Or. Admin. Code § 333-535-0270 - Details and Finishes
(1) The
nonconforming portions of existing facilities that are not being totally
modernized shall comply with the safety requirements dealing with interior
finishes as listed in chapters 18, 19, 20 and 21 of the National Fire
Protection Association (NFPA) 101, when the facility is also to be Medicare or
Medicaid certified.
(2) Details and
finishes in new construction projects, including additions and major
alterations, shall comply with the following:
(a) Details:
(A) Compartmentation, exits, fire alarms,
automatic extinguishing system, and other details relating to fire prevention
and fire protection shall comply with requirements listed in chapters 18, 19,
20 and 21 of the NFPA101, when the facility is also to be Medicare or Medicaid
certified.
(B) Items such as
drinking fountains, telephone booths, vending machines, and portable equipment
shall be located so as not to restrict corridor traffic or reduce the corridor
width below the required minimum.
(C) Rooms containing any of the following:
bathtubs, sitz baths, showers, or water closets, subject to occupancy by
patients, shall be equipped with doors and hardware that will permit access
from the outside in any emergency. When such rooms have only one opening, the
door shall be capable of opening outward or be otherwise designed to be opened
without need to push against a patient who may have collapsed within the
room.
(D) If psychiatric care units
are required by the program, suitable hardware shall be provided on doors to
patient toilet rooms so that access to these rooms can be controlled by
staff.
(E) If required by the
program, doors to patient rooms in psychiatric care units shall not be lockable
from inside the room.
(F) Windows
and other doors that may be frequently left in an open position shall be
provided with insect screens.
(G)
Patient rooms intended for occupancy of 24 hours or more shall have windows
with sills not more than 3 feet above the floor (windows in Intensive Care Unit
and Critical Care Unit may be 5 feet above the floor).
(H) Linen and refuse chutes shall meet
requirements of NFPA101, and have a minimum cross sectional dimension of not
less than 2 feet.
(I) Thresholds
and expansion joint covers shall be made flush with the floor surface to
facilitate use of wheelchairs and carts. Expansion joints shall be constructed
to restrict passage of smoke and fire.
(J) Grab bars shall be provided at all
patients' toilets, showers, tubs, and sitz baths, except in psychiatric patient
care units. The bars shall have one and one-half inch clearance to walls and
shall have sufficient strength and anchorage to sustain a concentrated load of
250 pounds.
(K) Anchoring. Sinks in
hand-washing stations shall be securely anchored to withstand an applied
vertical load of not less than 250 pounds on the fixture front.
(L) Mirrors shall not be installed at
hand-washing stations in food preparation areas or in sensitive areas such as
nurseries, clean and sterile utility, storage rooms and scrub sinks.
(M) Hand drying devices. Provision for hand
drying shall be included at all hand-washing stations except scrub sinks.
Hospital policy shall determine hand drying procedures at scrub sink locations.
These shall be single use separate individual paper or cloth units enclosed in
such a way as to provide protection against dust or soil and insure single unit
dispensing. Hot air dryers are permitted provided that installation is such to
preclude possible contamination by recirculation of air.
(N) Radiation protection requirements for
Radiographic Imaging and gamma ray installations shall be in accordance with
National Council of Radiation Protection Reports Numbers 33 and 49. Provision
shall be made for testing the completed installation before use and all defects
must be corrected before acceptance. Prior to their use, all installations
shall be approved and licensed by the Radiation Control Section of the Oregon
Health Authority, Public Health Division.
(O) The minimum ceiling height shall be 7
feet 10 inches with the following exceptions:
(i) Boiler rooms shall have ceiling
clearances not less than 2 feet 6 inches above the main boiler header and
connecting piping.
(ii)
Radiographic, operating and delivery rooms, and other rooms containing
ceiling-mounted equipment or ceiling-mounted surgical light fixtures shall have
height required to accommodate the equipment or fixtures.
(iii) Ceilings in corridors, storage, toilet
rooms, and other minor rooms shall be not less than 7 feet 6 inches.
(iv) Soffits, signage, lights, mechanical
items and other suspended items located in the path of normal traffic shall not
be less than 7 feet above the floor. Cubicle curtain tracks and television
suspensions in individual rooms shall not be less than 6 feet 8 inches above
the floor.
(P) Recreation
rooms, exercise rooms and similar space where impact noises may be generated
shall not be located directly over patient bed area, delivery or operating
suites, unless special provisions are made to minimize such noise.
