Chapter 13 of the International
Building Code, 2021 edition, as incorporated by reference, is further modified
as follows:
(A)
Replace section 1301.1.1 with the following:
1301.1.1
Criteria.
Buildings are
to be designed and constructed in accordance with the applicable provisions of
the "International Energy Conservation Code" or the requirements of "ASHRAE
90.1" listed in Chapter 35 of this code except as modified in Sections
1301.2 and
1301.3.
(B)
Add new section
1301.2 that reads as
follows:
1301.2
Modifications to the International Energy Conservation
Code.
The following changes are made to
the International Energy Conservation Code:
Residential
Provisions
1.
Section R403.3.7 is to read:
"
Building cavities
(Mandatory).
Building framing cavities are
not to be used as supply ducts."
Commercial
Provisions
1.
Add a new paragraph at the end of
Section C402.1 General
that reads: "Compliance with ACI/TMS 122.1 is permitted for
mitigating the effects of thermal bridges in concrete or masonry
assemblies."
2.
Section C405.11 Automatic Receptacle Control:
Delete section and subsections.
3
. Section
C405.12 Energy Monitoring:
Delete section
and subsections.
4.
Chapter 6 Referenced Standards:
Add promulgating agencies American Concrete Institute
(ACI), 38800 Country Club Drive, Farmington Hills, MI 48331 and The Masonry
Society (TMS), 105 South Sunset Street, Suite Q, Longmont, CO 80501 and
Referenced standard ACI-TMS Code 122.1-21 titled
Thermal
Bridge Mitigation for Buildings having Concrete and Masonry Walls and Masonry
Veneer- Code Requirements and Commentary.
(C)
Add new section
1301.3 that reads as
follows:
1301.3
Modifications to ASHRAE 90.1.
The following changes are made to the ASHRAE
90.1:
1.
Section 5.1.2.3 Space Conditioning Categories:
Add a new exception 2 to read as follows:
"Building and portions of buildings
used for industrial or manufacturing purposes that are not cooled and where the
energy use of the industrial or manufacturing processes exceeds 80 percent of
the total energy use of the building may be considered as a
semiheated space
for
the purposes of thermal envelope requirements."
2.
Add new
Section 5.2.3 Thermal bridging mitigation that
reads as follows:" Compliance with ACI/TMS
122.1 is permitted for mitigating the effects of thermal bridges in concrete or
masonry assemblies."
3.
Section 8.4.2 Automatic Receptacle
Control:
Delete
section.
4.
Section 8.4.3 Electrical Energy Monitoring:
Delete section and
subsections.
5.
Section 12 Normative References:
Add promulgating agencies American Concrete Institute
(ACI), 38800 Country Club Drive, Farmington Hills, MI 48331 and The Masonry
Society (TMS), 105 South Sunset Street, Suite Q, Longmont, CO 80501 and
Normative reference ACI-TMS Code 122.1-21 titled
Thermal
Bridge Mitigation for Buildings having Concrete and Masonry Walls and Masonry
Veneer- Code Requirements and Commentary.
Replaces: 4101:1-13-01
Notes
Ohio Admin. Code 4101:1-13-01
Effective:
3/1/2024
Five Year Review (FYR) Dates:
03/01/2029
Promulgated
Under: 119.03
Statutory Authority: 3781.10(A)(1)
Rule
Amplifies: 3781.10, 3781.11, 3791.04
Prior Effective Dates:
09/06/2005, 07/01/2007, 11/01/2011, 07/01/2014, 01/01/2017,
11/01/2017