the Administrative Code and their listing. Records of inspections
and testing shall be maintained.
(a)
904.8.1 System test.
Systems shall be inspected and tested for proper
operation at 12-month intervals.
(b)
904.8.2
High-pressure cylinders.
High-pressure
cylinders shall be weighed and the date of the last hydrostatic test shall be
verified at six-month intervals. Where a container shows a loss in original
content of more than 10 per cent, the cylinder shall be
refilled or replaced.
(c)
904.8.3 Low-pressure containers.
The liquid-level gauges of low-pressure containers
shall be observed at one-week intervals. Where a container shows a content loss
of more than 10 per cent, the container shall be refilled to
maintain the minimum gas requirements.
(d)
904.8.4
System hoses.
System hoses shall be
examined at 12-month intervals for damage. Damaged hoses shall be replaced or
tested. At five-year intervals, all hoses shall be tested.
(i)
904.8.4.1
Test procedure. Hoses shall be tested at not less than 2,500 pounds per
square inch (psi) (17 238 kPa) for high-pressure systems and at not less than
900 psi (6206 kPa) for low-pressure systems.
(e)
904.8.5
Auxiliary equipment.
Auxiliary and
supplementary components, such as switches, door and window releases,
interconnected valves, damper releases and supplementary alarms, shall be
manually operated at 12-month intervals to ensure that such components are in
proper operating condition.
(9)
904.9 Halon
systems.
Halogenated extinguishing systems
shall be installed, maintained, periodically inspected and tested in accordance
with NFPA 12A as listed in rule
1301:7-7-80
of the Administrative Code and their listing. Records of inspections
and testing shall be maintained.
(a)
904.9.1 System test.
Systems shall be inspected and tested for proper
operation at 12-month intervals.
(b)
904.9.2
Containers.
The extinguishing agent
quantity and pressure of containers shall be checked at six-month intervals.
Where a container shows a loss of original weight of more than 5 per
cent or a loss in original pressure (adjusted for temperature) of more
than 10 per cent, the container shall be refilled or replaced.
The weight and pressure of the container shall be recorded on a tag attached to
the container.
(c)
904.9.3 System hoses.
System hoses shall be examined at 12-month intervals for
damage. Damaged hoses shall be replaced or tested. At five-year intervals, all
hoses shall be tested.
(i)
904.9.3.1 Test procedure. For Halon 1301
systems, hoses shall be tested at not less than 1,500 psi (10 343 kPa) for 600
psi (4137 kPa) charging pressure systems and not less than 900 psi (6206 kPa)
for 360 psi (2482 kPa) charging pressure systems. For Halon 1211 hand-hose line
systems, hoses shall be tested at 2,500 psi (17 238 kPa) for high-pressure
systems and 900 psi (6206 kPa) for low-pressure
systems.
(d)
904.9.4 Auxiliary equipment.
Auxiliary and supplementary components, such as
switches, door and window releases, interconnected valves, damper releases and
supplementary alarms, shall be manually operated at 12-month intervals to
ensure such components are in proper operating
condition.
(10)
904.10 Clean-agent systems.
Clean-agent fire-extinguishing systems shall be
installed, maintained, periodically inspected and tested in accordance with
NFPA 2001 as listed in rule
1301:7-7-80
of the Administrative Code and their listing. Records of inspections
and testing shall be maintained.
(a)
904.10.1 System test.
Systems shall be inspected and tested for proper
operation at 12-month intervals.
(b)
904.10.2
Containers.
The extinguishing agent
quantity and pressure of the containers shall be checked at six-month
intervals. Where a container shows a loss in original weight of more than 5
per cent or a loss in original pressure, adjusted for
temperature, of more than 10 per cent, the container shall be
refilled or replaced. The weight and pressure of the container shall be
recorded on a tag attached to the container.
(c)
904.10.3
System hoses.
System hoses shall be
examined at 12-month intervals for damage. Damaged hoses shall be replaced or
tested. All hoses shall be tested at five-year
intervals.
(11)
904.11 Automatic water mist systems.
Automatic water mist systems shall be permitted in
applications that are consistent with applicable listing or approvals and shall
comply with paragraphs (D)(11)(a)(904.11.1)
to (D)(11)(c)( 904.113) of this rule.
(a)
904.11.1
Design and installation requirements.
Automatic water mist systems shall be designed and installed
in accordance with paragraphs (C)(11)(a)(i)(904.11.1.1)
to (D)(11)(a)(iv)(904.11.1.4) of this
rule.
(i)
904.11.1.1 General. Automatic water mist
systems shall be designed and installed in accordance with NFPA 750 as
listed in rule
1301:7-7-80
of the Administrative Code and the manufacturer's
instructions.
(ii)
904.11.1.2 Actuation. Automatic water mist
systems shall be automatically actuated.
(iii)
904.11.1.3 Water supply protection. Connections
to a potable water supply shall be protected against backflow in accordance
with the plumbing code as listed in rule
1301:7-7-80
of the Administrative Code.
(iv)
904.11.1.4
Secondary water supply. Where a secondary water supply is required for
an automatic sprinkler system, an automatic water mist system shall be provided
with an approved secondary water supply.
(b)
904.11.2
Water mist system supervision and alarms.
Supervision and alarms shall be provided as required for
automatic sprinkler systems in accordance with paragraph
(C)(4)( 903.4) of this rule.
(i)
904.11.2.1
Monitoring. Monitoring shall be provided as required for automatic
sprinkler systems in accordance with paragraph
(C)(4)(a)(903.4.1) of this rule.
(ii)
904.11.2.2
Alarms. Alarms shall be provided as required for automatic sprinkler
systems in accordance with paragraph (C)(4)(b)(903.4.2)
of this rule.
(iii)
904.11.2.3 Floor control valves. Floor control
valves shall be provided as required for automatic sprinkler systems in
accordance with paragraph (C)(4)(c)(903.4.3) of this
rule.
(c)
904.11.3 Testing and maintenance.
Automatic water mist systems shall be tested and
maintained in accordance with paragraph (A)(6)( 901.6)
of this rule.
(12)
904.12
Commercial cooking systems.
The automatic
fire-extinguishing system for commercial cooking systems shall be of a type
recognized for protection of commercial cooking equipment and exhaust systems
of the type and arrangement protected. Pre-engineered automatic dry- and
wet-chemical extinguishing systems shall be tested in accordance with UL 300
as listed in rule
1301:7-7-80
of the Administrative Code and listed and labeled for the intended
application. Other types of automatic fire-extinguishing systems shall be
listed and labeled for specific use as protection for commercial cooking
operations. The system shall be installed in accordance with this code, its
listing and the manufacturer's installation instructions. Automatic
fire-extinguishing systems of the following types shall be installed in
accordance with the referenced standard indicated, as follows:
1.
Carbon dioxide
extinguishing systems, NFPA 12 as listed in rule
1301:7-7-80
of the Administrative Code.
2.
Automatic
sprinkler systems, NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code.
3.
Foam-water
sprinkler system or foam-water spray systems, NFPA 16 as listed in rule
1301:7-7-80
of the Administrative Code.
4.
Dry-chemical
extinguishing systems, NFPA 17 as listed in rule
1301:7-7-80
of the Administrative Code.
5.
Wet-chemical
extinguishing systems, NFPA 17A as listed in rule
1301:7-7-80
of the Administrative Code.
Exception:
Factory-built commercial cooking recirculating systems
that are tested in accordance with UL 710B as listed in rule
1301:7-7-80
of the Administrative Code and listed, labeled and installed in
accordance with section 304.1 of the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
(a)
904.12.1
Manual system operation.
A manual
actuation device shall be located at or near a means of egress from the cooking
area not less than 10 feet (3048 mm) and not more than 20 feet (6096 mm) from
the kitchen exhaust system. The manual actuation device shall be installed not
more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor
and shall clearly identify the hazard protected. The manual actuation shall
require a maximum force of 40 pounds (178 N) and a maximum movement of 14
inches (356 mm) to actuate the fire suppression system.
Exception:
Automatic sprinkler systems shall not be required to be
equipped with manual actuation means.
(b)
904.12.2
System interconnection.
The actuation of
the fire extinguishing system shall automatically shut down the fuel or
electrical power supply to the cooking equipment. The fuel and electrical
supply reset shall be manual.
(c)
904.12.3
Carbon dioxide systems.
When carbon
dioxide systems are used, there shall be a nozzle at the top of the ventilating
duct. Additional nozzles that are symmetrically arranged to give uniform
distribution shall be installed within vertical ducts exceeding 20 feet (6096
mm) and horizontal ducts exceeding 50 feet (15 240 mm). Dampers shall be
installed at either the top or the bottom of the duct and shall be arranged to
operate automatically upon activation of the fire-extinguishing system. When
the damper is installed at the top of the duct, the top nozzle shall be
immediately below the damper. Automatic carbon dioxide fire-extinguishing
systems shall be sufficiently sized to protect all hazards venting through a
common duct simultaneously.
(i)
904.12.3.1 Ventilation system.
Commercial-type cooking equipment protected by an automatic carbon
dioxide extinguishing system shall be arranged to shut off the ventilation
system upon activation.
(d)
904.12.4
Special provisions for automatic sprinkler systems.
Automatic sprinkler systems protecting commercial-type
cooking equipment shall be supplied from a separate, readily accessible,
indicating-type control valve that is identified.
(i)
904.12.4.1
Listed sprinklers. Sprinklers used for the protection of fryers shall be
tested in accordance with UL 199E as listed in rule
1301:7-7-80
of the Administrative Code, listed for that application and installed
in accordance with their listing.
(e)
904.12.5
Portable fire extinguishers for commercial cooking equipment.
Portable fire extinguishers shall be provided within a
30-foot (9144 mm) distance of travel from commercial-type cooking equipment.
Cooking equipment involving solid fuels or vegetable or animal oils and fats
shall be protected by a Class K rated portable extinguisher in accordance with
paragraphs (D)(12)(e)(i)(904.12.5.1) or
(D)(12)(e)(ii)(904.12.5.2) of this rule, as applicable.
(i)
904.12.5.1
Portable fire extinguishers for solid fuel cooking appliances. Solid
fuel cooking appliances, whether or not under a hood, with fireboxes 5 cubic
feet ( 0.14 m3) or less in volume shall have a
minimum 2.5 -gallon (9 L) or two 1.5 -gallon (6 L) Class K wet-chemical
portable fire extinguishers located in accordance with
paragraph (D)(12)(e)(904.12.5) of this
rule.
(ii)
904.12.5.2 Class K portable fire extinguishers
for deep fat fryers. When hazard areas include deep fat fryers, listed
Class K portable fire extinguishers shall be provided as follows:
(a)
For up to four
fryers having a maximum cooking medium capacity of 80 pounds ( 36.3 kg) each:
One Class K portable fire extinguisher of a minimum 1.5 gallon (6 L)
capacity.
(b)
For every additional group of four fryers having a
maximum cooking medium capacity of 80 pounds ( 36.3 kg) each: one additional
Class K portable fire extinguisher of a minimum 1.5 gallon (6 L) capacity shall
be provided.
(c)
For individual fryers exceeding 6 square feet ( 0.55
m2) in surface area: Class K portable fire
extinguishers shall be installed in accordance with the extinguisher
manufacturer's recommendations.
(f)
904.12.6
Operations and maintenance. Automatic fire-extinguishing systems
protecting commercial cooking systems shall be maintained in accordance with
paragraphs (D)(12)(f)(i)(904.12.6.1) to
(D)(12)(f)(iii)(904.12.6.3) of this rule.
(i)
904.12.6.1
Existing automatic fire extinguishing systems. Where changes in the
cooking media, positioning of cooking equipment or replacement of cooking
equipment occur in existing commercial cooking systems, the automatic
fire-extinguishing system shall be required to comply with the applicable
provisions of paragraphs (D)(12)( 904.12) to
(D)(12)(d)(904.12.4) of this rule.
