Or. Admin. Code § 860-024-0016 - Minimum Vegetation Clearance Requirements
(1) For purposes of this rule:
(a) "Cycle Buster" means vegetation that will
not make it through the routine trim cycle without encroaching on the required
minimum clearances and, therefore require pruning midterm before the routine
cycle is completed.
(b) "Readily
climbable" means vegetation having both of the following characteristics:
(A) Low limbs, accessible from the ground and
sufficiently close together so that the vegetation can be climbed by a child or
average person without using a ladder or other special equipment; and
(B) A main stem or major branch that would
support a child or average person either within arms' reach of an uninsulated
energized electric line or within such proximity to the electric line that the
climber could be injured by direct or indirect contact with the line.
(c) "Vegetation" means trees,
shrubs, and any other woody plants.
(d) "Volts" means nominal voltage levels,
measured phase-to-phase.
(2) The requirements in this rule provide the
minimum standards for conductor clearances from vegetation to provide safety
for the public and utility workers, reasonable service continuity, and fire
prevention. Each Operator of electric supply facilities must have a vegetation
management program and keep appropriate records to ensure that timely trimming
is accomplished to keep the designated minimum clearances in section (4) below.
These records must be made available to the Commission upon request. If
clearances are not being maintained, the Commission may require the Operator to
implement an alternative vegetation management program and/or specific trim
cycles.
(3) Each Operator of
electric supply facilities must trim or remove readily climbable vegetation as
specified in section (4) of this rule to minimize the likelihood of direct or
indirect access to a high voltage conductor by a member of the public or any
unauthorized person.
(4) Under
reasonably anticipated operational conditions, an Operator of electric supply
facilities must maintain the following minimum clearances of vegetation from
conductors:
(a) Ten feet for conductors
energized above 200,000 volts.
(b)
Seven and one-half feet for conductors energized at 50,001 through 200,000
volts.
(c) Five feet for conductors
energized at 600 through 50,000 volts.
(A)
Clearances may be reduced to three feet if the vegetation is not readily
climbable.
(B) Intrusion of limited
small branches and new tree growth into this minimum clearance area is
acceptable provided the vegetation does not come closer than six inches to the
conductor.
(5) For conductors energized below 600 volts,
an Operator of electric supply facilities must trim vegetation to prevent it
from causing strain or abrasion on electric conductors. Where trimming or
removal of vegetation is not practical, the Operator of electric supply
facilities must install suitable material or devices to avoid insulation damage
by abrasion.
(6) In determining the
extent of trimming or vegetation removal required to maintain the clearances
required in section (4) of this rule, the Operator of electric supply
facilities must consider at minimum the following factors for each conductor:
(a) Voltage;
(b) Location;
(c) Configuration;
(d) Sag of conductors at elevated
temperatures and under wind and ice loading; and
(e) Growth habit, strength, and health of
vegetation (including rates of tree mortality) growing adjacent to the
conductor, with the combined displacement of the vegetation, supporting
structures, and conductors under adverse weather or routine wind conditions;
and
(f) The amount of trimming or
vegetation removal required to minimize Cycle Buster vegetation interference of
energized conductors.
(7) Each Operator of communications
facilities must ensure vegetation around communications lines do not pose a
foreseeable danger to the pole or electric supply Operator's
facilities.
Notes
Statutory/Other Authority: ORS 183, ORS 756, ORS 757 & ORS 758
Statutes/Other Implemented: ORS 757.035 & ORS 758.280 - 758.286
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.