34 Pa. Code § 3a.162 - Portable boilers
(a) A portable
boiler must meet the requirements of §
3a.21 (relating to
stamping).
(b) A portable boiler
may be mounted in covered trailers if the following conditions are met:
(1) A 30-inch clearance is provided on both
ends of the boiler.
(2) The
boiler's trailer is provided with chocks and is anchored to prevent movement
during operation.
(3) The boiler is
anchored to the trailer.
(4) The
trailer provides a means or area to remove boiler tubes.
(5) The roof or the ceiling of the trailer
provides space to allow proper operation of all valves and
appurtenances.
(c) The
clearance on one side of a boiler mounted in a covered trailer may be reduced
to 3 inches if the trailer has access panels for removal of handhole plugs for
inspection and maintenance.
(d) The
user or operator shall notify the Department in writing and obtain written
Department approval before a portable boiler is moved and placed in
service.
(e) Inspection of portable
boilers shall be performed in accordance with §
3a.111(1)-(7)
(relating to field inspections).