(ii)
904.12.6.2
Extinguishing system service. Automatic fire-extinguishing systems shall
be serviced at least every 6 months and after activation of the system.
Inspection shall be by qualified individuals, and a certificate of inspection
shall be forwarded to the fire code official upon completion.
(iii)
904.12.6.3 Fusible link and sprinkler head
replacement. Fusible links and automatic sprinkler heads shall be
replaced at least annually, and other protection devices shall be serviced or
replaced in accordance with the manufacturer's instructions.
Exception:
Frangible bulbs are not required to be replaced
annually.
(13)
904.13
Domestic cooking systems in Group I-2 Condition I. In Group I-2
Condition 1 occupancies where cooking facilities are installed in accordance
with Section 407.2.6 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, the domestic cooking hood provided over
the cooktop or range shall be equipped with an automatic fire-extinguishing
system of a type recognized for protection of domestic cooking equipment.
Pre-engineered automatic extinguishing systems shall be tested in accordance
with UL 300A as listed in rule
1301:7-7-80
of the Administrative Code and listed and labeled for the intended
application. The system shall be installed in accordance with this code, its
listing and the manufacturer's instructions.
(a)
904.13.1
Manual system operation and interconnection.
Manual actuation and system interconnection for the
hood suppression system shall be in accordance with paragraphs
(D)(12)(a)(904.12.1) and (D)(12)(b)(904.12.2) of this rule,
respectively.
(b)
904.13.2 Portable fire extinguishers for domestic cooking
equipment in Group I-2 Condition 1.
A
portable fire extinguisher complying with paragraph (F)(906)
of this rule shall be installed within a 30-foot (9144 mm)
distance of travel from domestic cooking
appliances.
(F)
Section 906
Portable fire extinguishers
(1)
906.1 Where required. Portable fire
extinguishers shall be installed in all of the following locations:
(a)
In new and
existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
Exceptions:
1.
In Group R-2
occupancies, portable fire extinguishers shall be required only in locations
specified in paragraphs (b) through (f) of this rule
where each dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C.
2.
In Group E
occupancies, portable fire extinguishers shall be required only in locations
specified in paragraphs (b) through (f) of this rule where each classroom is
provided with a portable fire extinguisher having a minimum rating of
2-A:20-B:C.
(b)
Within 30 feet
(9144 mm) of commercial cooking appliances and domestic cooking
appliances in Group I-2 nursing homes.
(c)
In areas where
flammable or combustible liquids are stored, used or dispensed.
(d)
On each floor of
structures under construction, except Group R-3 occupancies, in accordance with
paragraph (O)(1)( 3315.1) of rule
1301:7-7-33
of the Administrative Code.
(e)
Where required by
the paragraphs indicated in Table 906.1of this
rule.
(f)
Special-hazard areas, including but not limited to
laboratories, computer rooms and generator rooms, where required by the fire
code official and in accordance with the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
Table 906.1
Additional required portable fire
extinguishers
|
Paragraph
|
Subject
|
|
Paragraph
(C)(5)(
303.5) of rule
1301:7-7-03
of the Administrative Code
|
Asphalt kettles
|
|
Paragraph
(G)(5)(
307.5) of rule
1301:7-7-03
of the Administrative Code
|
Open burning
|
|
Paragraph
(H)(1)(c)(308.1.3) of rule
1301:7-7-03
of the Administrative Code
|
Open
flames-torches
|
|
Paragraph
(I)(4)(
309.4) of rule
1301:7-7-03
of the Administrative Code
|
Powered industrial
trucks
|
|
Paragraph
(E)(2)(
2005.2) of rule
1301:7-7-20
of the Administrative Code
|
Aircraft towing
vehicles
|
|
Paragraph
(E)(3)( 2005.3) of rule
1301:7-7-20
of the Administrative Code
|
Aircraft welding
apparatus
|
|
Paragraph
(E)(4)(
2005.4) of rule
1301:7-7-20
of the Administrative Code
|
Aircraft fuel-servicing tank
vehicles
|
|
Paragraph
(E)(5)(
2005.5) of rule
1301:7-7-20
of the Administrative Code
|
Aircraft hydrant fuel-servicing
vehicles
|
|
Paragraph
(E)(6)(
2005.6) of rule
1301:7-7-20
of the Administrative Code
|
Aircraft fuel-dispensing
stations
|
|
Paragraph
(G)(7)(
2007.7) of rule
1301:7-7-20
of the Administrative Code
|
Heliports and
helistops
|
|
Paragraph
(H)(4)(
2108.4) of rule
1301:7-7-21 of the
Administrative Code
|
Dry cleaning
plants
|
|
Paragraph
(E)(5)(
2305.5) of rule
1301:7-7-23
of the Administrative Code
|
Motor fuel-dispensing
facilities
|
|
Paragraph
(J)(6)(d)(2310.6.4) of rule
1301:7-7-23
of the Administrative Code
|
Marine motor fuel-dispensing
facilities
|
|
Paragraph
(K)(6)(
2311.6) of rule
1301:7-7-23
of the Administrative Code
|
Repair garages
|
|
Paragraph
(D)(4)(a)(2404.4.1) of rule
1301:7-7-24 of
the Administrative Code
|
Spray-finishing
operations
|
|
Paragraph
(E)(4)(b)(2405.4.2) of rule
1301:7-7-24 of
the Administrative Code
|
Dip-tank
operations
|
|
Paragraph
(F)(4)(b)(2406.4.2) of rule
1301:7-7-24 of
the Administrative Code
|
Powder-coating
areas
|
|
Paragraph
(D)(2)(
2804.2) of rule
1301:7-7-28
of the Administrative Code
|
Lumberyards/woodworking
facilities
|
|
Paragraph
(H)(8)(
2808.8) of rule
1301:7-7-28
of the Administrative Code
|
Recycling
facilities
|
|
Paragraph
(I)(5)(
2809.5) of rule
1301:7-7-28
of the Administrative Code
|
Exterior lumber
storage
|
|
Paragraph
(C)(5)(
2903.5) of rule
1301:7-7-29
of the Administrative Code
|
Organic-coating
areas
|
|
Paragraph
(F)(3)(
3006.3) of rule
1301:7-7-30 of
the Administrative Code
|
Industrial ovens
|
|
Paragraph
(D)(12)(
3104.12) of rule
1301:7-7-31
of the Administrative Code
|
Tents and membrane
structures
|
|
Paragraph
(F)(10)(
3206.10) of rule
1301:7-7-32
of the Administrative Code
|
High-piled storage
|
|
Paragraph
(O)(1)(
3315.1) of rule
1301:7-7-33
of the Administrative Code
|
Buildings under construction or
demolition
|
|
Paragraph
(Q)(3)(
3317.3) of rule
1301:7-7-33
of the Administrative Code
|
Roofing operations
|
|
Paragraph
(H)(2)(
3408.2) of rule
1301:7-7-34
of the Administrative Code
|
Tire
rebuilding/storage
|
|
Paragraph
(D)(2)(f)(3504.2.6) of rule
1301:7-7-35
of the Administrative Code
|
Welding and other hot
work
|
|
Paragraph
(D)(4)(
3604.4) of rule
1301:7-7-36 of the
Administrative Code
|
Marinas
|
|
Paragraph
(C)(6)(
3703.6) of rule
1301:7-7-37 of
the Administrative Code
|
Combustible fibers
|
|
Paragraph
(C)(2)(a)(5703.2.1) of rule
1301:7-7-57
of the Administrative Code
|
Flammable and combustible
liquids, general
|
|
Paragraph
(D)(3)(c)(i)(5704.3.3.1) of rule
1301:7-7-57
of the Administrative Code
|
Indoor storage of flammable and
combustible liquids
|
|
Paragraph
(D)(3)(g)(v)(ii)(5704.3.7.5.2) of rule
1301:7-7-57
of the Administrative Code
|
Liquid storage rooms for
flammable and combustible liquids
|
|
Paragraph
(E)(4)(i)(5705.4.9) of rule
1301:7-7-57
of the Administrative Code
|
Solvent distillation
units
|
|
Paragraph
(F)(2)(g)(5706.2.7) of rule
1301:7-7-57
of the Administrative Code
|
Farms and construction
sites-flammable and combustible liquids storage
|
|
Paragraph
(F)(4)(j)(i)(5706.4.10.1) of rule
1301:7-7-57
of the Administrative Code
|
Bulk plants and terminals for
flammable and combustible liquids
|
|
Paragraph
(F)(5)(d)(v)(5706.5.4.5) of rule
1301:7-7-57
of the Administrative Code
|
Commercial, industrial,
governmental or manufacturing establishments-fuel dispensing
|
|
Paragraph
(F)(6)(d)(5706.6.4) of rule
1301:7-7-57
of the Administrative Code
|
Tank vehicles for flammable and
combustible liquids
|
|
Paragraph
(F)(5)(g)(5906.5.7) of rule
1301:7-7-59 of
the Administrative Code
|
Flammable solids
|
|
Paragraph
(H)(2)(
6108.2) of rule
1301:7-7-61
of the Administrative Code
|
LP-gas
|
(2)
906.2
General requirements.
Portable fire
extinguishers shall be selected, installed and maintained in accordance with
this paragraph and NFPA 10 as listed in rule
1301:7-7-80
of the Administrative Code.
Exceptions:
1.
The distance of
travel to reach an extinguisher shall not apply to the spectator seating
portions of Group A-5 occupancies.
2.
Thirty-day
inspections shall not be required and maintenance shall be allowed to be once
every 3 years for dry-chemical or halogenated agent portable fire extinguishers
that are supervised by a listed and approved electronic monitoring device,
provided that all of the following conditions are met:
2.1
Electronic
monitoring shall confirm that extinguishers are properly positioned, properly
charged and unobstructed.
2.2
Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.
2.3
The extinguishers
shall be installed inside of a building or cabinet in a noncorrosive
environment.
2.4
Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance is
performed.
2.5
A written log of required hydrostatic test dates for
extinguishers shall be maintained by the owner to verify that hydrostatic tests
are conducted at the frequency required by NFPA 10 as listed in rule
1301:7-7-80
of the Administrative Code.
3.
In Group I-3,
portable fire extinguishers shall be permitted to be located at staff
locations.
(a)
906.2.1 Certification of service personnel for
portable fire extinguishers. Service personnel providing or conducting
maintenance on portable fire extinguishers shall possess a valid certificate
issued by an approved governmental agency, or other approved organization for
the type of work performed.
(3)
906.3 Size
and distribution.
The size and
distribution of portable fire extinguishers shall be in accordance with
paragraphs (F)(3)(a)(906.3.1) to
(F)(3)(d)(906.3.4) of this rule.
(a)
906.3.1
Class A fire hazards. Portable fire extinguishers for occupancies that
involve primarily Class A fire hazards, the minimum sizes and distribution
shall comply with Table 906.3(1)of this rule.
Table 906.3
(1)
Fire extinguishers for Class A
fire hazards
|
Light (low) hazard
occupancy
|
Ordinary (moderate)
hazard occupancy
|
Extra (high) hazard
occupancy
|
|
Minimum rated single
extinguisher
|
2-Ac
|
2-A
|
4-Aa
|
|
Maximum floor area per unit of
A
|
3,000 square feet
|
1,500 square feet
|
1,000 square feet
|
|
Maximum floor area for
extinguisherb
|
11,250 square feet
|
11,250 square feet
|
11,250 square feet
|
|
Maximum distance of travel to
extinguisher
|
75 feet
|
75 feet
|
75 feet
|
For SI: 1 foot = 304.8 mm, 1 square
foot = 0.0929 m2, 1 gallon = 3.785 L.
a. Two 21/2-gallon water-type
extinguishers shall be deemed the equivalent of one 4-A rated
extinguisher.
b. Annex E. 3.3 of NFPA 10 as
listed in rule
1301:7-7-80
of the Administrative Code provides more details concerning
application of the maximum floor area criteria.
c. Two water-type extinguishers each
with a 1-A rating shall be deemed the equivalent of one 2-A rated extinguisher
for Light (Low) Hazard Occupancies.