(Q) Rooms containing heat-producing equipment
(such as boiler or heater rooms and laundries) shall be insulated and
ventilated to prevent any floor surface above from exceeding a temperature of
10°F above the ambient room temperature of the room producing the heat
generation.
(R) Sound transmission
criteria shown in Table 1 (OAR 333-535-0270) shall apply to partition, floor
and ceiling construction in patient areas.
(S) Mechanical equipment located on the same
floor or above patient rooms, offices, nurse stations, and similar occupied
spaces shall be effectively sound isolated from the floor and
structure.
(T) Equipment and supply
storage shall be provided for each hospital department in accordance with the
Functional Program; however, a minimum of 10 square feet per bed shall be
provided in patient care areas. In all other departments, the amount required
shall be based on either a study of supply and equipment needs which shall be
submitted with construction plans for review or a minimum of 10 percent of
gross departmental area. All rooms and corridors within a department shall be
included when calculating gross departmental area.
(b) Finishes:
(A) Cubicle curtains and draperies shall be
noncombustible or rendered flame retardant and shall pass both the large and
small scale tests of NFPA Standard 701.
(B) Flame spread and smoke developed ratings
of finishes are covered under the State of Oregon Building Code. Whenever
possible, the use of materials known to produce large amounts of noxious gases
shall be avoided.
(C) Floor
materials shall be easily cleanable and have wear resistance appropriate for
the location involved. Floors in areas used for food preparation or food
assembly shall be water-resistant and grease-proof. Joints in tile and similar
material in such areas shall be resistant to food acids. In all areas
frequently subject to wet cleaning methods, floor materials shall not be
physically affected by germicidal and cleaning solutions. Floors that are
subject to traffic while wet (such as shower and bath areas, kitchens,
operating and C-section rooms, clean core areas, recovery areas except
step-down recovery and similar work areas) shall have a non-slip surface as
recommended by Americans with Disabilities Act, Architectural and
Transportation Barriers Compliance Board (Access Board).
(D) Wall bases in kitchens, operating and
C-section rooms, clean core areas, surgical scrub corridors, soiled workrooms,
endoscopy rooms, housekeeping closets and other areas that are frequently
subject to wet cleaning methods shall be made integral and coved with the
floor, tightly sealed to the wall, and constructed without voids that can
harbor insects.
(E) Wall finishes
shall be washable and, in the immediate area of plumbing fixtures, shall be
smooth and moisture resistant (orange peel not allowed). Finish, trim, and
floor and wall construction in dietary and food preparation areas shall be free
from spaces that can harbor rodents and insects.
(F) Floor and wall penetrations by pipes,
ducts, and conduits shall be tightly sealed to minimize entry of rodents and
insects. Joints of structural elements shall be similarly sealed.
(G) Ceilings in restricted areas such as:
surgery rooms, delivery rooms, clean core areas and specialized radiographic
rooms shall be constructed with material that are monolithic, scrubbable, and
capable of withstanding chemicals, such as gypsum board, and be without
crevices that can contain dirt particles.
(H) Ceilings in semi-restricted areas such
as: airborne infection isolation rooms, protective environment rooms and
central sterile supply spaces shall be smooth, scrubbable, nonabsorptive,
nonperforated, capable of withstanding cleaning with chemicals, and without
crevices that can harbor mold and bacterial growth.
(I) If lay-in ceiling is provided in
semi-restricted areas, it shall be gasketed or clipped down to prevent the
passage of particles from the cavity above the ceiling plane into the
semi-restricted environment. Perforated, tegular, serrated cut, or highly
textured tiles are not acceptable.
(J) Dietary and food preparation areas shall
have a finished ceiling covering all overhead duct work and piping.
(K) Finished ceilings may be omitted in
general storage areas, and similar spaces, unless required for fire-resistive
purposes.
(L) Acoustical ceilings
shall be provided for corridors in patient areas, nurses' stations, labor
rooms, day rooms, recreation rooms, dining areas, and waiting areas.
(M) In dietary areas and in other areas where
dust fallout may present a problem, suspended ceilings shall be
provided.
(N) Ceilings of patient
rooms in psychiatric care units shall be of monolithic or bonded
construction.
(O) Top-set rubber or
vinyl wall base, where used, shall be sealed tightly to the floor as well as to
the wall.
Notes
Tables & Publications referenced are available from the agency.
To view tables referenced in rule text, click here to view rule.
Statutory/Other Authority: ORS 441.060
Statutes/Other Implemented: ORS 441.060
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.