Or. Admin. Code § 437-004-0716 - Oxygen
(1) Scope. This
applies to the installation of bulk oxygen systems on agricultural
establishments.
(2) Bulk oxygen
systems.
(a) Definition. A bulk oxygen system
is an assembly of equipment, such as oxygen storage containers, pressure
regulators, safety devices, vaporizers, manifolds, and interconnecting piping,
with storage capacity more than 13,000 cubic feet of oxygen, Normal Temperature
and Pressure (NTP), connected in service or ready for service, or more than
25,000 cubic feet of oxygen (NTP) including unconnected reserves on hand at the
site. The bulk oxygen system ends where oxygen at service pressure first enters
the supply line. The oxygen containers may be stationary or movable, and the
oxygen may be gas or liquid.
(b)
Location.
(A) General. Bulk oxygen storage
systems must be above ground, outdoors or in a noncombustible building,
adequately vented and used exclusively for oxygen storage. Locate containers
and associated equipment so there is no exposure to electric power lines,
flammable or combustible liquid lines, or flammable gas lines.
(B) Accessibility. Locate the system so that
it is readily accessible to mobile supply equipment at ground level and to
authorized personnel.
(C) Leakage.
For liquid oxygen storage, provide noncombustible surfacing in the area where
any leakage might fall during operation of the system and filling of the
container. Asphalt or bituminous paving is combustible.
(D) Elevation. When locating bulk oxygen
systems near above-ground flammable or combustible liquid storage that may be
either indoors or outdoors, it is advisable to locate the system on ground
higher than the flammable or combustible liquid storage.
(E) Dikes. When a bulk oxygen system must be
lower than adjacent flammable or combustible liquid storage, there must be
suitable means (such as diking, diversion curbs, or grading) to prevent
accumulation of liquids under the bulk oxygen system.
(c) Distance between systems and exposures.
(A) The minimum distance from any bulk oxygen
storage container to exposures, measured in the most direct line except as in
(2)(c)(A)(v) and (vii) below, must be as follows:
(i) Fifty feet from combustible
structures.
(ii) Twenty-five feet
from structures with fire-resistive exterior walls or sprinklered buildings of
other construction, but not less than one-half the height of the adjacent side
wall of the structure.
(iii) At
least 10 feet from any opening in adjacent walls of fire resistive structures.
Spacing from such structures must be adequate to permit maintenance, but not be
less than 1 foot.
(iv) Flammable
liquid storage above-ground. [Table not included. See ED. NOTE.]
(v) Flammable liquid storage below-ground.
[Table not included. See ED. NOTE.]
(vi) Combustible liquid storage above-ground.
[Table not included. See ED. NOTE.]
(vii) Combustible liquid storage below
ground. [Table not included. See ED. NOTE.]
(viii) Flammable gas storage. (Such as
compressed flammable gases, liquefied flammable gases and flammable gases in
low pressure gas holders). [Table not included. See ED. NOTE.]
(ix) Fifty feet from solid materials that
burn rapidly, such as excelsior or paper.
(x) Twenty-five feet from solid materials
that burn slowly, such as coal and heavy timber.
(xi) Seventy-five feet in one direction and
35 feet in approximately 90° direction from confining walls (not including
firewalls less than 20 feet high) to provide adequate ventilation in courtyards
and similar confining areas.
(xii)
Twenty-five feet from areas such as offices, lunchrooms, locker rooms, time
clock areas, and similar locations where people may gather.
(B) Exceptions. The distances in
(2)(c)(A)(i), (ii), (iv) to (x) above, do not apply where there are protective
structures, like firewalls, between the bulk oxygen storage installation and
the exposure high enough to safeguard the oxygen storage systems. In those
cases, the bulk oxygen storage installation may be a minimum distance of 1 foot
from the firewall.
(d)
Storage containers.
(A) Permanently installed
containers must be on substantial noncombustible supports on firm
noncombustible foundations.