Table
906.3(2)a
Flammable or combustible liquids
with depths of less than or equal to 0.25 -inch
|
Type of
hazard
|
Basic minimum
extinguisher rating
|
Maximum distance of
travel to extinguishers (feet)
|
|
Light (low)
|
5-B
10-B
|
30
50
|
|
Ordinary
(moderate)
|
10-B
20-B
|
30
50
|
|
Extra (high)
|
40-B
80-B
|
30
50
|
For SI: 1 inch = 25.4 mm, 1 foot =
304.8 mm.
a. For requirements on water-soluble
flammable liquids and alternative sizing criteria, see section 5.5 of NFPA 10
as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
906.3.2
Class B fire hazards.
Portable fire
extinguishers for occupancies involving flammable or combustible liquids with
depths of less than or equal to 0.25 -inch ( 6.4 mm) shall be selected and
placed in accordance with Table 9063(2) of this rule.
Portable fire extinguishers for
occupancies involving flammable or combustible liquids with a depth of greater
than 0.25 -inch ( 6.4 mm) shall be selected and placed in accordance with NFPA
10 as listed in rule
1301:7-7-80
of the Administrative Code.
(c)
906.3.3
Class C fire hazards.
Portable fire
extinguishers for Class C fire hazards shall be selected and placed on the
basis of the anticipated Class A or B hazard.
(d)
906.3.4
Class D fire hazards.
Portable fire
extinguishers for occupancies involving combustible metals shall be selected
and placed in accordance with NFPA 10 as listed in rule
1301:7-7-80
of the Administrative Code.
(4)
906.4
Cooking grease fires. Fire extinguishers provided for the protection of
cooking grease fires shall be of an approved type compatible with the automatic
fire-extinguishing system agent and in accordance with
paragraph (D)(12)(e)(904.12.5) of this
rule.
(5)
906.5 Conspicuous location.
Portable fire extinguishers shall be located in
conspicuous locations where they will be readily accessible and immediately
available for use. These locations shall be along normal paths of travel,
unless the fire code official determines and in accordance with the
building code as listed in rule
1301:7-7-80
of the Administrative Code that the hazard posed indicates the need
for placement away from normal paths of travel.
(6)
906.6
Unobstructed and unobscured.
Portable fire
extinguishers shall not be obstructed or obscured from view. In rooms or areas
in which visual obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
(7)
906.7
Hangars and brackets.
Hand-held portable
fire extinguishers, not housed in cabinets, shall be installed on the hangers
or brackets supplied. Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's installation
instructions.
(8)
906.8 Cabinets.
Cabinets used to house portable fire extinguishers shall not
be locked.
Exceptions:
1.
Where portable
fire extinguishers subject to malicious use or damage are provided with a means
of ready access.
2.
In Group I-3 occupancies and in mental health areas in
Group I-2 occupancies, access to portable fire extinguishers shall be permitted
to be locked or to be located in staff locations provided the staff has
keys.
(9)
906.9 Extinguisher installation.
The installation of portable fire extinguishers shall
be in accordance with paragraphs (F)(9)(a)(906.9.1)
to (F)(9)(c)(906.9.3) of this rule.
(a)
906.9.1
Extinguishers weighing 40 pounds or less.
Portable fire extinguishers having a gross weight not
exceeding 40 pounds (18 kg) shall be installed so that their tops are not more
than 5 feet (1524 mm) above the floor.
(b)
906.9.2
Extinguishers weighing more than 40 pounds.
Hand-held portable fire extinguishers having a gross
weight exceeding 40 pounds (18 kg) shall be installed so that their tops are
not more than 3.5 feet (1067 mm) above the floor.
(c)
906.9.3
Floor clearance.
The clearance between the
floor and the bottom of installed hand-held portable fire extinguishers shall
be not less than 4 inches (102 mm).
(10)
906.10
Wheeled units.
Wheeled fire extinguishers
shall be conspicuously located in a designated
location.
(I)
Section 909
Smoke control systems
(1)
909.1 Scope and purpose.
This paragraph applies to mechanical
or passive smoke control systems where they are required for new buildings or
portions thereof by provisions of the building code as listed in rule
1301:7-7-80
of the Administrative Code or this code. The purpose of this
paragraph is to establish minimum requirements for the design,
installation and acceptance testing of smoke control systems that are intended
to provide a tenable environment for the evacuation or relocation of occupants.
These provisions are not intended for the preservation of contents, the timely
restoration of operations or for assistance in fire suppression or overhaul
activities. Smoke control systems regulated by this paragraph
serve a different purpose than the smoke- and heat-venting provisions found in
paragraph (J)(910) of this rule. Mechanical
smoke control systems shall not be considered exhaust systems under chapter 5
of the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
909.2
General design requirements.
Buildings,
structures, or parts thereof required by the building code as listed in
rule
1301:7-7-80
of the Administrative Code or this code to have a smoke control system
or systems shall have such systems designed in accordance with the applicable
requirements of paragraph (I)(909) of this
rule and the generally accepted and well-established principles of
engineering relevant to the design. The construction documents shall include
sufficient information and detail to describe adequately the elements of the
design necessary for the proper implementation of the smoke control systems.
These documents shall be accompanied with sufficient information and analysis
to demonstrate compliance with these provisions.
(3)
909.3
Special inspection and test requirements.
In addition to the ordinary inspection and test requirements
that buildings, structures and parts thereof are required to undergo, smoke
control systems subject to the provisions of paragraph
(I)(909) of this rule shall undergo special inspections and
tests sufficient to verify the proper commissioning of the smoke control design
in its final installed condition. The design submission accompanying the
construction documents shall clearly detail procedures and methods to be used
and the items subject to such inspections and tests. Such commissioning shall
be in accordance with generally accepted engineering practice and, where
possible, based on published standards for the particular testing involved. The
special inspections and tests required by this paragraph shall
be conducted under the same terms as in section 1704 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code.
(4)
909.4
Analysis.
A rational analysis supporting
the types of smoke control systems to be employed, the methods of their
operations, the systems supporting them and the methods of construction to be
utilized shall accompany the construction documents submission and include, but
not be limited to, the items indicated in paragraphs
(I)(4)(a)(909.4.1) to (I)(4)(g)(909.4.7) of this
rule.
(a)
909.4.1 Stack effect.
The system shall be designed such that the maximum probable
normal or reverse stack effect will not adversely interfere with the system's
capabilities. In determining the maximum probable stack effect, altitude,
elevation, weather history and interior temperatures shall be
used.
(b)
909.4.2 Temperature effect of fire.
Buoyancy and expansion caused by the design fire in
accordance with paragraph (I)(9)( 909.9) of this
rule shall be analyzed. The system shall be designed such that these
effects do not adversely interfere with the system's
capabilities.
(c)
909.4.3 Wind effect.
The design shall consider the adverse effects of wind. Such
consideration shall be consistent with the wind-loading provisions of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(d)
909.4.4
Systems.
The design shall consider the
effects of the heating, ventilating and air-conditioning ("HVAC") systems on
both smoke and fire transport. The analysis shall include all permutations of
systems status. The design shall consider the effects of the fire on the
heating, ventilating and air-conditioning systems.
(e)
909.4.5
Climate.
The design shall consider the
effects of low temperatures on systems, property and occupants. Air inlets and
exhausts shall be located so as to prevent snow or ice
blockage.
(f)
909.4.6 Duration of operation.
All portions of active or engineered smoke control
systems shall be capable of continued operation after detection of the fire
event for a period of not less than either 20 minutes or 1.5 times the
calculated egress time, whichever is greater.
(g)
909.4.7
Smoke control system interaction.
The
design shall consider the interaction effects of the operation of multiple
smoke control systems for all design scenarios.
(5)
909.5 Smoke
barrier construction. Smoke barriers required for passive smoke control
and a smoke control system using the pressurization method shall comply with
section 709 of the building code as listed in rule
1301:7-7-80
of the Administrative Code. The maximum allowable leakage area shall
be the aggregate area calculated using the following leakage area ratios:
1.
Walls:
A/Aw = 0.00100
2.
Interior exit
stairways and ramps and exit passageways: A/Aw =
0.00035
3.
Enclosed exit access stairways and ramps and all other
shafts: A/Aw = 0.00150
4.
Floors and roofs:
A/Af = 0.00050
where:
A = Total leakage area, square feet
(m2).
Af = Unit floor
or roof area of barrier, square feet
(m2).
Aw = Unit wall
area of barrier, square feet (m2)
The leakage area ratios shown do not
include openings due to gaps around doors and operable windows. The total
leakage area of the smoke barrier shall be determined in accordance with
paragraph (I)(5)(a)(909.5.1) of this rule and
tested in accordance with paragraph (I)(5)(b)(909.5.2)
of this rule.
(a)
909.5.1
Total leakage area.
Total leakage area of
the barrier is the product of the smoke barrier gross area multiplied by the
allowable leakage area ratio, plus the area of other openings such as gaps
around doors and operable windows.
(b)
909.5.2
Testing of leakage area.
Compliance with
the maximum total leakage area shall be determined by achieving the minimum air
pressure difference across the barrier with the system in the smoke control
mode for mechanical smoke control systems utilizing the pressurization method.
Compliance with the maximum total leakage area of passive smoke control systems
shall be verified through methods such as door fan testing or other methods, as
approved by the fire code official pursuant to paragraph
(A)(1)( 901.1) of this rule. At locations or in structures not
regulated by the building code as listed in rule
1301:7-7-80
of the Administrative Code, the test method shall be approved by the fire code
official prior to system installation.
(c)
909.5.3
Opening protection.
Openings in smoke
barriers shall be protected by automatic-closing devices actuated by the
required controls for the mechanical smoke control system. Door openings shall
be protected by fire door assemblies complying with section 716.5.3 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
Exceptions:
1.
Passive smoke
control systems with automatic-closing devices actuated by spot-type smoke
detectors listed for releasing service installed in accordance with
paragraph (G)(3)( 907.3) of this
rule.
2.
Fixed openings between smoke zones that are protected
utilizing the airflow method.
3.
In Group I-1
Condition 2, Group I-2 and ambulatory care facilities, where a pair of
opposite-swinging doors are installed across a corridor in accordance with
paragraph (I)(5)(c)(i)(909.5.3.1) of this
rule, the doors shall not be required to be protected in accordance
with section 716 of the building code as listed in rule
1301:7-7-80
of the Administrative Code. The doors shall be close-fitting within
operational tolerances shall not have a center mullion or undercuts in excess
of 3/4-inch ( 19.1 mm) louvers or grilles. The doors shall have head and jamb
stops and astragals or rabbets at meeting edges and where permitted by the door
manufacturer's listing, positive-latching devices are not
required.
4.
In Group I-2 and ambulatory care facilities, where such
doors are special-purpose horizontal sliding, accordion or folding door
assemblies installed in accordance with paragraph
(J)(1)(d)(iii)(1010.1.4.3) of rule
1301:7-7-10 of
the Administrative Code and are automatic closing by smoke detection
in accordance with section 716.5.9.3 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
5.
Group
I-3.
6.
Openings between smoke zones with clear ceiling heights
of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20
minutes as determined by the design fire size.
(i)
909.5.3.1
Group I-1 Condition 2, Group I-2 and ambulatory care facilities. In
Group I-1, Condition 2, Group I-2 and ambulatory care facilities, where doors
are installed across a corridor, the doors shall be automatic closing by smoke
detection in accordance with section 716.5.9.3 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code and shall have a vision panel with
fire-protection-rated glazing materials in fire-protection-rated frames, the
area of which shall not exceed that tested.
