Ohio Admin. Code 901:5-2-10 - New permanent storage vessels erected on site
(A) After January
1, 2002, no person shall either erect on site or cause to be erected on site a
new permanent storage vessel unless;
(1) It
is built to:
(a) The API 650 standard; or
(b) Exceed the API 650 standard.
If the vessel is to be built to exceed the API 650 standard, plans and
specifications for the vessel shall be submitted to the director prior to
installation of the vessel. The plans and specifications submitted under this
section shall include documentation prepared by a professional engineer
registered under Chapter 4733. of the Revised Code of the following:
(i) That the permanent storage vessel to be
installed exceeds the API 650 standard; and
(ii) The inspection schedule, protocol, and
standards against which the integrity of the permanent storage vessel shall be
measured during those inspections over the lifetime of the vessel; and
(iii) The protocol and
specifications required for proper repairs to the permanent storage vessel;
(2) The
storage vessel and appurtenances meet the requirements of paragraphs (A) and
(B) of rule
901:5-2-03
of the Administrative Code;
(3) It
is sited within a secondary containment facility, which meets the requirements
of paragraph (C) of rule
901:5-2-03
of the Administrative Code;
(4)
The plans and specifications for the secondary containment facility have first
been approved in accordance with rule
901:5-2-02
of the Administrative Code by the director of agriculture; and,
(5) It complies with all applicable zoning
regulations, building standards, and fire codes; and, any permits required by
state or federal law have been issued.
(B) The director shall notify each applicant
within thirty days after receipt of the plans and specifications for the
containment facility that they have either been approver or disapproved.
(C) Before the vessel may be used
for liquid fertilizer storage the owner shall obtain a written verification
from an authorized inspector stating that the vessel, as installed, is in
compliance with the paragraph (A)(1) of this rule. The written verification
shall be kept on the property where the vessel is located and a copy shall be
submitted to the Ohio department of agriculture.
(D) For permanent storage vessels:
(1) Built to API 650 standards, after the
date an initial written verification of compliance is issued for a new
permanent storage vessel erected on site the vessel shall be reinspected every
ten years in accordance with and shall comply with the requirements of:
(a) Paragraph (B) of rule
901:5-2-09
of the Administrative Code; or,
(b) If a permanent storage vessel erected on
site does not meet the API 650 standard, the owner of the vessel shall obtain
from the authorized inspector written verification indicating non-compliance
and listing each item not in compliance with the API standard 650. The owner
shall notify the department of the non-compliance and neither the owner nor any
other person shall use the vessel to hold liquid fertilizer until the vessel is
brought into compliance and a written verification is issued by an authorized
inspector stating the vessel is in compliance with the API 650 standards. When
a written verification of compliance is issued it shall be kept on the property
where the vessel is located.
(2) Built to exceed API 650 standards, after
the date an initial written verification of compliance is issued for a new
permanent storage vessel erected on site, the vessel shall be reinspected in
accordance with the schedule, protocol and standards for inspection submitted
pursuant to paragraph (A)(1)(b)(ii) of this rule. If the vessel does not meet
the standard to which it was built, the owner of the vessel shall obtain from
the authorized inspector written verification indicating that non-compliance
and listing each item not in compliance with the standard documented under
paragraph (A)(1)(b) of this rule. The owner shall notify the department of the
non-compliance and neither the owner nor any other person shall use the vessel
to hold liquid fertilizer until the vessel is brought into compliance and a
written verification is issued by an authorized inspector stating the vessel is
in compliance with the standards under which it was built. When a written
verification of compliance is issued it shall be kept on the property where the
vessel is located.
If an authorized inspector determines that a shorter inspection interval is necessary, subsequent inspections shall be conducted in accordance with that interval.
Notes
Promulgated Under: 119.03
Statutory Authority: 905.44
Rule Amplifies: 905.44
Prior Effective Dates: 11-12-01; 11/21/2007