(B)
Make liquid oxygen storage containers from materials meeting the impact test
requirements of paragraph UG-84 of ASME Boiler and Pressure Vessel Code,
Section VIII - Unfired Pressure Vessels - 1968. Containers operating at
pressures more than 15 pounds per square inch gage (p.s.i.g.) must comply with
ASME Boiler and Pressure Vessel Code, Section VII - Unfired Pressure Vessels -
1968. Insulation on the liquid oxygen container must be
noncombustible.
(C) High-pressure
gaseous oxygen containers must comply with one of the following:
(i) ASME Boiler and Pressure Vessel Code,
Section VIII - Unfired Pressure Vessels - 1968.
(ii) DOT Specifications and
Regulations.
(e) Piping, tubing, and fittings.
(A) Piping, tubing, and fittings must be
suitable for oxygen service and for the pressures and temperatures
involved.
(B) Piping and tubing
must conform to Section 2 - Gas and Air Piping Systems of Code for Pressure
Piping, American National Standard (ANSI), B31.1-1967 with addenda
B31.10a-1969.
(C) Fabricate piping
or tubing for operating temperatures below 20° F. from materials meeting
the impact test requirements of paragraph UG-84 of ASME Boiler and Pressure
Vessel Code, Section VIII - Unfired Pressure Vessels - 1968, when tested at the
anticipated minimum operating temperature.
(f) Safety relief devices.
(A) Equip bulk oxygen storage containers,
regardless of design pressure, with safety relief devices required by the ASME
code or the DOT specifications and regulations.
(B) Bulk oxygen storage containers designed
and constructed according to DOT specifications must have safety relief devices
as required.
(C) Bulk oxygen
storage containers that comply with the ASME Boiler and Pressure Vessel Code,
Section VIII - Unfired Pressure Vessel - 1968 must have safety relief devices
that comply with the Compressed Gas Association Pamphlet "Safety Relief Device
Standards for Compressed Gas Storage Containers," S-1, Part 3.
(D) Equip insulation casings on liquid oxygen
containers with suitable safety relief devices.
(E) Safety relief devices must not allow
moisture that would interfere with proper operation to collect and
freeze.
(g) Liquid
oxygen vaporizers.
(A) Anchor the vaporizer
and use connecting piping sufficiently flexible to compensate for expansion and
contraction due to temperature changes.
(B) Adequately protect the vaporizer and its
piping on the oxygen and heating medium sections with safety relief
devices.
(C) Heat used in an oxygen
vaporizer must be indirectly supplied only through media such as steam, air,
water or water solutions that do not react with oxygen.
(D) If electric heaters provide the primary
source of heat, ground the vaporizing system.
(h) Equipment assembly and installation.
(A) Remove oil, grease or other readily
oxidizable materials before placing the system in service.
(B) Make joints in piping and tubing by
welding or by using flanged, threaded, slip, or compression fittings. Gaskets
or thread sealants must be suitable for oxygen service.
(C) Valves, gages, regulators, and other
accessories must be suitable for oxygen service.
(D) People familiar with proper practices
must supervise the installation of bulk oxygen systems.
(E) After installation test and prove tight
all field erected piping at maximum operating pressure. Use oil-free,
non-flammable substances for testing.
(F) Protect storage containers, piping,
valves, regulating equipment, and other accessories from physical damage and
tampering.
(G) Adequately ventilate
enclosures for oxygen control or operating equipment.
(H) The bulk oxygen storage location must
have permanent placards that say: "OXYGEN - NO SMOKING - NO OPEN
FLAMES", or an equivalent warning.
(I) Bulk oxygen installations are not
hazardous locations as defined and covered in Division 4/S. Therefore, general
purpose or weatherproof types of electrical wiring and equipment are acceptable
depending on whether the installation is indoors or outdoors. Install this
equipment according to Division 4/S.
(i) For installations that require operation
of equipment by the user, keep legible instructions by the equipment.
(j) Cut back or clear combustible growth 15
feet from any bulk oxygen storage container.
Notes
The Table(s) referenced in this rule is not printed in the OAR Compilation. Copies are available from the agency.
Stat. Auth.: ORS 654.025(2) & ORS 656.726(3)
Stats. Implemented: ORS 654.001 - ORS 654.295
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.