(ii)
909.5.3.2
Ducts and air transfer openings. Ducts and air transfer openings are
required to be protected with a minimum Class II, 250°F (121°C) smoke damper
complying with section 717 of the building code as listed in rule
1301:7-7-80
of the Administrative
Code.
(6)
909.6
Pressurization method. The primary mechanical means of controlling smoke
shall be by pressure differences across smoke barriers. Maintenance of a
tenable environment is not required in the smoke-control zone of fire
origin.
(a)
909.6.1 Minimum pressure difference.
The minimum pressure difference across a smoke barrier
shall be 0.05 -inch water gage ( 0.0124 kPa) in fully sprinklered
buildings.
In buildings allowed to be other than
fully sprinklered, the smoke control system shall be designed to achieve
pressure differences at least two times the maximum calculated pressure
difference produced by the design fire.
(b)
909.6.2
Maximum pressure difference.
The maximum
air pressure difference across a smoke barrier shall be determined by required
door-opening or closing forces. The actual force required to open exit doors
when the system is in the smoke control mode shall be in accordance with
paragraph (J)(1)(c)(1010.1.3) of rule
1301:7-7-10 of
the Administrative Code.
Opening and
closing forces for other doors shall be determined by standard engineering
methods for the resolution of forces and reactions. The calculated force to set
a side-hinged, swinging door in motion shall be determined by:
F = Fdc +
K(WA[DELTA]P)/2(W-d)_____________(Equation 9-1)
where:
A = Door area, square feet
(m2).
d = Distance from door handle to latch
edge of door, feet (m).
F = Total door opening force, pounds
(N).
Fdc = Force
required to overcome closing device, pounds (N).
K = Coefficient 5.2 ( 1.0
).
W = Door width, feet (m).
[DELTA]P = Design pressure difference,
inches of water (Pa).
(c)
909.6.3
Pressurized stairways and elevator hoistways. Where stairways or
elevator hoistways are pressurized, such pressurization systems shall comply
with paragraph (I)(909) of this rule as smoke
control systems, in addition to the requirements of paragraph
(I)(21)( 909.21) of this rule and section 909.20 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(7)
909.7
Airflow design method.
Where approved by
the fire code official pursuant to paragraph (A)(1)( 901.1)
of this rule, smoke migration through openings fixed in a
permanently open position, which are located between smoke control zones by the
use of the airflow method, shall be permitted. The design airflow shall be in
accordance with this paragraph. Airflow shall be directed to
limit smoke migration from the fire zone. The geometry of openings shall be
considered to prevent flow reversal from turbulent effects. Smoke control
systems using the airflow method shall be designed in accordance with NFPA 92
as listed in rule
1301:7-7-80
of the Administrative Code. At locations or in structures not regulated by the
building code as listed in rule
1301:7-7-80
of the Administrative Code, airflow design method shall be approved by the fire
code official prior to system installation.
(a)
909.7.1
Prohibited conditions. This method shall not be employed where either
the quantity of air or the velocity of the airflow will adversely affect other
portions of the smoke control system, unduly intensify the fire, disrupt plume
dynamics or interfere with exiting. In no case shall airflow toward the fire
exceed 200 feet per minute (1.02 m/s). Where the calculated
airflow exceeds this limit, the airflow method shall not be
used.
(8)
909.8 Exhaust method.
When approved by the fire code official
pursuant to paragraph (A)(1)( 901.1) of this
rule, mechanical smoke control for large enclosed volumes, such as in
atriums or malls, shall be permitted to utilize the exhaust method. Smoke
control systems using the exhaust method shall be designed in accordance with
NFPA 92 as listed in rule
1301:7-7-80
of the Administrative Code. At locations or in structures not regulated by the
building code as listed in rule
1301:7-7-80
of the Administrative Code, the exhaust method shall be approved by the fire
code official prior to system installation.
(a)
909.8.1
Smoke layer. The height of the lowest horizontal surface of the smoke
layer interface shall be maintained not less than 6 feet (1829 mm) above a
walking surface that forms a portion of a required egress system within the
smoke zone.
(9)
909.9 Design fire.
The design fire shall be based on a rational analysis
performed by the registered design professional and approved by the fire code
official pursuant to paragraph (A)(1)( 901.1) of this
rule. The design fire shall be based on the analysis in accordance
with paragraph (I)(4)( 909.4) of this rule
and this paragraph. At locations or in structures not regulated by the
building code as listed in rule
1301:7-7-80
of the Administrative Code, the design fire shall be approved by the fire code
official prior to system installation.
(a)
909.9.1
Factors considered.
The engineering
analysis shall include the characteristics of the fuel, fuel load, effects
included by the fire and whether the fire is likely to be steady or
unsteady.
(b)
909.9.2 Design fire fuel.
Determination of the design fire shall include
consideration of the type of fuel, fuel spacing and
configuration.
(c)
909.9.3 Heat-release assumptions.
The analysis shall make use of best available data from
approved sources and shall not be based on excessively stringent limitations of
combustible material.
(d)
909.9.4 Sprinkler effectiveness
assumptions.
A documented engineering
analysis shall be provided for conditions that assume fire growth is halted at
the time of sprinkler activation.
(10)
909.10 Equipment.
Equipment including, but not limited to, fans, ducts,
automatic dampers and balance dampers shall be suitable for their intended use,
suitable for the probable exposure temperatures that the rational analysis
indicates, and as approved by the fire code official pursuant to
paragraph (A)(1)( 901.1) of this rule. At locations or in
structures not regulated by the building code as listed in rule
1301:7-7-80
of the Administrative Code, the equipment shall be approved by the fire code
official prior to system installation.
(a)
909.10.1
Exhaust fans.
Components of exhaust fans
shall be rated and certified by the manufacturer for the probable temperature
rise to which the components will be exposed. This temperature rise shall be
computed by:
Ts =
(Qc/mc) +
(Ta)_____________(Equation 9-3)
where:
c = Specific heat of smoke at smoke
layer temperature, Btu/lb°F· (kJ/kg · K).
m = Exhaust rate, pounds per second
(kg/s).
Qc = Convective
heat output of fire, Btu/s (kW).
Ta = Ambient
temperature, °F (K).
Ts = Smoke
temperature, °F (K).
Exception:
Reduced Ts as calculated based on the assurance of
adequate dilution air.
(b)
909.10.2
Ducts.
Duct materials and joints shall be
capable of withstanding the probable temperatures and pressures to which they
are exposed as determined in accordance with paragraph
(I)(10)(a)(909.10.1) of this rule. Ducts shall be constructed
and supported in accordance with the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code. Ducts shall be leak tested to 1.5 times
the maximum design pressure in accordance with nationally accepted practices.
Measured leakage shall not exceed 5 per cent of design flow.
Results of such testing shall be a part of the documentation procedure. Ducts
shall be supported directly from fire-resistance-rated structural elements of
the building by substantial, noncombustible supports.
Exception:
Flexible connections, for the purpose of vibration
isolation, complying with the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code and that are constructed of approved
fire-resistance-rated materials.
(c)
909.10.3
Equipment, inlets and outlets.
Equipment
shall be located so as to not expose uninvolved portions of the building to an
additional fire hazard. Outside air inlets shall be located so as to minimize
the potential for introducing smoke or flame into the building. Exhaust outlets
shall be so located as to minimize reintroduction of smoke into the building
and to limit exposure of the building or adjacent buildings to an additional
fire hazard.
(d)
909.10.4 Automatic dampers.
Automatic dampers, regardless of the purpose for which
they are installed within the smoke control system, shall be listed and conform
to the requirements of section 716.3 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(e)
909.10.5
Fans.
In addition to other requirements,
belt-driven fans shall have 1.5 times the number of belts required for the
design duty with the minimum number of belts being two. Fans shall be selected
for stable performance based on normal temperature and, where applicable,
elevated temperature. Calculations and manufacturer's fan curves shall be part
of the documentation procedures. Fans shall be supported and restrained by
noncombustible devices in accordance with the structural design requirements of
chapter 16 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
Motors driving fans shall not be
operated beyond their nameplate horsepower (kilowatts) as determined from
measurement of actual current draw and shall have a minimum service factor of
1.15.
(11)
909.11 Standby
power.
Smoke control systems shall be
provided with standby power in accordance with paragraph
(D)(604) of rule
1301:7-7-06
of the Administrative Code.
(a)
909.11.1
Equipment room.
The standby power source
and its transfer switches shall be in a room separate from the normal power
transformers and switch gears and ventilated directly to and from the exterior.
The room shall be enclosed with not less than 1-hour fire barriers constructed
in accordance with section 707 of the building code as listed in rule
1301:7-7-80
of the Administrative Code or horizontal assemblies constructed in
accordance with section 711 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, or both.
(b)
909.11.2
Power sources and power surges.
Elements
of the smoke control system relying on volatile memories or the like shall be
supplied with uninterruptible power sources of sufficient duration to span
15-minute primary power interruption. Elements of the smoke control system
susceptible to power surges shall be suitably protected by conditioners,
suppressors or other approved means.
(12)
909.12 Detection and control
systems.
Fire detection systems providing
control input or output signals to mechanical smoke control systems or elements
thereof shall comply with the requirements of paragraph
(G)(907) of this rule. Such systems shall be equipped with a
control unit complying with UL 864 as listed in rule
1301:7-7-80
of the Administrative Code and listed as smoke control
equipment.
(a)
909.12.1 Verification. Control systems for
mechanical smoke control systems shall include provisions for verification.
Verification shall include positive confirmation of actuation, testing, manual
override and the presence of power downstream of all disconnects. A
preprogrammed weekly test sequence shall report abnormal conditions audibly,
visually and by printed report. The preprogrammed weekly test shall operate all
devices, equipment and components used for smoke control.
Exception:
Where verification of individual components tested
through the preprogrammed weekly testing sequence will interfere with, and
produce unwanted effects to, normal building operation, such individual
components are permitted to be bypassed from the preprogrammed weekly testing,
where approved by the fire code official and in accordance with both of the
following:
1.
Where the operation of components is bypassed from the
preprogrammed weekly test, presence of power downstream of all disconnects
shall be verified weekly by a listed control unit.
2.
Testing of all
components bypassed from the preprogrammed weekly test shall be in accordance
with paragraph (I)(20)(f)(909.20.6) of this
rule.
(b)
909.12.2 Wiring.
In addition to meeting requirements of NFPA 70
as listed in rule
1301:7-7-80
of the Administrative Code, all wiring, regardless of voltage, shall
be fully enclosed within continuous raceways.
(c)
909.12.3
Activation.
Smoke control systems shall be
activated in accordance with this paragraph.
(i)
909.12.3.1
Pressurization, airflow or exhaust method. Mechanical smoke control
systems using the pressurization, airflow or exhaust method shall have
completely automatic control.
(ii)
909.12.3.2
Passive method. Passive smoke control systems actuated by approved
spot-type detectors listed for releasing service shall be
permitted.
(d)
909.12.4 Automatic control.
Where completely automatic control is required or used,
the automatic-control sequences shall be initiated from an appropriately zoned
automatic sprinkler system complying with paragraph
(C)(3)(a)(i)(903.3.1.1) of this rule, manual controls that are
readily accessible to the fire department, and any smoke detectors required by
the engineering analysis.
(13)
909.13 Control air
tubing. Control air tubing shall be of sufficient size to meet the
required response times. Tubing shall be flushed clean and dry prior to final
connections and shall be adequately supported and protected from damage. Tubing
passing through concrete or masonry shall be sleeved and protected from
abrasion and electrolytic action.
