25 Pa. Code § 109.607 - Pressures
(a) Distribution
systems and distribution system modifications shall be designed and constructed
to maintain normal operating pressures of not less than 25 p.s.i.g. nor more
than 125 p.s.i.g. at the main, except that during periods of peak seasonal
loads the pressures at the time of hourly maximum demand may be not less than
20 p.s.i.g. nor more than 150 p.s.i.g. and that during periods of hourly
minimum demand the pressure may be not more than 150 p.s.i.g.
(b) A public water system may furnish a
service which does not comply with the specifications in subsection (a) where
compliance with the specifications would prevent it from furnishing adequate
service to a customer or where called for by good engineering
practices.
(c) The Department may
require service improvements incorporating standards other than those set forth
in this section when it determines that the improvements are
necessary.