(a)
909.13.1 Materials. Control air tubing
shall be hard drawn copper, Type L, ACR in accordance with ASTM B 42, ASTM B
43, ASTM B 68, ASTM B 88, ASTM B 251 and ASTM B 280 as listed in rule
1301:7-7-80
of the Administrative Code. Fittings shall be wrought copper or brass,
solder type, in accordance with ASME B 16.18 or ASME B 16.22as listed
in rule
1301:7-7-80
of the Administrative Code. Changes in direction shall be made with
appropriate tool bends. Brass compression-type fittings shall be used at final
connection to devices; other joints shall be brazed using a BCuP5 brazing alloy
with solidus above 1,100°F (593°C) and liquid is below 1,500°F (816°C). Brazing
flux shall be used on copper-to-brass joints only.
Exception:
Nonmetallic tubing used within control panels and at
the final connection to devices, provided all of the following conditions are
met:
1.
Tubing shall comply with the requirements of section
602.2.1.3 of the mechanical code as listed in rule
1301:7-7-80
of the Administrative Code.
2.
Tubing and the
connected device shall be completely enclosed with a galvanized or paint-grade
steel enclosure having a minimum thickness of 0.0296 -inches ( 0.7534 mm) (No.
22 gage). Entry to the enclosure shall be by copper tubing with a protective
grommet of neoprene or teflon or by suitable brass compression to male-barbed
adapter.
3.
Tubing shall be identified by appropriately documented
coding.
4.
Tubing shall be neatly tied and supported within
enclosure. Tubing bridging cabinet and doors or moveable devices shall be of
sufficient length to avoid tension and excessive stress. Tubing shall be
protected against abrasion. Tubing serving devices on doors shall be fastened
along hinges.
(b)
909.13.2 Isolation from other
functions.
Control tubing serving other
than smoke control functions shall be isolated by automatic isolation valves or
shall be an independent system.
(c)
909.13.3
Testing.
Control air tubing shall be
tested at three times the operating pressure for not less than 30 minutes
without any noticeable loss in gauge pressure prior to final connection to
devices.
(14)
909.14 Marking and
identification.
The detection and control
systems shall be clearly marked at all junctions, accesses and
terminations.
(15)
909.15 Control
diagrams.
Identical control diagrams
showing all devices in the system and identifying their location and function
shall be maintained current and kept on file with the fire code official, the
fire department and in the fire command center in a format and manner approved
by the fire chief.
(16)
909.16 Fire fighter's smoke
control panel.
A fire fighter's smoke
control panel for fire department emergency response purposes only shall be
provided and shall include manual control or override of automatic control for
mechanical smoke control systems. The panel shall be located in a fire command
center complying with paragraph (H)(508) of rule
1301:7-7-05
of the Administrative Code in high-rise buildings or buildings with
smoke-protected assembly seating. In all other buildings, the fire fighter's
smoke control panel shall be installed in an approved location adjacent to the
fire alarm control panel. The fire fighter's smoke control panel shall comply
with paragraphs (I)(16)(a)(909.16.1) to
(I)(16)(c)(909.16.3) of this rule.
(a)
909.16.1
Smoke control systems.
Fans within the
building shall be shown on the fire fighter's control panel. A clear indication
of the direction of airflow and the relationship of components shall be
displayed. Status indicators shall be provided for all smoke control equipment,
annunciated by fan and zone and by pilot-lamp-type indicators as follows:
(i)
Fans, dampers and
other operating equipment in their normal status - "WHITE."
(ii)
Fans, dampers
and other operating equipment in their off or closed status -
"RED."
(iii)
Fans, dampers and other operating equipment in their on
or open status - "GREEN."
(iv)
Fans, dampers
and other operating equipment in a fault status -
"YELLOW/AMBER."
(b)
909.16.2 Smoke control panel.
The fire fighter's control panel shall provide control
capability over the complete smoke control system equipment within the building
as follows:
(i)
"ON-AUTO-OFF" control over each individual piece of
operating smoke control equipment that can also be controlled from other
sources within the building. This includes stairway pressurization fans; smoke
exhaust fans; supply, return and exhaust fans; elevator shaft fans; and other
operating equipment used or intended for smoke control
purposes.
(ii)
"OPEN-AUTO-CLOSE" control over individual dampers
relating to smoke control and that are also controlled from other sources
within the building.
(iii)
"ON-OFF" or "OPEN-CLOSE" control over smoke control and
other critical equipment associated with a fire or smoke emergency and that can
only be controlled from the fire fighter's control panel.
Exceptions:
1.
Complex systems,
where approved, where the controls and indicators are combined to control and
indicate all elements of a single smoke zone as a unit.
2.
Complex systems,
where approved, where the control is accomplished by computer interface using
approved, plain English commands.
(c)
909.16.3
Control action and priorities. The fire fighter's control panel actions
shall be as follows:
(i)
"ON-OFF" and "OPEN-CLOSE" control actions shall have
the highest priority of any control point within the building. Once issued from
the fire fighter's control panel, automatic or manual control from any other
control point within the building shall not contradict the control action.
Where automatic means are provided to interrupt normal, nonemergency equipment
operation or produce a specific result to safeguard the building or equipment
including, but not limited to, duct freezestats, duct smoke detectors,
high-temperature cutouts, temperature-actuated linkage and similar devices,
such means shall be capable of being overridden by the fire-fighter's control
panel. The last control action as indicated by each fire fighter's control
panel switch position shall prevail. Control actions shall not require the
smoke control system to assume more than one configuration at any one
time.
Exception:
Power disconnects required by NFPA 70 as listed
in rule
1301:7-7-80
of the Administrative Code.
(ii)
Only the "AUTO"
position of each three-position fire-fighter's control panel switch shall allow
automatic or manual control action from other control points within the
building. The "AUTO" position shall be the "NORMAL," nonemergency, building
control position. Where a fire fighter's control panel is in the "AUTO"
position, the actual status of the device (on, off, open, closed) shall
continue to be indicated by the status indicator described in
paragraph (I)(16)(a)(909.16.1) of this rule.
Where directed by an automatic signal to assume an emergency condition, the
"NORMAL" position shall become the emergency condition for that device or group
of devices within the zone. Control actions shall not require the smoke control
system to assume more than one configuration at any one
time.
(17)
909.17 System response
time.
Smoke-control system activation
shall be initiated immediately after receipt of an appropriate automatic or
manual activation command. Smoke control systems shall activate individual
components (such as dampers and fans) in the sequence necessary to prevent
physical damage to the fans, dampers, ducts and other equipment. For purposes
of smoke control, the fire fighter's control panel response time shall be the
same for automatic or manual smoke control action initiated from any other
building control point. The total response time, including that necessary for
detection, shutdown of operating equipment and smoke control system startup,
shall allow for full operational mode to be achieved before the conditions in
the space exceed the design smoke condition. The system response time for each
component and their sequential relationships shall be detailed in the required
rational analysis and verification of their installed condition reported in the
required final report.
(18)
909.18 Acceptance
testing.
Devices, equipment, components
and sequences shall be individually tested. These tests, in addition to those
required by other provisions of this code, shall consist of determination of
function, sequence and, where applicable, capacity of their installed
condition.
(a)
909.18.1 Detection devices.
Smoke or fire detectors that are a part of a smoke
control system shall be tested in accordance with this rule in
their installed condition. When applicable, this testing shall include
verification of airflow in both minimum and maximum conditions.
(b)
909.18.2
Ducts.
Ducts that are part of a smoke
control system shall be traversed using generally accepted practices to
determine actual air quantities.
(c)
909.18.3
Dampers.
Dampers shall be tested for
function in their installed condition.
(d)
909.18.4
Inlets and outlets.
Inlets and outlets
shall be read using generally accepted practices to determine air
quantities.
(e)
909.18.5 Fans.
Fans
shall be examined for correct rotation. Measurements of voltage, amperage,
revolutions per minute and belt tension shall be made.
(f)
909.18.6
Smoke barriers.
Measurements using
inclined manometers or other approved calibrated measuring devices shall be
made of the pressure differences across smoke barriers. Such measurements shall
be conducted for each possible smoke control condition.
(g)
909.18.7
Controls.
Each smoke zone equipped with an
automatic-initiation device shall be put into operation by the actuation of one
such device. Each additional device within the zone shall be verified to cause
the same sequence without requiring the operation of fan motors in order to
prevent damage. Control sequences shall be verified throughout the system,
including verification of override from the fire fighter's control panel and
simulation of standby power conditions.
(h)
909.18.8
Testing for smoke control. Smoke control systems shall be tested by a
special inspector in accordance with Section
1705.18 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code.
(i)
909.18.8.1
Scope of testing. Testing shall be conducted in accordance with the
following:
(a)
During erection of ductwork and prior to concealment for the
purposes of leakage testing and recording of device location.
(b)
Prior to
occupancy and after sufficient completion for the purposes of
pressure-difference testing, flow measurements, and detection and control
verification.
(ii)
909.18.8.2 Qualifications. Approved
agencies for smoke control testing shall have expertise in fire protection
engineering, mechanical engineering and certification as air
balancers.
(iii)
909.18.8.3 Reports. A complete report of
testing shall be prepared by the approved agency. The report shall include
identification of all devices by manufacturer, nameplate data, design values,
measured values and identification tag or mark. The report shall be reviewed by
the responsible registered design professional and, when satisfied that the
design intent has been achieved, the responsible registered design professional
shall sign, seal and date the report.
(a)
909.18.8.3.1 Report filing. A copy of the final
report shall be filed with the fire code official and the building code
official and an identical copy shall be maintained in an approved
location at the building.
(i)
909.18.9
Identification and documentation. Charts, drawings and other documents
identifying and locating each component of the smoke control system, and
describing their proper function and maintenance requirements, shall be
maintained on file at the building as an attachment to the report required by
paragraph (I)(18)(h)(iii)(909.18.8.3) of this
rule. Devices shall have an approved identifying tag or mark on them
consistent with the other required documentation and shall be dated indicating
the last time they were successfully tested and by whom.
(19)
909.19 System acceptance. Buildings, or portions thereof, required
by this code to comply with this paragraph shall not be
occupied until such time that the provisions of this
paragraph have been fully complied with and that the fire
department has received satisfactory instruction on the operation, both
automatic and manual, of the system and a written maintenance program complying
with the requirements of paragraph (I)(20)(a)(909.20.1)
of this rule has been submitted and approved by the fire code
official.
Exception:
In buildings of phased construction, a temporary
certificate of occupancy, as approved by the building official
in accordance with the building code as listed in rule
1301:7-7-80
of the Administrative Code, shall be allowed, provided that those
portions of the building to be occupied meet the requirements of this
paragraph and that the remainder does not pose a significant
hazard to the safety of the proposed occupants or adjacent buildings.
(20)
909.20
Maintenance.
Smoke control systems shall
be maintained to ensure to a reasonable degree that the system is capable of
controlling smoke for the duration required. The system shall be maintained in
accordance with the manufacturer's instructions and paragraphs
(I)(20)(a)(909.20.1) to (I)(20)(f)(909.20.6) of this
rule.
(a)
909.20.1 Schedule.
A
routine maintenance and operational testing program shall be initiated
immediately after the smoke control system has passed the acceptance tests. A
written schedule for routine maintenance and operational testing shall be
established.
(b)
909.20.2 Records.
Records of smoke control system testing and maintenance
shall be maintained. The record shall include the date of the maintenance,
identification of the servicing personnel and notification of any
unsatisfactory condition and the corrective action taken, including parts
replaced.
(c)
909.20.3 Testing.
Operational testing of the smoke control system shall
include all equipment such as initiating devices, fans, dampers, controls,
doors and windows.
(d)
909.20.4 Dedicated smoke control systems.
Dedicated smoke control systems shall be
operated for each control sequence semiannually. The system shall also be
tested under standby power conditions.
(e)
909.20.5
Nondedicated smoke control systems.
Nondedicated smoke control systems shall be operated for
each control sequence annually. The system shall be tested under standby power
conditions.
(f)
909.20.6 Components bypassing weekly test.
Where components of the smoke control system are
bypassed by the preprogrammed weekly test required by
paragraph (I)(12)(a)(909.12.1) of this rule,
such components shall be tested semiannually. The system shall be tested under
standby power conditions.
(21)
[BF]
909.21 Elevator hoistway pressurization alternative.
Where elevator hoistway pressurization is provided in
lieu of required enclosed elevator lobbies, the pressurization system shall
comply with paragraphs (I)(21)(a)(909.21.1)
to (I)(21)(k)(909.21.11) of this rule.
(a)
[BF]
909.21.1 Pressurization requirements. Elevator hoistways shall be
pressurized to maintain a minimum positive pressure of 0.10 inch of water (25
Pa) and a maximum positive pressure of 0.25 inch of water (67 Pa) with respect
to adjacent occupied space on all floors. This pressure shall be measured at
the midpoint of each hoistway door, with all elevator cars at the floor of
recall and all hoistway doors closed. The pressure differential shall be
measured between the hoistway and the adjacent elevator landing. The opening
and closing of hoistway doors at each level must be demonstrated during this
test. The supply air intake shall be from an outside, uncontaminated source
located a minimum distance of 20 feet (6096 mm) from any air exhaust system or
outlet.
Exceptions:
1.
On floors
containing only Group R occupancies, the pressure differential is permitted to
be measured between the hoistway and a dwelling unit or sleeping
unit.
2.
Where an elevator opens into a lobby enclosed in
accordance with Section 3007.6 or 3008.6 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, the pressure differential is permitted to be
measured between the hoistway and the space immediately outside the door(s)
from the floor to the enclosed lobby.
3.
The pressure
differential is permitted to be measured relative to the outdoor atmosphere on
floors other than the following:
3.1
The fire floor.
3.2
The two floors
immediately below the fire floor.
3.3
The floor
immediately above the fire floor.
4.
The minimum
positive pressure of 0.10 inch of water (25 Pa) and a maximum positive pressure
of 0.25 inch of water (67 Pa) with respect to occupied floors is not required
at the floor of recall with the doors open.
(i)
[BF]
909.21.1.1 Use of ventilation systems. Ventilation systems, other than
hoistway supply air systems, are permitted to be used to exhaust air from
adjacent spaces on the fire floor, two floors immediately below and one floor
immediately above the fire floor to the building's exterior where necessary to
maintain positive pressure relationships as required in
paragraph (I)(21)(a)(909.21.1) of this rule
during operation of the elevator shaft pressurization system.
(b)
[BF] 909.21.2 Rational analysis.
A rational analysis complying with
paragraph (I)(4)( 909.4) of this rule shall
be submitted with the construction documents.
(c)
[BF]
909.21.3 Ducts for system.
Any duct system
that is part of the pressurization system shall be protected with the same
fire-resistance rating as required for the elevator shaft
enclosure.
(d)
[BF] 909.21.4 Fan system.
The fan system provided for the pressurization system
shall be as required by paragraphs (I)(21)(d)(i)(909.21.4.1)
to (I)(21)(d)(iv)(909.21.4.4) of this
rule.
(i)
[BF] 909.21.4.1 Fire resistance. Where
located within the building, the fan system that provides the pressurization
shall be protected with the same fire-resistance rating required for the
elevator shaft enclosure.
(ii)
[BF]
909.21.4.2 Smoke detection. The fan system shall be equipped with a
smoke detector that will automatically shut down the fan system when smoke is
detected within the system.
(iii)
[BF]
909.21.4.3 Separate systems. A separate fan system shall be used for
each elevator hoistway.
(iv)
909.21.4.4 Fan capacity. The supply fan
shall be either adjustable with a capacity of not less than 1,000 cfm ( 0.4719
m3/s) per door, or that specified by a registered
design professional to meet the requirements of a designed pressurization
system.
(e)
[BF] 909.21.5 Standby power.
The pressurization system shall be provided with
standby power in accordance with paragraph (D)(604) of
rule
1301:7-7-06
of the Administrative Code.
(f)
[BF]
909.21.6 Activation of pressurization system.
The elevator pressurization system shall be activated
upon activation of either the building fire alarm system or the elevator lobby
smoke detectors. Where both a building fire alarm system and elevator lobby
smoke detectors are present, each shall be independently capable of activating
the pressurization system.
(g)
[BF]
909.21.7 Testing.
Testing for performance
shall be required in accordance with paragraph
(I)(18)(h)(909.18.8) of this rule. System acceptance shall be
in accordance with paragraph (I)(19)( 909.19) of this
rule.
(h)
[BF] 909.21.8 Marking and identification.
Detection and control systems shall be marked in accordance with
paragraph (I)(14)(909.14) of this
rule.
(i)
[BF] 909.21.9 Control diagrams. Control
diagrams shall be provided in accordance with paragraph
(I)(15) (909.15) of this
rule.
(j)
[BF] 909.21.10 Control panel. A control
panel complying with paragraph (I)(16)(909.16) of this
rule shall be provided.
(k)
[BF]
909.21.11 System response time. Hoistway pressurization systems shall
comply with the requirements for smoke control system response time in
paragraph (I)(17)(909.17) of this
rule.
(N)
Section 914
Fire protection based on special detailed requirements of use and
occupancy
(1)
914.1 General.
This
paragraph shall specify where fire protection systems are
required based on the detailed requirements of use and occupancy of the
building code as listed in rule
1301:7-7-80
of the Administrative Code.
(2)
914.2
Covered and open mall buildings.
Covered
and open mall buildings shall comply with paragraphs
(N)(2)(a)(914.2.1) to (N)(2)(d)(914.2.4) of this
rule.
(a)
914.2.1 Automatic sprinkler system.
Covered and open mall buildings and buildings connected
shall be equipped throughout with an automatic sprinkler system in accordance
with paragraph (C)(1)(a)(903.1.1) of this
rule, which shall comply with all of the following:
(i)
The automatic
sprinkler system shall be complete and operative throughout occupied space in
the mall building prior to occupancy of any of the tenant spaces. Unoccupied
tenant spaces shall be similarly protected unless provided with approved
alternative protection.
(ii)
Sprinkler protection for the mall of a covered mall
building shall be independent from that provided for tenant spaces or anchor
buildings.
(iii)
Sprinkler protection for the tenant spaces of an open
mall building shall be independent from that provided for anchor
buildings.
(iv)
Sprinkler protection shall be provided beneath exterior
circulation balconies located adjacent to an open mall.
(v)
Where tenant
spaces are supplied by the same system, they shall be independently
controlled.
Exception:
An automatic sprinkler system shall not be required in
spaces or areas of open parking garages separated from the covered or open mall
in accordance with section 402.4.2.3 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code and constructed in accordance with section
406.5 of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
(b)
914.2.2
Standpipe system.
The covered and open
mall building shall be equipped throughout with a standpipe system as required
by paragraph (E)(3)(c)(905.3.3) of this
rule.
(c)
914.2.3 Emergency voice/alarm communication
system.
Where the total floor area exceeds
50,000 square feet (4645 m2) within either a covered
mall building or within the perimeter line of an open mall building, an
emergency voice/alarm communication system shall be provided. Emergency
voice/alarm communication systems serving a mall, required or otherwise, shall
be accessible to the fire department. The system shall be provided in
accordance with paragraph (G)(5)(b)(ii)(907.5.2.2) of
this rule.
(d)
914.2.4 Fire department access to equipment.
Rooms or areas containing controls for air-conditioning systems,
automatic fire-extinguishing systems, automatic sprinkler systems or other
detection, suppression or control elements shall be identified for use by the
fire department.
(3)
914.3
High-rise buildings. High-rise buildings shall comply with
paragraphs (N)(3)(a)(914.3.1) to
(N)(3)(g)(914.3.7) of this rule.
(a)
914.3.1
Automatic sprinkler system.
Buildings and
structures shall be equipped throughout with an automatic sprinkler system in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of
this rule and a secondary water supply where required by
paragraph (N)(3)(c)(914.3.3) of this
rule.
Exception:
An automatic sprinkler system shall not be required in
spaces or areas of:
1.
Open parking garages in accordance with section 406.5
of the building code as listed in rule
1301:7-7-80
of the Administrative Code.
2.
Telecommunications
equipment buildings used exclusively for telecommunications equipment,
associated electrical power distribution equipment, batteries and standby
engines, provided that those spaces or areas are equipped throughout with an
automatic fire detection system in accordance with paragraph
(G)(2)( 907.2) of this rule and are separated from the
remainder of the building by not less than 1-hour fire barriers constructed in
accordance with section 707 of the building code as listed in rule
1301:7-7-80
of the Administrative Code or not less than 2-hour horizontal
assemblies constructed in accordance with section 711 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code, or both.
(i)
914.3.1.1
Number of sprinkler risers and system design. Each sprinkler system zone
in buildings that are more than 420 feet (128 m) in height shall be supplied by
a minimum of two risers. Each riser shall supply sprinklers on alternate
floors. If more than two risers are provided for a zone, sprinklers on adjacent
floors shall not be supplied from the same riser.
(a)
914.3.1.1.1
Riser location. Sprinkler risers shall be placed in interior exit
stairways and ramps that are remotely located in accordance with
paragraph (G)(1007) of rule
1301:7-7-10 of
the Administrative Code.
(ii)
914.3.1.2
Water supply to required fire pumps. In buildings that are more than 420
feet (128 m) in building height, required fire pumps shall be supplied by
connections to no fewer than two water mains located in different streets.
Separate supply piping shall be provided between each connection to the water
main and the pumps. Each connection and the supply piping between the
connection and the pumps shall be sized to supply the flow and pressure
required for the pumps to operate.
Exception:
Two connections to the same main shall be permitted
provided the main is valved such that an interruption can be isolated so that
the water supply will continue without interruption through no fewer than one
of the connections.
(b)
914.3.2
Secondary water supply.
An automatic
secondary on-site water supply having a capacity not less than the
hydraulically calculated sprinkler demand, including the hose stream
requirement, shall be provided for high-rise buildings assigned to in Seismic
Design Category C, D, E or F as determined by the building code as
listed in rule
1301:7-7-80
of the Administrative Code. An additional fire pump shall not be
required for the secondary water supply unless needed to provide the minimum
design intake pressure at the suction side of the fire pump supplying the
automatic sprinkler system. The secondary water supply shall have a duration of
not less than 30 minutes as determined by the occupancy hazard classification
in accordance with NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code.
Exception:
Existing buildings.
(c)
914.3.3
Fire alarm system.
A fire alarm system
shall be provided in accordance with paragraph (G)(2)(m)(907.2.13) of
this rule.
(d)
914.3.4 Automatic smoke detection.
Smoke detection shall be provided in accordance with
paragraph (G)(2)(m)(i)(907.2.13.1) of this
rule.
(e)
914.3.5 Emergency voice/alarm communication
system.
An emergency voice/alarm
communication system shall be provided in accordance with
paragraph (G)(5)(b)(ii)(907.5.2.2) of this
rule.
(f)
914.3.6 Emergency responder radio coverage.
Emergency responder radio coverage shall be provided in
accordance with paragraph (J)(510) of rule
1301:7-7-05
of the Administrative Code.
(g)
914.3.7
Fire command.
A fire command center
complying with paragraph (H)(508) of rule
1301:7-7-05
of the Administrative Code shall be provided in a location approved by
the fire department.
(4)
914.4
Atriums.
Atriums shall comply with
paragraphs (N)(4)(a)(914.4.1) and (N)(4)(b)(914.4.2)
of this rule.
(a)
914.4.1 Automatic sprinkler system.
An approved automatic sprinkler system shall be
installed throughout the entire building.
Exceptions:
1.
That area of a
building adjacent to or above the atrium need not be sprinklered, provided that
portion of the building is separated from the atrium portion by not less than a
2-hour fire barrier constructed in accordance with section 707 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code or horizontal assemblies constructed in
accordance with section 711 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, or both.
2.
Where the ceiling
of the atrium is more than 55 feet (16 764 mm) above the floor, sprinkler
protection at the ceiling of the atrium is not
required.
(b)
914.4.2 Fire alarm system.
A fire alarm system shall be provided where required by
paragraph (G)(2)(n)(907.2.14) of this
rule.
(5)
914.5 Underground buildings.
Underground buildings shall comply with
paragraphs (N)(5)(a)(914.5.1) to
(N)(5)(e)(914.5.5) of this rule.
(a)
914.5.1
Automatic sprinkler system.
The highest
level of exit discharge serving the underground portions of the building and
all levels below shall be equipped with an automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(i)(903.3.1.1)
of this rule. Water-flow switches and control valves shall be
supervised in accordance with paragraph (C)(4)( 903.4)
of this rule.
(b)
914.5.2
Smoke control system.
A smoke control
system is required to control the mitigation of products of combustion in
accordance with paragraph (I)(909) of this
rule and provisions of this paragraph. Smoke control
shall restrict movement of smoke to the general area of fire origin and
maintain means of egress in a usable condition.
(c)
914.5.3
Compartment smoke control system.
Where
compartmentation is required by section 405.4 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code, each compartment shall have an independent
smoke control system. The system shall be automatically activated and capable
of manual operation in accordance with paragraph
(G)(2)(r)(907.2.18) of this rule.
(d)
914.5.4
Fire alarm system.
A fire alarm system
shall be provided where required by paragraphs
(G)(2)(r)(907.2.18) and (G)(2)(s)(907.2.19) of this
rule.
(e)
914.5.5 Standpipe system.
The underground building shall be provided throughout
with a standpipe system in accordance with paragraph (E)(905)
of this rule.
(6)
914.6
Stages.
Stages shall comply with
paragraphs (N)(6)(a)(914.6.1) and (N)(6)(b)(914.6.2)
of this rule.
(a)
914.6.1 Automatic sprinkler system.
Stages shall be equipped with an automatic sprinkler
system in accordance with paragraph (C)(3)(a)(i)(903.3.1.1)
of this rule. Sprinklers shall be installed under the roof and
gridiron and under all catwalks and galleries over the stage. Sprinklers shall
be installed in dressing rooms, performer lounges, shops and storerooms
accessory to such stages.
Exceptions:
1.
Sprinklers are not
required under stage areas less than 4 feet (1219 mm) in clear height utilized
exclusively for storage of tables and chairs, provided the concealed space is
separated from the adjacent spaces by Type X gypsum board not less than
5/8-inch ( 15.9 mm) thickness.
2.
Sprinklers are not
required for stages 1,000 square feet (93 m2) or
less in area and 50 feet (15 240 mm) or less in height where curtains, scenery
or other combustible hangings are not retractable vertically. Combustible
hangings shall be limited to a single main curtain, borders, legs and a single
backdrop.
3.
Sprinklers are not required within portable orchestra
enclosures on stages.
(b)
914.6.2
Standpipe system.
Standpipe systems shall
be provided in accordance with paragraph (E)(905) of
this rule.
(7)
914.7
Special amusement buildings.
Special
amusement buildings shall comply with paragraphs
(N)(7)(a)(914.7.1) and (N)(7)(b)(914.7.2) of this rule.
(a)
914.7.1
Automatic sprinkler system. Special amusement buildings shall be
equipped throughout with an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) of this
rule. Where the special amusement building is temporary,
movable, or portable the sprinkler water supply shall be of an
approved temporary means.
Exception.:
1.
Automatic
sprinklers are not required where the total floor area of a temporary special
amusement occupancy is less than 1,000 square feet (93
m2) and the exit access travel distance from any
point to an exit is less than 50 feet (15 240 mm).
2.
Automatic
fire sprinklers are not required where the total floor area of a temporary
special amusement occupancy in an existing building is less than 5,000 square
feet (93 m2), the travel distance from any point to
an exit is less than 50 feet (15,240 mm), and where, in the opinion of the fire
code official, additional means have been provided to ensure an equivalent
level of safety for all occupants during the hours that the special amusement
building is operated and occupied. Such additional means may include, but not
be limited to: fire watches, reduced occupant loads, additional means of
egress, additional detection and portable fire extinguishers.
(b)
914.7.2 Automatic smoke detection. Special
amusement buildings shall be equipped with an automatic smoke detection system
in accordance with paragraph (G)(2)(l)(907.2.12) of
this rule.
(8)
914.8
Aircraft-related occupancies. Aircraft-related occupancies shall comply
with paragraphs (N)(8)(a)(914.8.1) to
(G)(2)(f)(914.8.6) of this rule.
(a)
914.8.1
Automatic smoke detection systems.
Airport
traffic control towers shall be provided with an automatic smoke detection
system installed in accordance with paragraph
(G)(2)(v)(907.2.22) of this rule.
(b)
914.8.2
Automatic sprinkler system for new airport traffic control towers.
Where an occupied floor is located more than 35 feet
(10 668 mm) above the lowest level of fire department vehicle access, new
airport traffic control towers shall be equipped with an automatic sprinkler
system in accordance with paragraph (C)(3)(a)(i)(903.3.1.1)
of this rule.
(c)
914.8.3
Fire suppression for aircraft hangars.
Aircraft hangars shall be provided with a fire suppression
system designed in accordance with NFPA 409 as listed in rule
1301:7-7-80
of the Administrative Code, based upon the classification for the
hangar given in Table 914.8.3 of this rule.
Exception:
Where a fixed base operator has separate repair
facilities on site, Group II hangars operated by a fixed base operator used for
storage of transient aircraft only shall have a fire suppression system, but
the system shall be exempt from foam requirements.
Table 914.8.3
Hangar fire suppression
requirementsa,b,c
|
Maximum single fire area,
square feet (m2)
|
Building code as
listed in rule 1301:7-7-80- Type of construction
|
|
IA
|
IB
|
IIA
|
IIB
|
IIIA
|
IIIB
|
IV
|
VA
|
VB
|
|
>40,001
|
Group I
|
Group I
|
Group I
|
Group I
|
Group I
|
Group I
|
Group I
|
Group I
|
Group I
|
|
40,000
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
|
30,000
|
Group III
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
|
20,000
|
Group III
|
Group III
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
Group II
|
|
15,000
|
Group III
|
Group III
|
Group III
|
Group II
|
Group III
|
Group II
|
Group III
|
Group II
|
Group II
|
|
12,000
|
Group III
|
Group III
|
Group III
|
Group
III
|
Group III
|
Group III
|
Group III
|
Group II
|
Group II
|
|
8,000
|
Group III
|
Group III
|
Group III
|
Group
III
|
Group III
|
Group III
|
Group III
|
Group III
|
Group II
|
|
5,000
|
Group III
|
Group III
|
Group III
|
Group
III
|
Group III
|
Group III
|
Group III
|
Group III
|
Group III
|
For SI: 1 square foot = 0.0929
m2, 1 foot = 304.8 mm.
a. Aircraft hangars with a door height
greater than 28 feet shall be provided with fire suppression for a Group I
hangar regardless of maximum fire area.
b. Groups shall be as classified in
accordance with NFPA 409 as listed in rule
1301:7-7-80
of the Administrative Code.
c. Membrane structures complying with
section 3102 of the building code as listed in rule
1301:7-7-80
of the Administrative Code shall be classified as a Group IV
hangar.
(i)
914.8.3.1 Hazardous operations. Any Group
III aircraft hangar according to Table 914.8.3 of this rule
that contains hazardous operations including, but not limited to, the following
shall be provided with a Group I or Group II fire suppression system in
accordance with NFPA 409 as listed in rule
1301:7-7-80
of the Administrative Code as applicable:
(a)
Doping.
(b)
Hot working
including, but not limited to, welding, torch cutting and torch
soldering.
(c)
Fuel transfer.
(d)
Fuel tank repair
or maintenance not including defueled tanks in accordance with NFPA 409
as listed in rule
1301:7-7-80
of the Administrative Code, inerted tanks or tanks that have never
been fueled.
(e)
Spray finishing operations.
(f)
Total fuel
capacity of all aircraft within the unsprinklered single fire area in excess of
1,600 gallons (6057L).
(g)
Total fuel capacity of all aircraft within the maximum
single fire area in excess of 7,500 gallons (28 390 L) for a hangar equipped
throughout with an automatic fire sprinkler system in accordance with
paragraph (C)(3)(a)(i)(9033.1.1) of this
rule.
(ii)
914.8.3.2 Separation of maximum single fire
areas. Maximum single fire areas established in accordance with hangar
classification and construction type in Table 914.8.3 of this
rule shall be separated by 2-hour fire walls constructed in accordance
with section 706 of the building code as listed in rule
1301:7-7-80
of the Administrative Code. In determining the maximum single fire
area as set forth in Table 914.8.3 of this rule, ancillary
uses that are separated from aircraft servicing areas by not less than a 1-hour
fire barrier constructed in accordance with section 707 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code shall not be included in the
area.
(d)
914.8.4 Finishing.
The process of "doping," involving the use of a
volatile flammable solvent, or of painting shall be carried on in a separate
detached building equipped with automatic fire-extinguishing equipment in
accordance with paragraph (C)(903) of this
rule.
(e)
914.8.5 Residential aircraft hangar smoke
alarms.
Smoke alarms shall be provided
within residential aircraft hangars in accordance with
paragraph (G)(2)(u)(907.2.21) of this
rule.
(f)
914.8.6 Aircraft paint hangar fire suppression.
Aircraft paint hangars shall be provided with fire
suppression as required by NFPA 409 as listed in rule
1301:7-7-80
of the Administrative Code.
(9)
914.9
Application of flammable finishes.
An
automatic sprinkler system or fire-extinguishing system shall be provided in
all spray, dip and immersing spaces and storage rooms, and shall be installed
in accordance with this rule.
(10)
914.10
Drying rooms.
Drying rooms designed for
high-hazard materials and processes, including special occupancies as provided
for in chapter 4 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, shall be protected by an approved
automatic fire-extinguishing system complying with the provisions of
this rule.
(11)
914.11
Ambulatory care facilities.
Occupancies
classified as ambulatory care facilities shall comply with
paragraphs (N)(11)(a)(914.11.1) to
(N)(11)(c)(914.11.3) of this rule.
(a)
914.11.1
Automatic sprinkler systems.
An automatic
sprinkler system shall be provided for ambulatory care facilities in accordance
with paragraph (C)(2)(b)(903.2.2) of this
rule.
(b)
914.11.2 Manual fire alarm systems.
A manual fire alarm system shall be provided for
ambulatory care facilities in accordance with paragraph
(G)(2)(b)(907.2.2) of this rule.
(c)
914.11.3
Fire alarm systems.
An automatic smoke
detection system shall be provided for ambulatory care facilities in accordance
with paragraph (G)(2)(b)(i)(907.2.2.1) of this
rule.
(P)
Section 916 Fire protection and
fire-fighting equipment certification
(1)
916.1
No person shall sell, offer for sale, or use any fire
protection or fire-fighting equipment which does not meet the minimum standards
for such equipment as specified in this code.
(2)
916.2
Except for public and private mobile fire trucks, no person
shall engage in the business of servicing, testing, repairing, or installing
fire protection or fire-fighting equipment for profit without first being
certified by the state fire marshal, as required by section
3737.65 of the Revised Code and
this code.
(3)
916.3 Terms defined for this
paragraph.
The following
words take on exclusive meanings as used in this paragraph of this rule
only.
"Company."
Any individual, sole proprietorship, partnership,
association, or corporation certified pursuant to this
rule.
"Company
branch."
A separate but
dependent office of a company certified pursuant to paragraph (P)(18)( 916.18)
of this rule that operates at a different address than the
company.
"Provisional
individual."
Any person
enrolled in a bona fide apprenticeship training program registered with the
apprenticeship council pursuant to section 4139.08 of the Revised Code or with
the bureau of apprenticeship and training of the United States department of
labor.
(4)
916.4 Individual and provisional
individual certification.
Upon satisfactory application and examination pursuant to
paragraphs
(P)(6)( 916.6) and (P)(7)(
916.7) of this rule, the state fire marshal may certify any individual
or provisional individual to service, test, repair or install fire protection
or fire-fighting equipment in the following categories:
(a)
Automatic
sprinkler and standpipe systems;
(b)
Fire
service mains and water tanks;
Exception:
Excavation and earth moving equipment operators are not
required to be certified in this category provided the work they perform to
meet the requirements of NFPA 22 and 24 is conducted under the direct
supervision and active direction of an individual certified in this category
(who remains on site while the work is
performed.)
(c)
Fire
pumps;
(d)
Fire alarm and detection
equipment;
(e)
Household fire warning equipment
only;
(f)
Portable fire
extinguishers;
(g)
Engineered extinguishing equipment other than
water;
(h)
Pre-engineered extinguishing equipment other
than water;
(i)
Fire pump diesel
technician;
(j)
Aerosol extinguishing equipment;
or
(k)
Such other categories as deemed necessary by the state fire
marshal.
(5)
916.5
"Satisfactory
application" includes, but is not limited to:
1.
The
provision to the state fire marshal of all information requested by the fire
marshal or required by this rule;
2.
The
provision to the state fire marshal of documentation describing the applicant's
recent work history relating to fire protection installer work or similar
construction trade experience including, upon request of the state fire
marshal, evidence that any work performed was completed with certified
individuals and in compliance with applicable codes.
(a)
916.5.1.
If the state
fire marshal has obtained evidence that the applicant, within two years prior
to the date of examination, engaged in unauthorized fire protection installer
work, the state fire marshal may deny the application. If the state fire
marshal has obtained evidence that a renewal applicant, within two years of the
date of renewal application, has engaged in fire protection installer work
performed in violation of the applicable codes, the state fire marshal may deny
the renewal application.
(6)
916.6
Those seeking certification to work on a particular
engineered or pre-engineered system must show at least one of the
following:
(a)
Proof from the manufacturer of training or approval to work
on the manufacturers engineered or pre-engineered system;
or
(b)
Documentation demonstrating that the applicant has witnessed
the code compliant installation of ten engineered or pre-engineered systems
within two years immediately prior to making application. The documentation
shall include the license number of the individual performing such
installation, type of system, date and location of
installation.
(7)
916.7
Except for provisional individuals, the state fire marshal
shall require all applicants to obtain a passing grade of at least seventy per
cent on a fire protection installer examination administered by the state fire
marshal prior to certification. The state fire marshal may administer the
examination by procuring or engaging a third party to provide testing services.
Fees for the examination may be assessed.
(8)
916.8
An
individual may only work in those categories for which he has been certified
pursuant to paragraph
(P)(4)( 916.4)
of this rule.
(9)
916.9
An
individual must be a company certified pursuant to paragraph
(P)(4)( 916.4) of this rule or must be
associated with a certified company when such individual engages in the
business of servicing, testing, repairing or installing fire protection or
fire-fighting equipment for profit.
(10)
916.10
Individuals may only work on those particular engineered or
pre-engineered systems for which the individual has recent experience or
education to show competence and has provided documentation thereof to the
state fire marshal. Individuals may only engage in the servicing, testing, or
repairing of any fire protection or fire-fighting equipment if they are
knowledgeable and experienced in the testing, maintenance and servicing
requirements of the equipment and of the testing, service or maintenance
methods of the equipment being worked on. Entities who engage persons to work
on engineered or pre-engineered systems or to test, service, repair or provide
maintenance on fire protection or fire-fighting equipment shall only engage
competent and qualified individuals for work.
(11)
916.11
Every certified individual shall carry the certificate
issued pursuant to paragraph
(P)(916)
of this rule on their person while engaging in the business of
servicing, testing, repairing or installing fire protection or fire-fighting
equipment for profit and produce the certificate for inspection upon request by
the fire code official.
(12)
916.12
A provisional individual must be supervised by a certified
individual at all times such provisional individual is engaging in work
requiring certification. The certified individual directly supervising the
individual issued the provisional certificate shall only supervise one
provisional certificate holder while engaging in work requiring certification.
The certified individual directly supervising the provisional certificate
holder shall possess a valid and current certificate for the certification
category of the work being performed.
(13)
916.13
Applications for certification and renewals shall be made on
forms provided by the state fire marshal. All applications and renewals shall
be accompanied by the appropriate fee, to be made payable to "Treasurer, State
of Ohio."
(14)
916.14
Original application for certification and renewal of an
individual or provisional individual shall, at a minimum, include the
following:
(a)
Name of applicant;
(b)
Categories for which applicant is seeking
certification;
(c)
If a non-resident of Ohio, an irrevocable
consent to legal service in Ohio (needed for original application
only);
(d)
If for a provisional individual, a copy of the
indenture agreement;
(e)
Documentation describing the applicant's recent work history
relating to fire protection installer work or similar construction trade
experience; and
(f)
Any other information requested by the state
fire marshal.
(15)
916.15
Fees for an individual or provisional certification shall be
as follows:
(a)
Original application of an individual or provisional
individual shall be thirty-five dollars for each category for which
certification is sought;
(b)
Renewal
of an individual or provisional individual shall be forty
dollars;
(c)
An application for a duplicate license shall be
made in writing to the state fire marshal. The application for a duplicate
license shall be accompanied by a ten-dollar fee.
(16)
916.16
Applications for renewal must be received by the state fire
marshal prior to the expiration date. Individual certification licenses and
company certification of an individual operating alone expire in accordance
with the following schedule:
(a)
Last name
beginning with "a-g" on January second of each year;
(b)
Last name
beginning with "h-m" on April first of each year;
(c)
Last name
beginning with "n-s" on July first of each year;
(d)
Last name
beginning with "t-z" on October first of each
year.
(17)
916.17
Upon expiration of certification, all applications for
renewal will be considered as a new application and the applicant shall be
required to pass a fire protection installer examination administered by the
state fire marshal prior to certification.
(18)
916.18
Upon satisfactory application, the state fire marshal may
certify any company to engage in the business of servicing, testing, repairing,
and installing fire protection and fire-fighting equipment. A company
certification authorizes a company to engage in fire protection installer work
only for those fire protection installer categories for which its employees are
certified pursuant to this rule.
(19)
916.19
Original application for certification and renewal of a
company shall, at a minimum, include the following:
(a)
Name of
applicant;
(b)
The primary business address of the
company;
(c)
Names of all persons responsible for the normal
operations of the company (e.g., officers of the corporation, partners,
etc.);
(d)
Proof of liability insurance or bonding in an
amount of at least fifty thousand dollars for completion and/or performance
purposes;
(e)
If a non-resident, an irrevocable consent to
legal service in Ohio (needed for original application only);
and
(f)
Any other information requested by the state fire
marshal.
(20)
916.20
Fees for a company certification shall be as
follows:
(a)
Original application of a company shall be two hundred
dollars, except that an individual operating as a company shall be required to
pay a fee of fifty dollars.
(b)
Renewal
of a company shall be one hundred fifty dollars, except that an individual
operating as a company shall be required to pay a fee of twenty-five dollars.
All renewal applications not submitted prior to the date of expiration, shall
pay new application fees in accordance with paragraph (P)(20)(a)( 916.20) of
this rule.
(c)
An application for a duplicate license shall be
made in writing to the state fire marshal. The application for a duplicate
license shall be accompanied by a ten-dollar fee.
(d)
The
original application for a company branch certificate shall be made in writing
to the state fire marshal. The application fee for a company branch certificate
shall be ten dollars per company branch certificate.
(i)
A company
branch certificate status is contingent upon the status of the company and
shall only operate if the company maintains a valid certificate.
(ii)
A branch is not required to pay renewal fees
separate from the company. A company branch certificate is automatically
renewed upon the satisfactory and approved renewal of the company unless
otherwise indicated in writing by the company.
(iii)
The
company is responsible for any fire protection installation or fire-fighting
equipment business conducted out of or in association with a company
branch.
(21)
916.21
All company certification licenses expire June thirtieth of
each year. Renewal shall be pursuant to standard renewal procedure. Upon
expiration of certification, all applications for renewal received by the state
fire marshal thereafter shall be considered as a new application and the
company applicant shall pay new application fees in accordance with paragraph
(P)(20)( 916.20) of this rule.
(22)
916.22
Any certified
individual or certified company that changes its primary mailing address as
previously filed with the state fire marshal or that experiences expiration of
required insurance coverage, shall submit written notification of such change
of address or insurance expiration to the state fire marshal within thirty days
of the change of address or insurance expiration. A certified company or the
company branch shall submit written notification to the state fire marshal of a
company branch office's address change or closure within thirty days of such
change or closure.
(23)
916.23
An
application for any certificate issued pursuant to paragraph
(P)(916) of this rule may be denied, or a
certificate issued pursuant to paragraph (P)(916) of this rule
may be suspended or revoked, for cause by the state fire marshal. Denial,
suspension or revocation for cause includes, but is not limited to, any of the
following reasons:
(a)
For knowingly committing an act that violates
any provision of the "Ohio Building Code," the "Ohio Fire Code," or the Revised
Code;
(b)
For engaging in or permitting a person to
engage in activity requiring certification, but for which activity the person
is not certified;
(c)
For gross
negligence or gross incompetence;
(d)
For
knowingly making any misrepresentation or false promise, or for dishonest or
illegal dealing;
(e)
For a continued course of misrepresentation or
the making of false promises individually, through employees or agents, through
advertising, or otherwise;
(f)
For
failure to notify the state fire marshal of a change of primary mailing
address;
(g)
In the case of a company, for failure to
maintain the liability insurance or bonding in an amount of at least fifty
thousand dollars for completion and/or performance
purposes;
(h)
In the case of a provisional individual, for
failure to complete the apprenticeship program or failure to maintain
enrollment in the apprenticeship training program; or
(i)
In the
case of a company, for failure to notify the state fire marshal upon expiration
of the required insurance coverage or of any changes to the information
required by paragraph
(P)(22)( 916.22)
of this rule or for failure to provide satisfactory evidence
documenting such changes to the required
information.
(24)
916.24
The state fire marshal shall comply with the provisions of
Chapter 119. of the Revised Code whenever denying, suspending or revoking a
certificate pursuant to paragraph
(P)(23)( 916.23) of this
rule.
(25)
916.25
No person who has been denied certification, or whose
certification is under suspension or revocation pursuant to
paragraph
(P)(23)( 916.23) of
this rule, may be associated with any company certified pursuant to paragraph
(P)(916) of this rule.
(26)
916.26
If an application for certification is denied, or if a
certification issued pursuant to paragraph
(P)(916) of this rule is suspended or revoked,
the company, company branch, or individual shall immediately cease engaging in
the business of servicing, testing, repairing or installing fire protection or
fire-fighting equipment for profit. If a certification is denied, suspended or
revoked, that company or a company that had its certification denied, suspended
or revoked, or an individual who had their certification denied, suspended or
revoked, may not reapply for certification pursuant to paragraph
(P)(916) of this rule until the suspension is lifted or until two years
expire from the date of denial or revocation of certification.
Exception: A company that
had its certification denied or an individual who had their certification
denied solely for failure to submit a complete application, may reapply for
certification pursuant to paragraph
(P)(916) of this rule without waiting for two years
to expire from the date of denial of
certification.
Replaces: 1301:7-7-09